Plan Review Details - Permit 22051035
Plan Review Stops For Permit 22051035
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-07-12 Cont ID  
Sent By mpeterso Date 2022-07-12 Time 10:25 Rev Time 0.00
Received By mpeterso Date 2022-07-12 Time 10:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-06-21 Cont ID  
Sent By mpeterso Date 2022-06-21 Time 14:06 Rev Time 0.00
Received By mpeterso Date 2022-06-21 Time 14:06 Sent To  
Notes
2022-06-21 14:09:57ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE A DETAILED FLOOR PLAN AS TO WHICH AND
 WHERE WIRING IS TO BE REMOVED AND REPLACED, IE IS ALL
 WIRING TO BE REMOVED? FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-12 Cont ID  
Sent By mpeterso Date 2022-07-12 Time 10:26 Rev Time 0.00
Received By mpeterso Date 2022-07-09 Time 08:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-21 Cont ID  
Sent By mpeterso Date 2022-06-21 Time 14:16 Rev Time 0.00
Received By mpeterso Date 2022-05-27 Time 08:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-07-12 Cont ID  
Sent By mpeterso Date 2022-07-12 Time 10:25 Rev Time 0.00
Received By mpeterso Date 2022-07-12 Time 10:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-06-21 Cont ID  
Sent By mpeterso Date 2022-06-21 Time 14:10 Rev Time 0.00
Received By mpeterso Date 2022-06-21 Time 14:10 Sent To  
Notes
2022-06-21 14:16:18SIGNATURE REVIEW FAILED
 1) DRAWING WITH TITLE BLOCK OF THE MCCANN GROUP
 REQUIRES A SEAL AND SIGNATURE IF AN ARCHITECT OR
 ENGINEER OR IF NOT SIGNED BY THE DESIGNER OF THE
 DRAWING AS PER STATUTES FS471/FS481
 2) ELECTRICAL DRAWING REQUIRES A SIGNATURE OF THE
 DESIGNER AS PER SECTION 107.2.1 WPB, AND FLORIDA
 STATUTES 471.003(2)(H) & 471.025.
  
 PLEASE CORRECT AS OUTLINED BELOW
  
 UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN TO THE
 SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF APPLICABLE)
 AND COMPLETE THE UPLOAD TASK IN PROJECTDOX..
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
 PLEASE EMAIL [email protected] AND CC TO
 [email protected] WITH ANY QUESTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  