Plan Review Details - Permit 22060009
Plan Review Stops For Permit 22060009
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-07-06 Cont ID  
Sent By pvalenti Date 2022-07-06 Time 10:29 Rev Time 0.00
Received By pvalenti Date 2022-07-06 Time 10:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-07-08 Cont ID  
Sent By pvalenti Date 2022-07-08 Time 15:43 Rev Time 0.00
Received By pvalenti Date 2022-07-08 Time 15:36 Sent To  
Notes
2022-07-08 15:44:23PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 THE FIRE RATING MUST BE MAINTAINED AT THE WALLS(DRYWALL
 BEHIND CEMENT BOARD) LOCATED AT THE NEW SHOWER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-07-06 Cont ID  
Sent By pvalenti Date 2022-07-06 Time 10:37 Rev Time 0.00
Received By pvalenti Date 2022-07-06 Time 10:33 Sent To  
Notes
2022-07-06 10:54:51PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 THE FIRE RATING MUST BE MAINTAINED AT THE WALLS(DRYWALL
 BEHIND CEMENT BOARD) LOCATED AT THE NEW SHOWER.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-07-08 Cont ID  
Sent By mpeterso Date 2022-07-08 Time 14:09 Rev Time 0.00
Received By mpeterso Date 2022-07-08 Time 14:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-06-23 Cont ID  
Sent By mpeterso Date 2022-06-23 Time 12:43 Rev Time 0.00
Received By mpeterso Date 2022-06-23 Time 12:43 Sent To  
Notes
2022-06-23 12:47:04ELECTRIC REVIEW FAILED
  
 1) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR,
 OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR OR
 PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3
 2) PLEASE DETAIL NEW ELECTRIC WORK TO BE IN COMPLIANCE
 WITH THE FOLLOWING,
 NEC 210.8 GFCI PROTECTION,
 NEC 210.12 AND NEC 406.4 ARC-FAULT PROTECTION,
 NEC 210.52 RECEPTACLE SPACING,
 NEC 406.12 AND NEC 406.4(D)(5) TAMPER RESISTANT
 RECEPTACLES,
 NEC 250.140 GROUNDING
 SMOKE/CARBON ALARMS AS PER FBC R 314
 3) SEE SIGNATURE REVIEW
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-06-06 Cont ID  
Sent By cwalker Date 2022-06-06 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-06-06 10:28:54FIRE COMMENTS:
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND/OR
 CEILINGS REQUIRES AN EVALUATION OF THE FIRE ALARM
 AND/OR FIRE SPRINKLER SYSTEMS FOR CODE COMPLIANT
 COVERAGE.
 ALL EXISTING FIRE ALARM AND/OR FIRE SPRINKLER SYSTEMS
 SHALL REMAIN OPERATIONAL DURING DEMOLITION AND
 CONSTRUCTION.
 THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEMS SHALL BE
 PROTECTED FROM DAMAGE DURING DEMOLITION AND
 CONSTRUCTION.
 ANY WORK PERFORMED ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEM SHALL BE CONDUCTED BY PROPERLY
 LICENSED CONTRACTORS UNDER SEPARATE PERMITS AND SHOP
 DRAWINGS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-08 Cont ID  
Sent By pvalenti Date 2022-07-08 Time 16:06 Rev Time 0.00
Received By pvalenti Date 2022-07-07 Time 07:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-06 Cont ID  
Sent By pvalenti Date 2022-07-06 Time 11:03 Rev Time 0.00
Received By pvalenti Date 2022-06-03 Time 08:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2022-06-13 Cont ID  
Sent By medwards Date 2022-06-13 Time 16:25 Rev Time 0.00
Received By medwards Date 2022-06-13 Time 16:25 Sent To  
Notes
2022-06-13 16:26:03NO MECHANICAL WORK IN SCOPE OF WORK FOR THIS PROJECT.
 ME

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-06-07 Cont ID  
Sent By rwbrown Date 2022-06-07 Time 05:53 Rev Time 0.00
Received By rwbrown Date 2022-06-07 Time 05:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-07-08 Cont ID  
Sent By mpeterso Date 2022-07-08 Time 14:09 Rev Time 0.00
Received By mpeterso Date 2022-07-08 Time 14:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-06-23 Cont ID  
Sent By mpeterso Date 2022-06-23 Time 12:47 Rev Time 0.00
Received By mpeterso Date 2022-06-23 Time 12:47 Sent To  
Notes
2022-06-23 12:50:01SIGNATURE REVIEW FAILED
 THE DESIGNER OF RECORD WHO PREPARED DRAWINGS SHALL
 PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 WPB,
 AND FLORIDA STATUTES 471.003(2)(H) & 471.025.
  
 PLEASE SUBMIT DIGITALLY SIGNED PLANS FOLLOWING
 PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  