Plan Review Stops For Permit 22051479 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2022-09-06 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-09-06 |
Time |
12:07 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-09-06 |
Time |
12:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2022-08-29 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-08-29 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-08-29 |
Time |
09:22 |
Sent To |
|
|
Notes |
2022-08-29 09:23:10 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. PROVIDE THE FLAME SPREAD TEST FOR WHISPERMAT LVT. | | (STC/IIC TESTS OK, ADDED TO OUR FILES). | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | OR UL 723. | | | | 4TH REVIEW - STC AND IIC TESTS FOR WHISPERMAT CS WERE | | UPLOADED. THE TESTS ARE NOT NEEDED. PROVIDE FLAME | | SPREAD TEST FOR WHISPERMAT LVT. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2022-08-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-08-15 |
Time |
08:05 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-08-15 |
Time |
08:05 |
Sent To |
|
|
Notes |
2022-08-15 08:05:52 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. PROVIDE THE FLAME SPREAD TEST FOR WHISPERMAT LVT. | | (STC/IIC TESTS OK, ADDED TO OUR FILES). | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | OR UL 723. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2022-08-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-08-01 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-08-01 |
Time |
14:28 |
Sent To |
|
|
Notes |
2022-08-01 14:30:13 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. WHISPERMAT LVT IS PROPOSED. WE DO NOT HAVE ANY TEST | | REPORTS ON FILE FOR THIS PRODUCT. THEREFORE PLEASE | | SUBMIT THE FOLLOWING (SEE ALSO PREVIOUS COMMENT LIST): | | | | A, B. STC/IIC, PROVIDE TEST REPORTS. WE DO NOT ACCEPT | | SPEC SHEETS, WE REQUIRE THE TEST REPORTS. | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | OR UL 723. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-07-18 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-07-18 |
Time |
17:08 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-07-18 |
Time |
17:08 |
Sent To |
|
|
Notes |
2022-07-18 17:09:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED | | UNDERLAYMENT: | | | | PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM | | CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED | | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | OR UL 723. | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2022-09-07 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2022-09-07 |
Time |
10:13 |
Rev Time |
0.00 |
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2022-08-08 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2022-08-08 |
Time |
|
Rev Time |
0.00 |
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2022-08-01 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2022-08-01 |
Time |
|
Rev Time |
0.00 |
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2022-08-01 09:52:50 | FIRE COMMENT: | | THE PRODUCT SPECIFICATIONS SUBMITTED ARE FOR THE | | UNDERLAYMENT MATERIAL. | | PROVIDE SPECIFICATIONS ON THE VINYL FLOORING TO BE | | INSTALLED AND THE PERFORMANCE IN A FIRE CONDITION, FOR | | FLAME SPREAD, SMOKE GENERATION AND THE CRITICAL RADIANT | | FLUX OF THE MATERIAL. NFPA 101, 10.2.7 | | C. WALKER | | 561-804-4762 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2022-06-02 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2022-06-02 |
Time |
|
Rev Time |
|
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2022-06-02 10:10:39 | FIRE COMMENT: | | PROVIDE SPECIFICATIONS ON THE TYPE OF VINYL FLOORING TO | | BE INSTALLED, INCLUDING INFORMATION ON THE TESTED AND | | LISTED PERFORMANCE OF THE MATERIAL IN A FIRE CONDITION, | | FOR FLAME SPREAD, SMOKE GENERATION AND THE CRITICAL | | RADIANT FLUX OF THE MATERIAL. NFPA 101, 10.2.7 | | C. WALKER | | 561-804-4762 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2022-09-08 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-09-08 |
Time |
09:28 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2022-08-30 |
Time |
16:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2022-08-29 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-08-29 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-08-17 |
Time |
15:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2022-08-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-08-15 |
Time |
08:05 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-08-06 |
Time |
07:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-08-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-08-01 |
Time |
14:30 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-07-29 |
Time |
15:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-07-18 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-07-18 |
Time |
17:09 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-06-01 |
Time |
11:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
N |
Date |
2022-07-18 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-07-18 |
Time |
17:09 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-07-18 |
Time |
17:09 |
Sent To |
|
|
Notes |
|
|