Plan Review Details - Permit 22051173
Plan Review Stops For Permit 22051173
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-08-10 Cont ID  
Sent By jwitmer Date 2022-08-10 Time 08:02 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-07-20 Cont ID  
Sent By jwitmer Date 2022-07-20 Time 08:45 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-07-20 08:45:45TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR?S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-08-23 Cont ID  
Sent By jwitmer Date 2022-08-23 Time 07:28 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-08-10 Cont ID  
Sent By jwitmer Date 2022-08-10 Time 08:02 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-20 Cont ID  
Sent By jwitmer Date 2022-07-20 Time 10:06 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-07-20 10:06:48WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22051173
 ADD: 515 N. FLAGLER DR. 19TH FLOOR
 CONT: TBD/ TO BE DETERMINED
 TEL:
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 20TH/2022
 ACTION: DENIED
  
 1) 8/03/22. COMPLIED. UPLOADED FILE FOR USG STRUCTURAL
 CONCRETE PANEL SUB-FLOORING. SPOKE WITH ENG. PHILL
 RIZZO.
  
 2) SHEET A-403 RESTROOM FLOOR DETAILS DOES NOT SHOW
 COMPLIANCE WITH THE 2020 FBC-ACCESSIBILITY CODE SECTION
 604.3.1 & FIGURE 604.3.1 CLEARANCE AT WATER CLOSETS AND
 OVERLAP IN SECTION 604.3.2.
  
 3) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-08-16 Cont ID  
Sent By mpeterso Date 2022-08-16 Time 14:10 Rev Time 0.00
Received By mpeterso Date 2022-08-16 Time 14:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-06-28 Cont ID  
Sent By mpeterso Date 2022-06-28 Time 09:19 Rev Time 0.00
Received By mpeterso Date 2022-06-28 Time 09:44 Sent To  
Notes
2022-06-28 09:44:44SEE SIGNATURE REVIEW

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 2 Status P Date 2022-08-16 Cont ID  
Sent By mpeterso Date 2022-08-16 Time 14:10 Rev Time 0.00
Received By mpeterso Date 2022-08-16 Time 14:10 Sent To  
Notes
2022-08-16 14:12:24VOICE AND DATA ONLY

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status F Date 2022-06-28 Cont ID  
Sent By mpeterso Date 2022-06-28 Time 09:20 Rev Time 0.00
Received By mpeterso Date 2022-06-28 Time 09:20 Sent To  
Notes
2022-06-28 09:20:33SEE SIGNATURE REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-08-22 Cont ID  
Sent By pleduc Date 2022-08-22 Time   Rev Time 0.00
Received By pleduc Date 2022-08-22 Time 12:07 Sent To  
Notes
2022-08-22 12:11:32FIRE PROVISO:
  
 **THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 **ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM,
 INCLUDING DEMO, SHALL BE DONE UNDER SEPARATE PERMITS &
 SHOP DRAWINGS.
  
 **THE ACCESS CONTROL SYSTEM SHALL BE INSTALLED UNDER
 SEPARATE PERMIT & SHOP DRAWINGS.
  
 **ALL ACCESS CONTROL SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 101 CH 7, MEANS OF EGRESS AS APPLICABLE TO THE
 TYPE OF CONTROL.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-08-09 Cont ID  
Sent By cwalker Date 2022-08-09 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-08-09 08:32:51FIRE PROVISO:
 **THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
 **ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM,
 INCLUDING DEMO, SHALL BE DONE UNDER SEPARATE PERMITS &
 SHOP DRAWINGS.
 **THE ACCESS CONTROL SYSTEM SHALL BE INSTALLED UNDER
 SEPARATE PERMIT & SHOP DRAWINGS.
 **ALL ACCESS CONTROL SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 101 CH 7, MEANS OF EGRESS AS APPLICABLE TO THE
 TYPE OF CONTROL.
 C. WALKER
 561-804-4762
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-06-02 Cont ID  
Sent By pleduc Date 2022-06-02 Time   Rev Time 0.00
Received By pleduc Date 2022-06-02 Time 15:43 Sent To  
Notes
2022-06-02 15:50:46FIRE PROVISO:
  
 **THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 **ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM,
 INCLUDING DEMO, SHALL BE DONE UNDER SEPARATE PERMITS &
 SHOP DRAWINGS.
  
 **THE ACCESS CONTROL SYSTEM SHALL BE INSTALLED UNDER
 SEPARATE PERMIT & SHOP DRAWINGS.
  
 **ALL ACCESS CONTROL SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 101 CH 7, MEANS OF EGRESS AS APPLICABLE TO THE
 TYPE OF CONTROL.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-26 Cont ID  
Sent By aoliver Date 2022-08-26 Time 07:23 Rev Time 0.00
Received By aoliver Date 2022-08-21 Time 07:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-16 Cont ID  
Sent By mpeterso Date 2022-08-16 Time 14:12 Rev Time 0.00
Received By mpeterso Date 2022-08-08 Time 16:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-07-21 Time   Rev Time 0.00
Received By cdecoeur Date 2022-05-31 Time 07:26 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-07-20 Cont ID  
Sent By jwitmer Date 2022-07-20 Time 10:05 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-08-12 Cont ID  
Sent By medwards Date 2022-08-12 Time 14:29 Rev Time 0.00
Received By medwards Date 2022-08-12 Time 14:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-06-10 Cont ID  
Sent By medwards Date 2022-06-10 Time 16:40 Rev Time 0.00
Received By medwards Date 2022-06-10 Time 16:40 Sent To  
Notes
2022-06-10 16:42:48PROVIDE A COMPLETE OUTDOOR AIR CALCULATION FOR EACH USE
 OF SPACE FOR THIS TENANT SPACE ACCORDING TO FMC
 403.3.1.1 AND TABLE 403.3.1.1. THE TABLE 403.3.1.1
 SHOULD BE USE FOR THE OCCUPANT COUNT FOR EACH SPACE AND
 NOT THE ARCHITECTURAL OCCUPANCY COUNTS.
  
 PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS TENANT SPACE. FEC C403.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-08-09 Cont ID  
Sent By rwbrown Date 2022-08-09 Time 07:21 Rev Time 0.00
Received By rwbrown Date 2022-08-09 Time 07:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-06-06 Cont ID  
Sent By rwbrown Date 2022-06-06 Time 12:28 Rev Time 0.00
Received By rwbrown Date 2022-06-06 Time 12:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-08-23 Cont ID  
Sent By jwitmer Date 2022-08-23 Time 07:31 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-08-09 Cont ID  
Sent By rwbrown Date 2022-08-09 Time 07:55 Rev Time 0.00
Received By rwbrown Date 2022-08-09 Time 07:55 Sent To  
Notes
2022-08-09 07:56:51ALL PAGES ARE NOT ELECTRONICALLY SIGNED/SEALED. THE A
 AND G SHEETS ARE NOT ELECTRONICALLY SIGNED/DIGITALLY
 SEALED.
  
 ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR
 ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH
 61G1-16 AND 61G15, F.A.C
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-06-28 Cont ID  
Sent By mpeterso Date 2022-06-28 Time 09:45 Rev Time 0.00
Received By mpeterso Date 2022-06-28 Time 09:45 Sent To  
Notes
2022-06-28 09:47:27SIGNATURE REVIEW FAILED
 ALL PLANS LABELED AS , A SHEETS, AV SHEETS, TC
 SHEETS,AND SC SHEETS DO NOT HAVE THE REQUIRED DIGITAL
 SIGNATURE
  
 SIGNATURE REVIEW FAILED
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
2022-06-10 16:44:32DIGITAL SIGNATURES FOR MECHANICAL DRAWINGS APPROVED ME

Review Stop Z ZONING
Rev No 3 Status P Date 2022-08-25 Cont ID  
Sent By ckimmerl Date 2022-08-25 Time 12:12 Rev Time 0.00
Received By ckimmerl Date 2022-08-25 Time 12:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-08-15 Cont ID  
Sent By ckimmerl Date 2022-08-15 Time 14:14 Rev Time 0.00
Received By ckimmerl Date 2022-08-15 Time 14:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-07-08 Cont ID  
Sent By ckimmerl Date 2022-07-08 Time 11:26 Rev Time 0.00
Received By ckimmerl Date 2022-07-08 Time 11:26 Sent To  
Notes
***NONE***