Plan Review Details - Permit 22051479
Plan Review Stops For Permit 22051479
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-09-06 Cont ID  
Sent By shill Date 2022-09-06 Time 12:07 Rev Time 0.00
Received By shill Date 2022-09-06 Time 12:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-08-29 Cont ID  
Sent By shill Date 2022-08-29 Time 09:22 Rev Time 0.00
Received By shill Date 2022-08-29 Time 09:22 Sent To  
Notes
2022-08-29 09:23:10****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PROVIDE THE FLAME SPREAD TEST FOR WHISPERMAT LVT.
 (STC/IIC TESTS OK, ADDED TO OUR FILES).
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 4TH REVIEW - STC AND IIC TESTS FOR WHISPERMAT CS WERE
 UPLOADED. THE TESTS ARE NOT NEEDED. PROVIDE FLAME
 SPREAD TEST FOR WHISPERMAT LVT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-08-15 Cont ID  
Sent By shill Date 2022-08-15 Time 08:05 Rev Time 0.00
Received By shill Date 2022-08-15 Time 08:05 Sent To  
Notes
2022-08-15 08:05:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PROVIDE THE FLAME SPREAD TEST FOR WHISPERMAT LVT.
 (STC/IIC TESTS OK, ADDED TO OUR FILES).
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-01 Cont ID  
Sent By shill Date 2022-08-01 Time 14:28 Rev Time 0.00
Received By shill Date 2022-08-01 Time 14:28 Sent To  
Notes
2022-08-01 14:30:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. WHISPERMAT LVT IS PROPOSED. WE DO NOT HAVE ANY TEST
 REPORTS ON FILE FOR THIS PRODUCT. THEREFORE PLEASE
 SUBMIT THE FOLLOWING (SEE ALSO PREVIOUS COMMENT LIST):
  
 A, B. STC/IIC, PROVIDE TEST REPORTS. WE DO NOT ACCEPT
 SPEC SHEETS, WE REQUIRE THE TEST REPORTS.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-18 Cont ID  
Sent By shill Date 2022-07-18 Time 17:08 Rev Time 0.00
Received By shill Date 2022-07-18 Time 17:08 Sent To  
Notes
2022-07-18 17:09:00****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED
 UNDERLAYMENT:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2022-09-07 Cont ID  
Sent By cwalker Date 2022-09-07 Time 10:13 Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-08-08 Cont ID  
Sent By cwalker Date 2022-08-08 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-08-01 Cont ID  
Sent By cwalker Date 2022-08-01 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-08-01 09:52:50FIRE COMMENT:
 THE PRODUCT SPECIFICATIONS SUBMITTED ARE FOR THE
 UNDERLAYMENT MATERIAL.
 PROVIDE SPECIFICATIONS ON THE VINYL FLOORING TO BE
 INSTALLED AND THE PERFORMANCE IN A FIRE CONDITION, FOR
 FLAME SPREAD, SMOKE GENERATION AND THE CRITICAL RADIANT
 FLUX OF THE MATERIAL. NFPA 101, 10.2.7
 C. WALKER
 561-804-4762
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-06-02 Cont ID  
Sent By cwalker Date 2022-06-02 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-06-02 10:10:39FIRE COMMENT:
 PROVIDE SPECIFICATIONS ON THE TYPE OF VINYL FLOORING TO
 BE INSTALLED, INCLUDING INFORMATION ON THE TESTED AND
 LISTED PERFORMANCE OF THE MATERIAL IN A FIRE CONDITION,
 FOR FLAME SPREAD, SMOKE GENERATION AND THE CRITICAL
 RADIANT FLUX OF THE MATERIAL. NFPA 101, 10.2.7
 C. WALKER
 561-804-4762
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-09-08 Cont ID  
Sent By shill Date 2022-09-08 Time 09:28 Rev Time 0.00
Received By aoliver Date 2022-08-30 Time 16:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-08-29 Cont ID  
Sent By shill Date 2022-08-29 Time 09:23 Rev Time 0.00
Received By shill Date 2022-08-17 Time 15:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-15 Cont ID  
Sent By shill Date 2022-08-15 Time 08:05 Rev Time 0.00
Received By shill Date 2022-08-06 Time 07:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-01 Cont ID  
Sent By shill Date 2022-08-01 Time 14:30 Rev Time 0.00
Received By shill Date 2022-07-29 Time 15:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-18 Cont ID  
Sent By shill Date 2022-07-18 Time 17:09 Rev Time 0.00
Received By shill Date 2022-06-01 Time 11:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-07-18 Cont ID  
Sent By shill Date 2022-07-18 Time 17:09 Rev Time 0.00
Received By shill Date 2022-07-18 Time 17:09 Sent To  
Notes
***NONE***