Plan Review Details - Permit 22051284
Plan Review Stops For Permit 22051284
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-01-24 Cont ID  
Sent By jgomez Date 2023-01-24 Time 13:49 Rev Time 0.00
Received By jgomez Date 2023-01-24 Time 13:33 Sent To  
Notes
2023-01-24 13:49:37BUILDING REVIEW APPROVED WITH PROVISO (NOTE: PROVIDE
 INFORMATION FOR REVIEW PRIOR TO INSTALLATION/INSPECTION
 TO AVOID CONFLICTS/DELAYS):
 1-PROVIDE PRODUCT APPROVAL FOR: (A)ROOF TILE HIP &
 RIDGE METAL SUPPORT. (B)STRUCTURAL MULLIONS THAT MEETS
 DESIGN PRESSURES FOR WINDOW "J", (C)EXTERIOR OUTSWING
 DOOR ON NEW UNDER STAIR STORAGE. (D)EXTERIOR SOLID
 OUTSWING DOOR ON NEW PRIVACY WALL NEXT TO THE NEW
 STAIRWAY. (E)ENTRY DOOR WITH SIDELITES AS SHOWN ON
 PLANS. (F)FIXED WINDOW SIZE SPECIFIED FOR WINDOW "L"
 (6'-0" X 5'-10").
 2-DESIGNER OF RECORD TO APPROVE IN WRITING ALL PRODUCT
 APPROVALS.
 3-REVISE ENERGY CALCULATIONS: (A)REVISE ITEM #1 ON PAGE
 ONE. THIS IS EXISTING AND NEW CONSTRUCTION (ADDITION).
 (B)REVISE DOORS INFORMATION. THERE ARE NOT WOOD DOORS
 ON THE NORTH AND SOUTH SIDE. (C)REVISE WINDOWS
 INFORMATION TO MATCH PLANS. CHECK WINDOWS AREAS, NUMBER
 OF WINDOWS/GLASS DOORS SHOWN ON PLANS, WINDOW
 ORIENTATION AND WINDOWS OVERHANG DEPTH AND SEPARATION
 AND REVISE AS REQUIRED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-01-23 Cont ID  
Sent By jgomez Date 2023-01-23 Time 14:16 Rev Time 0.00
Received By jgomez Date 2023-01-20 Time 14:00 Sent To  
Notes
2023-01-23 14:16:59RESIDENTIAL(R3)ADDITION/ALTERATION THIRD BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22051284
 201 SUMMA ST
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY.
  
 ***IMPORTANT****
 CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT
 THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION
 BEFORE PERMIT ISSUANCE.
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 PREVIOUS COMMENT:
 C)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED AS
 SPECIFIED ON PLANS.
  
 RESPONSE:
 NOT ADDRESSED. CONTRACTOR DOESN'T MENTION EITHER IF
 SUBMITTING LATER AS A DEFERRED SUBMITTAL.
  
 PREVIOUS COMMENT:
 E)STRUCTURAL MULLIONS AS SHOWN ON PLANS. AND REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
 NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL,
 INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE
 CORRESPONDING TO DRAWINGS SUBMITTED.
  
 RESPONSE:
 MULLION SIZE MARKED ON SHEET 9 OF 25 OF MULLION NOA
 20-0406.03 DOESN'T MEET THE CALCULATED DESIGN PRESSURES
 FOR WINDOW "J", NEED TO SPECIFY ANOTHER SIZE.
  
 PREVIOUS COMMENT:
 G)EXTERIOR OUTSWING DOOR ON NEW UNDER STAIR STORAGE.
  
 RESPONSE:
 NOT ADDRESSED. CONTRACTOR DOESN'T MENTION EITHER IF
 SUBMITTING LATER AS A DEFERRED SUBMITTAL.
  
 PREVIOUS COMMENT:
 H)EXTERIOR SOLID OUTSWING DOOR ON NEW PRIVACY WALL NEXT
 TO THE NEW STAIRWAY.
  
 RESPONSE:
 NOT ADDRESSED. CONTRACTOR DOESN'T MENTION EITHER IF
 SUBMITTING LATER AS A DEFERRED SUBMITTAL.
  
 I)ENTRY DOOR WITH SIDELITES AS SHOWN ON PLANS.
  
 J)FIXED WINDOW SIZE SPECIFIED FOR WINDOW "L" (6'-0" X
 5'-10").
  
 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- ENERGY CALCULATIONS SUBMITTED:
 PREVIOUS COMMENT:
 E)REVISE/CLARIFY ITEM #1 ON PAGE ONE. EXISTING OR NEW
 CONSTRUCTION (ADDITION). COORDINATE WITH COMMENT (D)
 ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 STILL NO CLEAR. PLANS SHOW EXISTING HOUSE AND AN
 ADDITION. THEREFORE, IT IS EXISTING AND ADDITION.
  
 PREVIOUS COMMENT:
 N)REVISE/CLARIFY DOORS INFORMATION ON PAGE 3. WHERE ARE
 THE WOOD DOORS ON THE NORTH AND SOUTH SIDE? SEE PLANS
 AND REVISE AS REQUIRED. AND COORDINATE WITH COMMENT (D)
 ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 THERE ARE NO WOOD DOORS ON THE NORTH AND SOUTH SIDE.
 SEE PLANS AND REVISE AS REVISE AS REQUIRED.
  
 PREVIOUS COMMENT:
 O)REVISE/CLARIFY WINDOWS INFORMATION ON PAGE 3. REVISE
 WINDOWS AREA, AND OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED. AND
 COORDINATE WITH COMMENT (D) ABOVE. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 WINDOWS INFORMATION DOESN'T MATCH PLANS. CHECK WINDOWS
 AREAS, NUMBER OF WINDOWS/GLASS DOORS SHOWN ON PLANS,
 WINDOW ORIENTATION AND WINDOWS OVERHANG DEPTH AND
 SEPARATION AND REVISE AS REQUIRED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-12 Cont ID  
Sent By jgomez Date 2022-12-12 Time 17:30 Rev Time 0.00
Received By jgomez Date 2022-12-09 Time 10:42 Sent To  
Notes
2022-12-12 17:30:32RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22051284
 201 SUMMA ST
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY.
  
 ***IMPORTANT****CONTRACTOR TO ADVICE IF PROVISO OPTION
 IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED
 INFORMATION BEFORE PERMIT ISSUANCE.
  
 ***IMPORTANT***
 ENERGY CALCULATIONS NEED TO BE CERTIFIED AT THE BOTTOM
 OF FORM BY THE OWNER OR AUTHORIZED AGENT BEFORE ISSUING
 THE PERMIT
  
  
 1-OK.
 2-OK.
 3-OK.
  
 ORIGINAL COMMENT
 4- SPECIFY ATTIC ACCESS SIZE AND LOCATION SHOWING
 COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL.
 NOTE: MAKE SURE THERE IS ENOUGH HEADROOM ABOVE ATTIC
 ACCESS PANEL.
  
 RESPONSE:
 ROOF FRAMING PLAN NEEDS TO BE REVISED TO ALLOW FOR THE
 ATTIC ACCESS PROPOSED LOCATION AND SIZE. ALSO, IT LOOKS
 LIKE THE PROPOSED LOCATION MAY NOT PROVIDE THE REQUIRED
 HEADROOM CLEARANCE. PROVIDE DETAIL SHOWING THE ACTUAL
 HEADROOM ON THE PROPOSED LOCATION.
  
 5- ENLARGED STAIR PLAN DETAIL 2 ON SHEET A-501:
 ORIGINAL COMMENT:
 B)PROVIDE STAIR NOSING DETAIL SHOWING COMPLIANCE WITH
 SEC. R311.7.5.3 FBC-RESIDENTIAL.
  
 RESPONSE:
 TREAD DIMENSION SHOWN ON DETAIL 10 DOESN'T MATCH TREAD
 DIMENSION SHOWN ON DETAIL 2. REVISE AS REQUIRED TO
 MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 6- ENGINEER OF RECORD TO REVISE ROOF SHEATHING NAILING
 SPECIFICATIONS TO COMPLY WITH NEW 2020 FBC-RESIDENTIAL
 SPECIFICATIONS. REVISED NAIL SPACING SPECIFIED IN ALL
 DETAILS AND SPECIFICATIONS SUBMITTED TO COMPLY TABLE
 R803.2.3.1 FBC-RESIDENTIAL. NAIL SPACING TO BE 4" O.C.
 NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS
 SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR
 EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM
 REQUIREMENTS.
  
 RESPONSE:
 ROOF NOTE #1 ON SHEET S-2 WAS NOT REVISED.
  
 7- OK.
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)OK.
  
 ORIGINAL COMMENT:
 B)ROOF TILE ADHESIVE. TILE BOND NOA 16-0222.01
 SUBMITTED EXPIRED ON 08/23/21. NEED CURRENT PRODUCT
 APPROVAL. ALSO, COORDINATE WITH ROOF TILE COMMENT
 ABOVE.
  
 RESPONSE:
 REPEAT COMMENT. SAME NOA WAS SUBMITTED.
  
 ORIGINAL COMMENT:
 C)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED AS
 SPECIFIED ON PLANS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 D)OK.
  
 ORIGINAL COMMENT:
 E)STRUCTURAL MULLIONS AS SHOWN ON PLANS. AND REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
 NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL,
 INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE
 CORRESPONDING TO DRAWINGS SUBMITTED.
  
 RESPONSE:
 CLEARLY SPECIFY OR MARK MULLION SIZE ON NOA 20-0406.03
 SUBMITTED.
  
 ORIGINAL COMMENT:
 F)NEW OUTSIDE OUTSWING DOOR IN EXISTING LIVING ROOM
 AREA.
 NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL,
 INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE
 CORRESPONDING TO DRAWINGS SUBMITTED.
  
 RESPONSE:
 PROVIDE COMPLETE PRODUCT APPROVAL INCLUDING THE FLORIDA
 PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO
 DRAWINGS SUBMITTED.
 NOTE: THERE ARE SEVERAL DOOR PRODUCT APPROVALS
 SUBMITTED. CLEARLY LABEL EACH PRODUCT APPROVAL LIKE
 ENTRY DOOR, STORAGE, LIVING ROOM, ETC TO AVOID
 CONFLICTS/DELAYS. PLEASE COORDINATE WITH THE PERMIT
 LIBRARIAN TO SEE WHICH PRODUCT APPROVALS YOU WANT TO BE
 DELETED.
  
 ORIGINAL COMMENT:
 G)EXTERIOR OUTSWING DOOR ON NEW UNDER STAIR STORAGE.
 NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL,
 INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE
 CORRESPONDING TO DRAWINGS SUBMITTED.
  
 RESPONSE:
 COORDINATE WITH ITEM ABOVE.
  
 ORIGINAL COMMENT:
 H)EXTERIOR SOLID OUTSWING DOOR ON NEW PRIVACY WALL NEXT
 TO THE NEW STAIRWAY.
  
 RESPONSE:
 COORDINATE WITH ITEM ABOVE.
  
 ORIGINAL COMMENT:
 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 COORDINATE WITH ITEM ABOVE.
  
 10- ENERGY CALCULATIONS SUBMITTED:
 ORIGINAL COMMENT:
 A) THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SECTION 553.907, FLORIDA STATUTES, PRIOR TO
 RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION. SECTION R101.5.1.1.2 FBC-RESIDENTIAL.
  
 RESPONSE:
 THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM
 THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS
 PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO
 RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 B)OK.
 C)OK.
  
 ORIGINAL COMMENT:
 D)IT IS NOT CLEAR IF THE CALCULATIONS ARE DONE FOR THE
 ENTIRE HOUSE OR JUST THE ADDITION. CALCULATIONS CAN BE
 DONE EITHER WAY, BUT THEY NEED TO BE CONSISTENT. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 STILL NOT CLEAR. CONDITIONED FLOOR AREA ON ITEM 6 OF
 PAGE ONE DOESN'T MATCH A/C AREAS SHOWN ON PLANS. SHEET
 G-001.
  
 ORIGINAL COMMENT:
 E)REVISE/CLARIFY ITEM #1 ON PAGE ONE. EXISTING OR NEW
 CONSTRUCTION (ADDITION). COORDINATE WITH COMMENT (D)
 ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO
 AVOID MORE CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 F)REVISE/CLARIFY ITEM #4 ON PAGE ONE. PROVIDE CORRECT
 NUMBER OF BEDROOMS. COORDINATE WITH COMMENT (D)ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO
 AVOID MORE CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 G)REVISE/CLARIFY ITEM #6 ON PAGE ONE. PROVIDE CORRECT
 CONDITIONED FLOOR AREA. SEE PLANS AND COORDINATE WITH
 COMMENT (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO
 AVOID MORE CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 H)REVISE/CLARIFY ITEM #11 ON PAGE ONE. PLANS SHOW
 UNVENTED ATTIC AND THEY SHOW DIFFERENT R-VALUES FOR
 CEILING INSULATION DEPENDING ON THE ROOF TYPE. SEE
 PLANS AND REVISE AS REQUIRED. AND COORDINATE WITH
 COMMENT (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 CEILING INSULATION DOESN'T MATCH PLANS. SEE SHEETS
 A-400 AND A-401 AND REVISE AS REQUIRED.
  
 I)OK.
  
 ORIGINAL COMMENT:
 J)REVISE/CLARIFY PROJECT INFORMATION ON PAGE 2. TWO
 STORY ONLY APPLIES IF ENTIRE HOUSE IS CONSIDERED.
 ADDITION ALONE IS ONE STORY. SEE PLANS AND COORDINATE
 WITH COMMENT (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO
 AVOID MORE CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 K)REVISE/CLARIFY SPACES INFORMATION ON PAGE 2. KITCHEN
 ONLY APPLIES TO ENTIRE HOUSE. SEE PLANS AND REVISE AS
 REQUIRED. AND COORDINATE WITH COMMENT (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO
 AVOID MORE CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 L)REVISE/CLARIFY ROOF TYPE INFORMATION ON PAGE 2. IT
 LOOKS LIKE THERE ARE MORE GABLES IN THIS HOUSE. AND IS
 MISSING THE ROOF AREA. SEE PLANS AND REVISE AS
 REQUIRED. AND COORDINATE WITH COMMENT (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO
 AVOID MORE CONFLICTS/DELAYS.
 NOTE: THERE ARE GABLE ROOFS IN THIS HOUSE ALSO. PROVIDE
 REQUIRED INFORMATION.
  
 M)OK.
  
 ORIGINAL COMMENT:
 N)REVISE/CLARIFY DOORS INFORMATION ON PAGE 3. WHERE ARE
 THE WOOD DOORS ON THE NORTH AND SOUTH SIDE? SEE PLANS
 AND REVISE AS REQUIRED. AND COORDINATE WITH COMMENT (D)
 ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO
 AVOID MORE CONFLICTS/DELAYS.
 NOTE: PLANS DON'T SHOW WOOD DOORS.
  
 ORIGINAL COMMENT:
 O)REVISE/CLARIFY WINDOWS INFORMATION ON PAGE 3. REVISE
 WINDOWS AREA, AND OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED. AND
 COORDINATE WITH COMMENT (D) ABOVE. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO
 AVOID MORE CONFLICTS/DELAYS.
 NOTE: WINDOWS OVERHANG DEPTH AND SEPARATION DON'T MATCH
 PLANS. SEE ELEVATIONS.
  
 ORIGINAL COMMENT:
 P)REVISE/CLARIFY GARAGE INFORMATION ON PAGE 3.
 COORDINATE WITH COMMENT (D) ABOVE. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO
 AVOID MORE CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 Q)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 RESPONSE:
 NO ADDRESSED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-26 Cont ID  
Sent By jgomez Date 2022-07-26 Time 15:33 Rev Time 0.00
Received By jgomez Date 2022-07-26 Time 11:04 Sent To  
Notes
2022-07-26 15:40:06RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22051284 201 SUMMA ST
  
 NOTE:
 ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE
 DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT
 WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES.
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. SEC.
 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 2- SIZE OF NEW ENTRY DOOR IS NOT GIVEN. SPECIFY DOOR
 SIZE TO VERIFY COMPLIANCE WITH EGRESS SEC. R11.2
 FBC-RESIDENTIAL.
 NOTE: DOOR SCHEDULE ON SHEET G-004 IS NOT SHOWING ANY
 OF THE EXTERIOR DOORS. ENTRY DOOR, DOOR E100 BY THE
 EXISTING LIVING ROOM, DOOR E103 ON NEW STORAGE ROOM
 UNDERNEATH NEW EXTERIOR STAIRS AND SOLID DOOR E102 ON
 PRIVACY WALL. PROVIDE THIS INFORMATION.
  
 3- BEDROOM #1 AND BEDROOM #2 CASEMENT EGRESS WINDOWS.
 TYPICALLY, 30 INCH WIDE CASEMENT WINDOWS DON'T PROVIDE
 THE REQUIRED CLEAR WIDTH OPENING BECAUSE OF THE
 OPERATING HINGE. PRODUCT APPROVAL SUBMITTED IS FOR PGT
 WINDOWS. PGT WINDOWS HAVE A SPECIAL "EGRESS HINGE".
 DESIGNER OF RECORD TO SPECIFY ON PLANS THE EGRESS HINGE
 ON THE PGT WINDOWS OR SPECIFY OTHER WINDOW SIZE THAT
 MEETS THE BEDROOM EGRESS REQUIREMENTS WITHOUT THE
 SPECIAL REQUEST. SEC. 107.2.1 CITY AMENDMENTS. SEC.
 R310.2.1 FBC-RESIDENTIAL.
 NOTE: REVISE/CLARIFY COMMENTS ON WINDOW SCHEDULE.
 WINDOW MARKED "D" IS THE EGRESS WINDOW NOT "A". ALSO,
 WINDOW "J" COMMENTS CALL FOR 2 PANEL. THESE DOESN'T
 MATCH PLANS AND ELEVATIONS.
  
 4- SPECIFY ATTIC ACCESS SIZE AND LOCATION SHOWING
 COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL.
 NOTE: MAKE SURE THERE IS ENOUGH HEADROOM ABOVE ATTIC
 ACCESS PANEL.
  
 5- ENLARGED STAIR PLAN DETAIL 2 ON SHEET A-501:
 A) NEED TO PROVIDE HANDRAIL SHOWING COMPLIANCE WITH
 SEC. R311.7.8 FBC-RESIDENTIAL.
  
 B)PROVIDE STAIR NOSING DETAIL SHOWING COMPLIANCE WITH
 SEC. R311.7.5.3 FBC-RESIDENTIAL.
  
 C)WINDER TREAD AT TOP OF STAIR NEED TO COMPLY WITH SEC.
 R311.7.5.2.1 FBC-RESIDENTIAL. SPECIFY DIMENSIONS.
  
 D)HEIGHT OF THE GUARDRAIL AT THE CORNER OF TOP LANDING
 OF STAIR DOESN'T COMPLY WITH SEC. R312.1
 FBC-RESIDENTIAL. REVISE ALL DRAWINGS AS REQUIRED. SEE
 STAIR SECTION A ON SHEET A-501 AND DETAIL 3 ON SHEET
 A-500.
  
 6- ENGINEER OF RECORD TO REVISE ROOF SHEATHING NAILING
 SPECIFICATIONS TO COMPLY WITH NEW 2020 FBC-RESIDENTIAL
 SPECIFICATIONS. REVISED NAIL SPACING SPECIFIED IN ALL
 DETAILS AND SPECIFICATIONS SUBMITTED TO COMPLY TABLE
 R803.2.3.1 FBC-RESIDENTIAL. NAIL SPACING TO BE 4" O.C.
 NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS
 SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR
 EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM
 REQUIREMENTS.
  
 7-ENGINEER OF RECORD TO SPECIFY DESIGN PRESSURES FOR
 SOLID DOOR E102 LOCATED IN THE PRIVACY WALL NEXT TO THE
 NEW STAIRWAY LEADING TO THE TERRACE AREA. SEC.
 107.2.1.2 CITY AMENDMENTS. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF TILE. NOA 18-0509.17 SUBMITTED EXPIRED ON
 04/26/22. NEED CURRENT PRODUCT APPROVAL.
 ALSO, CLEARLY MARK ADHESIVE PADDY SIZE TO BE USED AS
 REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
 NOTE: ROOF TILE ADHESIVE PRODUCT APPROVAL SUBMITTED IS
 FOR TILE BOND. ACCORDING TO ROOF TILE NOA THE MINIMUM
 ATTACHMENT RESISTANCE USING TILE BOND ADHESIVE IS
 31.3FT-LBF. ACCORDING TO FRSA MANUAL THE MINIMUM
 REQUIRED UPLIFT MOMENT FOR TILE AT HIS HOUSE IS MORE
 THAN 31.3FT-LBF. NEED TO SPECIFY OTHER TILE ADHESIVE
 THAT MEETS OR EXCEEDS THE MINIMUM REQUIRED UPLIFT
 MOMENT FOR TILE. OR PROVIDE CALCULATIONS SHOWING
 COMPLIANCE WITH TILE BOND ADHESIVE.
  
 NOTE; THERE ARE TWO DIFFERENT ROOF TILE NOA'S
 SUBMITTED. CLARIFY WHICH ONE IS GOING TO BE USED TO
 AVOID CONFLICTS/DELAYS.
  
 B)ROOF TILE ADHESIVE. TILE BOND NOA 16-0222.01
 SUBMITTED EXPIRED ON 08/23/21. NEED CURRENT PRODUCT
 APPROVAL. ALSO, COORDINATE WITH ROOF TILE COMMENT
 ABOVE.
  
 C)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED.
  
 D)TERRACE UNDERLAYMENT THAT IS DESIGNED TO BE INSTALLED
 WITH FINISH FLOOR SPECIFIED ON PLANS. DESIGNER OF
 RECORD TO PROVIDE SPECIFICATIONS FOR FINISH FLOORING.
 NOTE: CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE
 INSTALLED AND RAS 117 CALCULATIONS MAY BE REQUIRED IF
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ZONES.
  
 E)STRUCTURAL MULLIONS AS SHOWN ON PLANS. AND REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
 NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL,
 INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE
 CORRESPONDING TO DRAWINGS SUBMITTED.
  
 F)NEW OUTSIDE OUTSWING DOOR IN EXISTING LIVING ROOM
 AREA.
 NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL,
 INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE
 CORRESPONDING TO DRAWINGS SUBMITTED.
  
 G)EXTERIOR OUTSWING DOOR ON NEW UNDER STAIR STORAGE.
 NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL,
 INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE
 CORRESPONDING TO DRAWINGS SUBMITTED.
  
 H)EXTERIOR SOLID OUTSWING DOOR ON NEW PRIVACY WALL NEXT
 TO THE NEW STAIRWAY.
  
 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- ENERGY CALCULATIONS SUBMITTED:
 A) THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SECTION 553.907, FLORIDA STATUTES, PRIOR TO
 RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION. SECTION R101.5.1.1.2 FBC-RESIDENTIAL.
  
 B)PROVIDE THE NAME (NOT SIGNATURE) OF PERSON PERFORMING
 THE ANALYSIS AND GENERATING THE REPORT AS REQUIRED BY
 SEC. R405.4.2.1 FBC- ENERGY CONSERVATION.
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION NUMBER (THIS JURISDICTION IS 604700).
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)IT IS NOT CLEAR IF THE CALCULATIONS ARE DONE FOR THE
 ENTIRE HOUSE OR JUST THE ADDITION. CALCULATIONS CAN BE
 DONE EITHER WAY, BUT THEY NEED TO BE CONSISTENT. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)REVISE/CLARIFY ITEM #1 ON PAGE ONE. EXISTING OR NEW
 CONSTRUCTION (ADDITION). COORDINATE WITH COMMENT (D)
 ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F)REVISE/CLARIFY ITEM #4 ON PAGE ONE. PROVIDE CORRECT
 NUMBER OF BEDROOMS. COORDINATE WITH COMMENT (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)REVISE/CLARIFY ITEM #6 ON PAGE ONE. PROVIDE CORRECT
 CONDITIONED FLOOR AREA. SEE PLANS AND COORDINATE WITH
 COMMENT (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H)REVISE/CLARIFY ITEM #11 ON PAGE ONE. PLANS SHOW
 UNVENTED ATTIC AND THEY SHOW DIFFERENT R-VALUES FOR
 CEILING INSULATION DEPENDING ON THE ROOF TYPE. SEE
 PLANS AND REVISE AS REQUIRED. AND COORDINATE WITH
 COMMENT (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I)REVISE/CLARIFY ITEM #15 ON PAGE ONE. WATER HEATER IS
 GAS NOT ELECTRIC. SEE PLANS AND COORDINATE WITH COMMENT
 (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 J)REVISE/CLARIFY PROJECT INFORMATION ON PAGE 2. TWO
 STORY ONLY APPLIES IF ENTIRE HOUSE IS CONSIDERED.
 ADDITION ALONE IS ONE STORY. SEE PLANS AND COORDINATE
 WITH COMMENT (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 K)REVISE/CLARIFY SPACES INFORMATION ON PAGE 2. KITCHEN
 ONLY APPLIES TO ENTIRE HOUSE. SEE PLANS AND REVISE AS
 REQUIRED. AND COORDINATE WITH COMMENT (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 L)REVISE/CLARIFY ROOF TYPE INFORMATION ON PAGE 2. IT
 LOOKS LIKE THERE ARE MORE GABLES IN THIS HOUSE. AND IS
 MISSING THE ROOF AREA. SEE PLANS AND REVISE AS
 REQUIRED. AND COORDINATE WITH COMMENT (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 M)REVISE/CLARIFY ATTIC INFORMATION ON PAGE 2. THERE IS
 NOT 1/300 VENT RATIO. SEE PLANS AND REVISE AS REQUIRED.
 AND COORDINATE WITH COMMENT (D) ABOVE. AND IS MISSING
 THE ROOF AREA. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 N)REVISE/CLARIFY DOORS INFORMATION ON PAGE 3. WHERE ARE
 THE WOOD DOORS ON THE NORTH AND SOUTH SIDE? SEE PLANS
 AND REVISE AS REQUIRED. AND COORDINATE WITH COMMENT (D)
 ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 O)REVISE/CLARIFY WINDOWS INFORMATION ON PAGE 3. REVISE
 WINDOWS AREA, AND OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED. AND
 COORDINATE WITH COMMENT (D) ABOVE. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 P)REVISE/CLARIFY GARAGE INFORMATION ON PAGE 3.
 COORDINATE WITH COMMENT (D) ABOVE. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 Q)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-11-29 Cont ID  
Sent By mpeterso Date 2022-11-29 Time 15:00 Rev Time 0.00
Received By mpeterso Date 2022-11-29 Time 15:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-06-21 Cont ID  
Sent By mpeterso Date 2022-06-21 Time 14:47 Rev Time 0.00
Received By mpeterso Date 2022-06-21 Time 14:47 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2022-11-21 Cont ID  
Sent By rrossano Date 2022-11-21 Time   Rev Time 0.00
Received By rrossano Date 2022-11-21 Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2022-06-03 Cont ID  
Sent By rwbrown Date 2022-06-03 Time 09:50 Rev Time 0.00
Received By rwbrown Date 2022-06-03 Time 09:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-01-31 Cont ID  
Sent By asangele Date 2023-01-31 Time 12:06 Rev Time 0.00
Received By asangele Date 2023-01-31 Time 12:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-23 Cont ID  
Sent By jgomez Date 2023-01-23 Time 14:31 Rev Time 0.00
Received By jgomez Date 2023-01-04 Time 14:46 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-12 Cont ID  
Sent By jgomez Date 2022-12-12 Time 17:48 Rev Time 0.00
Received By jgomez Date 2022-11-16 Time 10:05 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-26 Cont ID  
Sent By jgomez Date 2022-07-26 Time 16:08 Rev Time 0.00
Received By jgomez Date 2022-05-27 Time 06:27 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2023-02-15 Cont ID  
Sent By lmarchan Date 2023-02-15 Time 12:23 Rev Time 0.00
Received By lmarchan Date 2023-01-24 Time 14:50 Sent To  
Notes
2023-02-13 11:05:27RECEIPT MU-2023-005070 - $22.46 PAID
2023-01-24 14:50:571/24/23 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2023-01-23 Cont ID  
Sent By jgomez Date 2023-01-23 Time 14:18 Rev Time 0.00
Received By jgomez Date 2023-01-23 Time 14:17 Sent To  
Notes
2023-01-23 14:18:21NOTE: IMPACT FEES QUESTIONNAIRE IS UPLOADED TO
 PROJECTDOX. PERMIT LIBRARIAN WILL EMAIL THE COUNTY WHEN
 THE PERMIT IS CLOSE TO ISSUANCE. JG.
  
  
 IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-07-26 Cont ID  
Sent By jgomez Date 2022-07-26 Time 16:03 Rev Time 0.00
Received By jgomez Date 2022-07-26 Time 16:02 Sent To  
Notes
2022-07-26 16:03:31NOTE: IMPACT FEES QUESTIONNAIRE IS UPLOADED TO
 PROJECTDOX. PERMIT LIBRARIAN WILL EMAIL THE COUNTY WHEN
 THE PERMIT IS CLOSE TO ISSUANCE. JG.
  
  
 IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-11-21 Cont ID  
Sent By medwards Date 2022-11-21 Time 11:02 Rev Time 0.00
Received By medwards Date 2022-11-21 Time 11:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-05-31 Cont ID  
Sent By medwards Date 2022-05-31 Time 15:03 Rev Time 0.00
Received By medwards Date 2022-05-31 Time 15:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-11-17 Cont ID  
Sent By rwbrown Date 2022-11-17 Time 07:58 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-06-03 Cont ID  
Sent By rwbrown Date 2022-06-03 Time 09:50 Rev Time 0.00
Received By rwbrown Date 2022-06-03 Time 09:24 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2023-01-24 Cont ID  
Sent By jgomez Date 2023-01-24 Time 14:13 Rev Time 0.00
Received By jgomez Date 2023-01-24 Time 14:13 Sent To  
Notes
2023-01-24 14:14:56ROOFING PROVISO:
  
 1-PROVIDE PRODUCT APPROVAL FOR (NOTE: PROVIDE
 INFORMATION FOR REVIEW PRIOR TO INSTALLATION/INSPECTION
 TO AVOID CONFLICTS/DELAYS):
 A)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED AS
 SPECIFIED ON PLANS.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 APPROVED:
 **TILE BOND ADHESIVE NOA 22-0614.05.
 **ROOF TILE NOA21-0420.08
 **BORAL UNDERLAYMENT NOA 18-0502.03
 **REGARD CONCRETE TERRACE WATERPROOFING NOA 18-0521.02
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2023-01-23 Cont ID  
Sent By jgomez Date 2023-01-23 Time 14:31 Rev Time 0.00
Received By jgomez Date 2023-01-20 Time 12:53 Sent To  
Notes
2023-01-23 14:31:21ROOFING REVIEW:
  
 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 C)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED AS
 SPECIFIED ON PLANS.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 APPROVED:
 **TILE BOND ADHESIVE NOA 22-0614.05.
 **ROOF TILE NOA21-0420.08
 **BORAL UNDERLAYMENT NOA 18-0502.03
 **REGARD CONCRETE TERRACE WATERPROOFING NOA 18-0521.02
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-12-12 Cont ID  
Sent By jgomez Date 2022-12-12 Time 17:43 Rev Time 0.00
Received By jgomez Date 2022-12-12 Time 17:41 Sent To  
Notes
2022-12-12 17:47:59ROOFING REVIEW:
  
 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 ORIGINAL COMMENT:
 A)OK.
  
 B)ROOF TILE ADHESIVE. TILE BOND NOA 16-0222.01
 SUBMITTED EXPIRED ON 08/23/21. NEED CURRENT PRODUCT
 APPROVAL. ALSO, COORDINATE WITH ROOF TILE COMMENT
 ABOVE.
  
 RESPONSE:
 REPEAT COMMENT. SAME NOA WAS SUBMITTED.
  
 ORIGINAL COMMENT:
 C)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED AS
 SPECIFIED ON PLANS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 COORDINATE WITH ITEM ABOVE
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-07-26 Cont ID  
Sent By jgomez Date 2022-07-26 Time 16:06 Rev Time 0.00
Received By jgomez Date 2022-07-26 Time 16:06 Sent To  
Notes
2022-07-26 16:08:20ROOFING REVIEW:
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF TILE. NOA 18-0509.17 SUBMITTED EXPIRED ON
 04/26/22. NEED CURRENT PRODUCT APPROVAL.
 ALSO, CLEARLY MARK ADHESIVE PADDY SIZE TO BE USED AS
 REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
 NOTE: ROOF TILE ADHESIVE PRODUCT APPROVAL SUBMITTED IS
 FOR TILE BOND. ACCORDING TO ROOF TILE NOA THE MINIMUM
 ATTACHMENT RESISTANCE USING TILE BOND ADHESIVE IS
 31.3FT-LBF. ACCORDING TO FRSA MANUAL THE MINIMUM
 REQUIRED UPLIFT MOMENT FOR TILE AT HIS HOUSE IS MORE
 THAN 31.3FT-LBF. NEED TO SPECIFY OTHER TILE ADHESIVE
 THAT MEETS OR EXCEEDS THE MINIMUM REQUIRED UPLIFT
 MOMENT FOR TILE. OR PROVIDE CALCULATIONS SHOWING
 COMPLIANCE WITH TILE BOND ADHESIVE.
  
 NOTE; THERE ARE TWO DIFFERENT ROOF TILE NOA'S
 SUBMITTED. CLARIFY WHICH ONE IS GOING TO BE USED TO
 AVOID CONFLICTS/DELAYS.
  
 B)ROOF TILE ADHESIVE. TILE BOND NOA 16-0222.01
 SUBMITTED EXPIRED ON 08/23/21. NEED CURRENT PRODUCT
 APPROVAL. ALSO, COORDINATE WITH ROOF TILE COMMENT
 ABOVE.
  
 C)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED.
  
 D)TERRACE UNDERLAYMENT THAT IS DESIGNED TO BE INSTALLED
 WITH FINISH FLOOR SPECIFIED ON PLANS. DESIGNER OF
 RECORD TO PROVIDE SPECIFICATIONS FOR FINISH FLOORING.
 NOTE: CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE
 INSTALLED AND RAS 117 CALCULATIONS MAY BE REQUIRED IF
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ZONES.
  
 2-- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-01-23 Cont ID  
Sent By jgomez Date 2023-01-23 Time 14:31 Rev Time 0.00
Received By jgomez Date 2023-01-23 Time 14:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-17 Cont ID  
Sent By rwbrown Date 2022-11-17 Time 08:02 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-21 Cont ID  
Sent By mpeterso Date 2022-06-21 Time 14:54 Rev Time 0.00
Received By mpeterso Date 2022-06-21 Time 14:54 Sent To  
Notes
2022-06-21 14:54:42ALL PLANS PASSED SIGNATURE REVIEW.MP
2022-05-31 15:05:45DIGITAL SIGNATURES FOR MECHANICAL APPROVED ME

Review Stop Z ZONING
Rev No 4 Status P Date 2023-01-31 Cont ID  
Sent By asangele Date 2023-01-31 Time 12:06 Rev Time 0.00
Received By asangele Date 2023-01-31 Time 12:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2023-01-10 Cont ID  
Sent By asangele Date 2023-01-10 Time 09:57 Rev Time 0.00
Received By asangele Date 2023-01-10 Time 09:57 Sent To  
Notes
2023-01-10 10:00:55FAILED
 1/10/2023
 A LANDSCAPE PERMIT IS REQUIRED
  
 THE VALUE OF THE CONSTRUCTION ($294,282) EXCEEDS 50% OF
 THE STRUCTURE'S VALUE ($750,000) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2022-11-18 Cont ID  
Sent By asangele Date 2022-11-18 Time 08:56 Rev Time 0.00
Received By asangele Date 2022-11-18 Time 08:56 Sent To  
Notes
2022-11-18 08:59:31FAILED
 11/18/2022
  
 PLEASE PROVIDE THE NEW ADDITION SETBACKS ON SURVEY.
  
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2022-06-08 Cont ID  
Sent By asangele Date 2022-06-08 Time 12:41 Rev Time 0.00
Received By asangele Date 2022-06-08 Time 12:41 Sent To  
Notes
***NONE***