Plan Review Details - Permit 22051248
Plan Review Stops For Permit 22051248
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-07-21 Cont ID  
Sent By shill Date 2022-07-21 Time 07:36 Rev Time 0.00
Received By shill Date 2022-07-21 Time 07:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-18 Cont ID  
Sent By shill Date 2022-07-18 Time 10:22 Rev Time 0.00
Received By shill Date 2022-07-18 Time 10:22 Sent To  
Notes
2022-07-18 10:23:42FS471, THE DOCUMENTS UPLOADED ARE NOT DIGITALLY SIGNED.
 IT APPEARS THAT THE DOCUMENTS WERE INITIALLY DIGITALLY
 SIGNED BUT THE DIGITAL SIGNATURE HAS BEEN REMOVED FROM
 THE DOCUMENTS.
  
 UPLOAD PAGES THAT ARE DIGITALLY SIGNED BY THE ENGINEER.
 IF YOU NEED TO VERIFY A DIGITAL SIGNATURE, EMAIL ONE
 PAGE TO:
  
 [email protected]
 [email protected]
  
 AND REQUEST THAT WE VERIFY THE DIGITAL SIGNATURE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-07-25 Cont ID  
Sent By mpeterso Date 2022-07-25 Time 10:07 Rev Time 0.00
Received By mpeterso Date 2022-07-25 Time 10:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-06-09 Cont ID  
Sent By mpeterso Date 2022-06-09 Time 10:10 Rev Time 0.00
Received By mpeterso Date 2022-06-09 Time 10:00 Sent To  
Notes
2022-06-09 10:10:37ELECTRIC REVIEW FAILED
 1) RECEPTACLE SPACING AT COUNTERTOPS, KITCHEN ISLAND
 AND BATH VANITY?S DO NOT APPEAR TO COMPLY WITH NEC
 210.52. PLEASE CORRECT AS APPLICABLE
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-25 Cont ID  
Sent By mpeterso Date 2022-07-25 Time 10:08 Rev Time 0.00
Received By mpeterso Date 2022-07-18 Time 17:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-18 Cont ID  
Sent By shill Date 2022-07-18 Time 10:23 Rev Time 0.00
Received By shill Date 2022-05-26 Time 07:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-07-19 Cont ID  
Sent By rwbrown Date 2022-07-19 Time 09:23 Rev Time 0.00
Received By rwbrown Date 2022-07-19 Time 09:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-05-28 Cont ID  
Sent By rwbrown Date 2022-05-28 Time 08:07 Rev Time 0.00
Received By rwbrown Date 2022-05-28 Time 07:57 Sent To  
Notes
2022-05-28 08:10:061ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - PLEASE INCLUDE AN
 "EXISTING" FLOOR PLAN TO CLEARLY SHOW THE CHANGES MADE
 IN THE FLOOR PLAN.
  
 2. 2017 WPB AMENDS 107.3.5.3 - PLEASE SHOW A RISER
 DIAGRAM THAT INDICATES ANY SIGNIFICANT CHANGES TO THE
 PLUMBING SYSTEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-07-21 Cont ID  
Sent By shill Date 2022-07-21 Time 07:36 Rev Time 0.00
Received By shill Date 2022-07-21 Time 07:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-06-09 Cont ID  
Sent By mpeterso Date 2022-06-09 Time 10:16 Rev Time 0.00
Received By mpeterso Date 2022-06-09 Time 10:16 Sent To  
Notes
2022-06-09 10:21:38SIGNATURE REVIEW FAILED
 1) DIGITAL SIGNATURE OF ENGINEER OF RECORD FOR ALL
 DRAWINGS CANNOT BE CERTIFIED BY ADOBE OR BLUEBEAM
 SOFTWARE AS REQUIRED. PLEASE CORRECT AS OUTLINED BELOW.
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
  
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING
 DEPARTMENT.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
 PLEASE EMAIL [email protected] AND CC TO
 [email protected] WITH ANY QUESTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  