Plan Review Stops For Permit 22050636 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2022-06-29 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-06-29 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-06-29 |
Time |
15:41 |
Sent To |
|
|
Notes |
2022-06-29 15:42:14 | FIRE SPRINKLER PIPE INSPECTION ALSO REQUIRED | | CODE: 603 | | | | FIRE SPRINKLER PERMIT # 22031530 | | | | TEST @ 200PSI FOR 2 HOURS PER NFPA13 | | | | TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13 | | | | CONTRACTOR TO PROVIDE FOR WORKING PRESSURE VERIFICATION | | (I.E. PRESSURE GAUGE 2HRS) | | AND/OR SYSTEM IS CHARGED/DISCHARGED UNDER WORKING | | PRESSURE. (I.E. VISUAL FOR LEAKS | | & INSPECTOR DRAIN AFTER 2 HRS) | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-06-30 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-06-30 |
Time |
09:26 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-06-28 |
Time |
14:24 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
N |
Date |
2022-06-30 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-06-30 |
Time |
09:26 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-06-30 |
Time |
09:26 |
Sent To |
|
|
Notes |
2022-06-30 09:26:55 | LESS THAN 49 HEADS. JG. |
|
|
|