Plan Review Details - Permit 22051029
Plan Review Stops For Permit 22051029
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-07-26 Cont ID  
Sent By jwitmer Date 2022-07-26 Time 07:29 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-07-19 Cont ID  
Sent By jwitmer Date 2022-07-19 Time 10:13 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-07-19 10:13:53TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR?S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-07-06 Cont ID  
Sent By jwitmer Date 2022-07-06 Time 11:15 Rev Time 0.00
Received By jwitmer Date 2022-07-06 Time 10:19 Sent To  
Notes
2022-07-06 10:27:13TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR?S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-07-26 Cont ID  
Sent By jwitmer Date 2022-07-26 Time 07:37 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-07-19 Cont ID  
Sent By jwitmer Date 2022-07-19 Time 10:13 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-07-19 10:11:23WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22051029
 ADD: 2427 PRESIDENTIAL WAY # 304
 CONT: AVANTE CONSTRUCTION & RENOVATION
 TEL: 561-756-6200
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JULY 19TH/2022
 ACTION: DENIED
  
 1-2) COMPLIED
  
 3) 2ND REQUEST. PLEASE NOTE, THE RESPONSE AND SHEET A-1
 STATE LAMINATED/ ENGINEERED WOOD FLOORING AND PROFLEX
 90 UNDERLAYMENT. THE CITY OF W. P. B. IS IN RECEIPT OF
 PROFLEX SUPER SIM 90 FOR TILE AND OR MARBLE ONLY NOT
 LAMINATED/ ENGINEERED WOOD FLOORING.
 PROFLEX DOES HAVE TESTING REPORTS FOR PROFLEX LV-200
 FOR LAMINATED FLOORS. REPORTS HAVE BEEN FORWARDED IN A
 RETURN E-MAIL TO YOUR OFFICE.
 1ST ROUND OF COMMENTS. THE FLOOR PLAN NOR ANY OF THE
 OTHER PLANS INDICATE THE TYPE OF FLOOR FINISH AND TYPE
 OF UNDERLAYMENT. FLOOR INSULATION/ UNDERLAYMENT (FBC-B
 2020) FOR TILE, STONE, MARBLE, VINYL (LYT/ LYP),
 LAMINATE FLOORING AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C1) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. (TILE
 & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED FLOOR
 AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 3C2) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR
 LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT
 SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY
 WITH THE REQUIREMENTS OF THE COC FF-1 ?PILL TEST? (CPSC
 16 CFR PART 1630) OR WITH ASTM D2859.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-06 Cont ID  
Sent By jwitmer Date 2022-07-06 Time 11:15 Rev Time 0.00
Received By jwitmer Date 2022-07-06 Time 10:19 Sent To  
Notes
2022-07-06 11:15:20WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22051029
 ADD: 2427 PRESIDENTIAL WAY # 304
 CONT: AVANTE CONSTRUCTION & RENOVATION
 TEL: 561-756-6200
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 06TH/2022
 ACTION: DENIED
  
 1) SHEET A-1 PROPOSED FLOOR PLAN:
 1A) THE OCCUPANCY IS DECLARED AS R, R1, R2 OR R3?
 PLEASE REVIEW THE 2020 FBC-BUILDING CODE RESIDENTIAL
 GROUP R SECTION 310.
  
 1B) THE CONSTRUCTION TYPE IS LISTED AS TYPE III. PLEASE
 REVIEW 2020 FBC-BUILDING CODE TABLE 504.4. PLEASE NOTE
 THIS IS A 24-STORY BUILDING, IN THE 2020 FBC-B TABLE
 504.4 FOR A R2 OCCUPANCY THE BUILDING TYPE WOULD BE
 I-A, PLEASE UPDATE THE PLANS.
  
 1C) DOOR & WINDOW NOTES. WINDOWS, DOORS & FRENCH GLASS
 DOOR INSTALLATION SHALL BE IN ACCORDANCE WITH
 MANUFACTURES SPECIFICATION SET FORTH IN THE APPROVED
 PRODUCT CONTROL APPROVAL. PLEASE NOTE THIS REVIEW CYCLE
 NO PRODUCT APPROVALS WERE SUBMITTED.
  
 COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS AND
 CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS
  
 1D) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
  
 1E) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE
 OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
  
 1F) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2) NONE OF THE PLANS PROVIDE WIND DESIGN CRITERIA. 2020
 FBC-B 1603.1.4 WIND DESIGN CRITERIA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 2.2. RISK CATEGORY.
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1. NOTE 24
 FLOOR BUILDING, NEGATIVE PRESSURES TAKEN FROM ROOF
 LEVEL.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 2.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 2.7) 2020 FBC-B 1709.5.1 HABITAT SPACES, WATER
 INTRUSION. EXTERIOR DOORS AND WINDOWS. EXCEPTION # 2.
 SILL LIMITING FACTOR.
  
 3) THE FLOOR PLAN NOR ANY OF THE OTHER PLANS INDICATE
 THE TYPE OF FLOOR FINISH AND TYPE OF UNDERLAYMENT.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C1) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. (TILE
 & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED FLOOR
 AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 3C2) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR
 LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT
 SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY
 WITH THE REQUIREMENTS OF THE COC FF-1 ?PILL TEST? (CPSC
 16 CFR PART 1630) OR WITH ASTM D2859.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-06-16 Cont ID  
Sent By fgiaquin Date 2022-06-16 Time 23:14 Rev Time 0.00
Received By fgiaquin Date 2022-06-16 Time 21:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-07-22 Cont ID  
Sent By cwalker Date 2022-07-22 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-07-14 Cont ID  
Sent By cwalker Date 2022-07-14 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-05-31 Cont ID  
Sent By cwalker Date 2022-05-31 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-05-31 10:51:02FIRE COMMENTS:
 SMOKE ALARM LOCATIONS ARE NOT INDICATED ON THE PLAN
 SUBMITTAL. NFPA 101, 30.3.4.6.1
 THE TYPE OF FINISHED FLOORING IS NOT INDICATED ON THE
 PLAN SUBMITTAL. NFPA 101, 10.2.7
 ANY AND ALL WORK ON THE LIFE SAFETY SYSTEMS (FIRE
 ALARM/FIRE SPRINKLERS) SHALL BE PERFORMED UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS BY PROPERLY LICENSED
 CONTRACTORS.
 THE LIFE SAFETY SYSTEMS (FIRE ALARM/FIRE SPRINKLERS)
 SHALL REMAIN ACTIVE DURING ALL PHASES OF DEMOLITION AND
 CONSTRUCTION. ANY IMPAIRMENTS TO ANY LIFE SAFETY SYSTEM
 LASTING MORE THAN 4 CONTINUOUS HOURS IN DURATION WILL
 REQUIRE THE IMPLEMENTATION OF FIRE WATCH.
 C. WALKER
 561-804-4762
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-26 Cont ID  
Sent By jwitmer Date 2022-07-26 Time 07:40 Rev Time 0.00
Received By jwitmer Date 2022-07-21 Time 08:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-19 Cont ID  
Sent By jwitmer Date 2022-07-19 Time 10:16 Rev Time 0.00
Received By jwitmer Date 2022-07-13 Time 16:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-07-06 Time   Rev Time 0.00
Received By cdecoeur Date 2022-05-27 Time 10:03 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-07-06 Cont ID  
Sent By jwitmer Date 2022-07-06 Time 11:15 Rev Time 0.00
Received By jwitmer Date 2022-07-06 Time 10:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-07-22 Cont ID  
Sent By medwards Date 2022-07-22 Time 13:32 Rev Time 0.00
Received By medwards Date 2022-07-22 Time 13:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-07-22 Cont ID  
Sent By medwards Date 2022-07-22 Time 13:33 Rev Time 0.00
Received By medwards Date 2022-07-22 Time 13:33 Sent To  
Notes
2022-07-15 13:54:00 
 SHOW HOW THE RETURN AIR WILL WILL TRAVEL FROM THE ROOMS
 WITH THE DOORS BACK TO THE AHU.
  
 FMC 601.6 BALANCED RETURN AIR. RESTRICTED RETURN AIR
 OCCURS IN
 BUILDINGS WHEN RETURNS ARE LOCATED IN CENTRAL ZONES AND
 CLOSED
 INTERIOR DOORS IMPEDE AIR FLOW TO THE RETURN GRILL OR
 WHEN CEILING
 SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS
 RESTRICT
 AIR MOVEMENT FROM ONE PORTION OF THE RETURN PLENUM TO
 ANOTHER. PROVISIONS SHALL BE MADE IN BOTH RESIDENTIAL
 AND
 COMMERCIAL BUILDINGS TO AVOID UNBALANCED AIR FLOWS AND
 PRESSURE
 DIFFERENTIALS CAUSED BY RESTRICTED RETURN AIR. PRESSURE
 DIFFERENTIALS
 ACROSS CLOSED DOORS WHERE RETURNS ARE CENTRALLY
 LOCATED SHALL BE LIMITED TO 0.01-INCH WC (2.5 PASCALS)
 OR LESS.
 PRESSURE DIFFERENTIALS ACROSS FIRE WALLS IN CEILING
 SPACE PLENUMS
 SHALL BE LIMITED TO 0.01-INCH WC (2.5 PASCALS) BY
 PROVIDING
 AIR DUCT PATHWAYS OR AIR TRANSFER PATHWAYS FROM THE
 HIGH PRESSURE ZONE TO THE LOW ZONE.
 EXCEPTIONS:
 1. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED
 1-INCH UNDERCUT TO ACHIEVE PROPER RETURN AIR
 BALANCE.
 2. TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE
 AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THEWALL
 TRANSFER GRILLES AND USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER RETURN AIR
 BALANCE.
 3. HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE
 REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS,
 EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL
 BE
 INCLUDED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-05-31 Cont ID  
Sent By medwards Date 2022-05-31 Time 13:25 Rev Time 0.00
Received By medwards Date 2022-05-31 Time 13:25 Sent To  
Notes
2022-05-31 13:28:17PROVIDE A COMPLETE SCOPE OF WORK AS WELL AS A DEMO
 DRAWING FOR THE MECHANICAL SYSTEM. THE NEW DRAWING DOES
 NOT SHOW ANYTHING ABOUT THE RETURN AIR SYSTEM. IS IT A
 PLENUM? IS IT DUCTED? IS THE DOOR AT THE MECHANICAL
 CLOSET A LOUVERED DOOR? FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-07-14 Cont ID  
Sent By ccole Date 2022-07-14 Time 16:27 Rev Time 0.00
Received By ccole Date 2022-07-14 Time 16:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-06-02 Cont ID  
Sent By ccole Date 2022-06-02 Time 12:52 Rev Time 0.00
Received By ccole Date 2022-06-02 Time 11:57 Sent To  
Notes
2022-06-02 12:53:381ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22051029
 6/2/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P.1: SHOW THE DISCHARGE LOCATION OF THE NEW WATER
 HEATER DRAIN PAN LINE- SEC. 504.7.2 FBC P.
  
 2) P.2 & P.3: PLEASE PROVIDE THE SIZES OF THE EXISTING
 SANITARY AND WASTE STACKS AND INDICATE HOW THE STACKS
 ARE BRING VENTED. SHOW THE LOCATIONS OF EXISTING VENT
 STACKS AND STACK VENTS- SEE SECS. 912.1.1, 912.2.2, &
 913.1- 913.4 FBC P. PLEASE NOTE THAT THE CURRENT RISERS
 FOR THE LAUNDRY, SECOND BATHROOM, AND MASTER BATHROOMS
 APPEAR TO SHOW NON-COMPLIANT VENTING.
  
 3) A PLUMBING DEMOLITION FLOOR PLAN WOULD HELP EXPEDITE
 THE REVIEW- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-07-22 Cont ID  
Sent By medwards Date 2022-07-22 Time 13:33 Rev Time 0.00
Received By medwards Date 2022-07-22 Time 13:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-07-19 Cont ID  
Sent By jwitmer Date 2022-07-19 Time 10:14 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-07-15 13:56:17MECHANICAL DIGITAL SIGNATURES APPROVED. ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-06 Cont ID  
Sent By jwitmer Date 2022-07-06 Time 11:21 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-05-31 13:28:56DIGITAL SIGNATURES FOR MECHANICAL APPROVED ME