Plan Review Details - Permit 22060055
Plan Review Stops For Permit 22060055 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2022-09-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-09-01 |
Time |
13:58 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-09-01 |
Time |
13:58 |
Sent To |
|
|
Notes |
2022-09-01 13:59:05 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC 107, PROVIDE A SURVEY AND SITE PLAN SHOWING | | PROPOSED LOCATION OF THE PROPOSED CONSTRUCTION TRAILER. | | | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-07-19 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-07-19 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-07-19 |
Time |
16:49 |
Sent To |
|
|
Notes |
2022-07-19 16:55:17 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC 107, SCOPE IS NOT CLEAR. YOU ARE PROPOSING TO | | INSTALL A "MOBILE OFFICE TRAILER" ON A RESIDENTIAL LOT. | | IT APPEARS THAT YOU MAY BE PROPOSING A TEMPORARY | | CONSTRUCTION TRAILER (EXEMPT FROM FLORIDA BUILDING CODE | | BUT NOT EXEMPT FROM ACCESSIBILITY), BUT THAT IS NOT THE | | PERMIT APPLICATION DESCRIPTION AND NOTHING IN THE | | SUBMITTAL INDICATES THAT. | | | | FBC ACCESSIBILITY, FBC B CHAPTER 10 - STAIR DETAIL DOES | | NOT COMPLY, NO RAMP SHOWN, NO ACCESSIBLE PARKING SPACE | | SHOWN, NO ACCESSIBLE ROUTE SHOWN | | | | IF THIS IS A TEMPORARY CONSTRUCTION TRAILER, EXEMPT | | FROM FBC, AND A LETTER IS PROVIDED STATING THAT NO | | MEETINGS WILL BE HELD ON SITE, THE ACCESSIBLE ROUTE IS | | NOT REQUIRED | | | | MODULARS TYPICALLY ARE REVIEWED BY THE STATE. HOWEVER | | THIS IS NOT REQUIRED IF THIS IS A TEMPORARY | | CONSTRUCTION TRAILER. | | | | TO RESOLVE, PLEASE SEND AN EMAIL CLARIFYING SCOPE AND | | INTENT FOR THIS MODULAR OFFICE. A NEW REVIEW WILL BE | | DONE AFTER FURTHER CLARIFICATION IS PROVIDED. | | | | 2. IF THIS IS NOT A TEMPORARY CONSTRUCTION TRAILER, | | IMPACT FEES WILL BE REQUIRED. | | | | 3. FS471, DOCUMENTS PREPARED BY AN ENGINEER AND | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED | | DATED ORIGINALS. IT APPEARS THIS IS A MODULAR, SO THERE | | ARE NO "PLANS", THERE IS ONLY AN APPROVAL FROM THE | | STATE. IF YOU ARE PROPOSING A STATE APPROVED MODULAR | | EMAIL [email protected], HAVE THE PAGES REMOVED | | FROM THE DRAWINGS FOLDER, UPLOAD ONE MULTIPAGE PDF TO | | SUPPORTING DOCS SHOWING THE STATE APPROVED MODULAR. | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2022-06-19 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2022-06-19 |
Time |
23:12 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2022-06-19 |
Time |
22:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2022-08-26 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-08-26 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-08-26 |
Time |
10:50 |
Sent To |
|
|
Notes |
2022-08-26 10:51:38 | THE PREVIOUS COMMENTS FROM FIRE WERE NOT ADDRESSED AND | | ARE RESUBMITTED BELOW. | | | | PLEASE ENSURE THE COMMENTS ARE ANSWERED AND COMPLY WITH | | THE REQUIREMENTS. | | | | | | ******************************************************* | | ***************************************** | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE IS NO INDICATION OF A SITE PLAN THAT LOCATES | | THE PROPOSED OFFICE TRAILER WITHIN THE SITE. | | | | PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE | | 4.2.1 SEPARATION DISTANCES, | | | | 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER | | CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH | | AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER | | FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS | | HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE | | IN ACCORDANCE WITH TABLE 4.2.1. | | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | NOTES: | | (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY | | STRUCTURES IS LESS THAN THE MINIMUM SEPARATION | | DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE | | CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING | | WALL LENGTHS OF THE TEMPORARY STRUCTURES. | | (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES | | SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL | | STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO | | MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE | | APPLYING THIS TABLE, IS 3600 MM (144 IN.). | | | | 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES, | | ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND | | PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE | | AUTHORITY HAVING JURISDICTION. | | | | | | FOR THE OFFICIAL RECORD PLEASE PROVIDE A SITE PLAN WITH | | ALL APPLICABLE DIMENSIONS TO THE PROPERTY LINES, | | BUILDINGS ON THE OTHER SIDE OF THE PROPERTY LINE, AND | | THE SITE PROPOSED BUILDING IN COMPLIANCE WITH NFPA | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2022-07-21 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-07-21 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-07-21 |
Time |
12:07 |
Sent To |
|
|
Notes |
2022-07-21 12:12:13 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE IS NO INDICATION OF A SITE PLAN THAT LOCATES | | THE PROPOSED OFFICE TRAILER WITHIN THE SITE. | | | | PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE | | 4.2.1 SEPARATION DISTANCES, | | | | 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER | | CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH | | AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER | | FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS | | HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE | | IN ACCORDANCE WITH TABLE 4.2.1. | | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | NOTES: | | (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY | | STRUCTURES IS LESS THAN THE MINIMUM SEPARATION | | DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE | | CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING | | WALL LENGTHS OF THE TEMPORARY STRUCTURES. | | (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES | | SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL | | STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO | | MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE | | APPLYING THIS TABLE, IS 3600 MM (144 IN.). | | | | 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES, | | ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND | | PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE | | AUTHORITY HAVING JURISDICTION. | | | | | | FOR THE OFFICIAL RECORD PLEASE PROVIDE A SITE PLAN WITH | | ALL APPLICABLE DIMENSIONS TO THE PROPERTY LINES, | | BUILDINGS ON THE OTHER SIDE OF THE PROPERTY LINE, AND | | THE SITE PROPOSED BUILDING IN COMPLIANCE WITH NFPA | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-09-02 |
|
|
Cont ID |
|
Sent By |
afowlkes |
Date |
2022-09-02 |
Time |
10:49 |
Rev Time |
0.00 |
Received By |
afowlkes |
Date |
2022-08-25 |
Time |
07:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-07-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-07-22 |
Time |
08:52 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-06-10 |
Time |
07:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2022-08-29 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-08-29 |
Time |
15:50 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-08-29 |
Time |
14:56 |
Sent To |
|
|
Notes |
2022-08-29 15:52:18 | 2ND REVIEW FBC-2020 PLUMBING | | PERMIT-22060055 | | 8/29/2022 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) RUBBER GARDEN HOSE IS NOT AN APPROVED MATERIAL FOR | | POTABLE WATER SERVICE USE- SEC. P2906.2.1 & TABLE | | P2906.4 FBC P. THE HOSE SHALL BE NSF 61 APPROVED AND | | LEAD FREE. | | | | WHEN RESUBMIITING PLEASE PROVIDE A SEPARATE PDF FOR THE | | SERVICE HOSE. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2022-06-13 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-06-13 |
Time |
12:18 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-06-13 |
Time |
11:47 |
Sent To |
|
|
Notes |
2022-06-13 12:19:08 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT-22060055 | | 6/13/2022 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE WATER SUPPLY AND SANITARY DRAINAGE PLANS FOR | | THE OFFICE TRAILER- SEC. 107.2.1 WPB. CLARIFY IF | | CONNECTIONS TO ONSITE UTILITIES ARE PROPOSED OR | | INSTALLATIONS OF POTABLE WATER SUPPLY AND SANITARY | | HOLDING TANKS WILL BE PROVIDED. PROVIDE A SITE PLAN | | SHOWING THE LOCATION OF THE TRAILER AND THE SYSTEMS, | | AND PIPIONG RUNS. SUBMIT MANUFACTURER'S SPECS FOR ALL | | PORTABLE TANKS IF USED INCLUDING A PUMP-OUT SCHEDULE | | FOR THE SANITARY HOLDING TANK. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
N |
Date |
2022-09-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-09-01 |
Time |
14:00 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-09-01 |
Time |
14:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2022-07-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-07-22 |
Time |
08:52 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-07-22 |
Time |
08:52 |
Sent To |
|
|
Notes |
2022-07-22 08:52:19 | SEE BUILDING REVIEW | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2022-09-02 |
|
|
Cont ID |
|
Sent By |
afowlkes |
Date |
2022-09-02 |
Time |
10:49 |
Rev Time |
0.00 |
Received By |
afowlkes |
Date |
2022-09-02 |
Time |
10:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2022-06-16 |
|
|
Cont ID |
|
Sent By |
afowlkes |
Date |
2022-06-16 |
Time |
15:37 |
Rev Time |
0.00 |
Received By |
afowlkes |
Date |
2022-06-16 |
Time |
15:37 |
Sent To |
|
|
Notes |
2022-06-16 15:38:26 | 06/16/22 FAILED - PLEASE SHOW ON A SURVEY WHERE THE | | TRAILER WILL BE LOCATED. | | | | PLEASE NOTE THE ADDITIONAL STANDARDS BELOW AS REQUIRED | | BY THE ZLDR'S | | TEMPORARY CONSTRUCTION OFFICES, STORAGE BUILDINGS, | | TRAILERS, AND WATCHMEN'S QUARTERS SHALL BE PERMITTED TO | | EXPEDITE CONSTRUCTION ON THE PROPERTY ON WHICH LOCATED. | | ALL SUCH STRUCTURES, INCLUDING TRAILERS, SHALL BE | | REMOVED WITHIN SEVEN DAYS OF THE FINAL CONSTRUCTION | | INSPECTION BY THE CITY AND PRIOR TO THE ISSUANCE OF A | | CERTIFICATE OF OCCUPANCY. | | | | ALEXANDER FOWLKES | | 5618221431 | | [email protected] |
|
|
|