Plan Review Details - Permit 22050636
Plan Review Stops For Permit 22050636
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-06-29 Cont ID  
Sent By pleduc Date 2022-06-29 Time   Rev Time 0.00
Received By pleduc Date 2022-06-29 Time 15:41 Sent To  
Notes
2022-06-29 15:42:14FIRE SPRINKLER PIPE INSPECTION ALSO REQUIRED
 CODE: 603
  
 FIRE SPRINKLER PERMIT # 22031530
  
 TEST @ 200PSI FOR 2 HOURS PER NFPA13
  
 TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13
  
 CONTRACTOR TO PROVIDE FOR WORKING PRESSURE VERIFICATION
 (I.E. PRESSURE GAUGE 2HRS)
 AND/OR SYSTEM IS CHARGED/DISCHARGED UNDER WORKING
 PRESSURE. (I.E. VISUAL FOR LEAKS
 & INSPECTOR DRAIN AFTER 2 HRS)
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-30 Cont ID  
Sent By jgomez Date 2022-06-30 Time 09:26 Rev Time 0.00
Received By jgomez Date 2022-06-28 Time 14:24 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-06-30 Cont ID  
Sent By jgomez Date 2022-06-30 Time 09:26 Rev Time 0.00
Received By jgomez Date 2022-06-30 Time 09:26 Sent To  
Notes
2022-06-30 09:26:55LESS THAN 49 HEADS. JG.