2022-05-26 14:10:08 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 22050617 3514 BROADWAY |
| |
| |
| 1ST REVIEW |
| |
| PLUMBING COMMENTS: DENIED |
| |
| A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| APPROVAL. |
| |
| 1.AS REQUIRED WPB FBC 107.2.1 AND WPB FBC 107.3.5.1.3, |
| THE FOLLOWING ITEMS SHALL BE ADDRESSED AS IS APPLICABLE |
| TO YOUR FACILITY: |
| ***A) MINIMUM PLUMBING FACILITIES |
| ***B) FIXTURE REQUIREMENTS |
| ***C) WATER SUPPLY PIPING |
| ***D) SANITARY DRAINAGE |
| ***E) WATER HEATERS |
| ***F) VENTS |
| ***G) ROOF DRAINAGE |
| ***H) BACKFLOW PREVENTION |
| ***I) IRRIGATION |
| ***J) LOCATION OF WATER SUPPLY LINE |
| ***K) GREASE TRAPS |
| ***L) ENVIRONMENTAL REQUIREMENTS |
| ***M) PLUMBING RISER (SANITARY AND WATER) |
| ***N) DESIGN FLOOD ELEVATION |
| SEE BELOW FOR MORE CLARIFICATION. |
| |
| 2. DUE TO CHANGE IN OCCUPANCY, THE FACILITY SHALL |
| COMPLY WITH THE 2020 FLORIDA BUILDING CODES. PER WPB |
| FBC 107.2.1 PROVIDE THE CURRENT OCCUPANCY AND THE NEW |
| OCCUPANCY OF THIS PROPOSED FACILITY. |
| |
| 3. THE SUBMITTED FLOOR PLAN DOES NOT MATCH THE |
| FOOTPRINT OF THE BUILDING. IT APPEARS THAT THE BUILDING |
| HAS BEEN DIVIDED INTO UNITS IN THE PAST (RE: PERMIT |
| 03090129). PERMIT12070469 INDICATES THE ENTIRE BUILDING |
| WAS DEVOTED TO A SINGLE OCCUPANT. PER WPB FBC 107.2.1, |
| PROVIDE AN OVERALL PLAN OF THE BUILDING AND INDICATE |
| THE SPACE THE SUBMITTED PLAN SPACE WILL OCCUPY. THERE |
| IS RECORD OF MASTER PERMIT 20081406 WITH SUB PERMITS |
| THAT INDICATES BATHROOM ADDITION(S) AND OTHER WORK, |
| HOWEVER I CAN FIND NO PLANS ASSOCIATED WITH THAT WORK. |
| |
| 4. THERE IS A KITCHEN SPACE NOTED. PER WPB FBC 107.2.1, |
| PROVIDE LAYOUT NOTING ALL PLUMBING FIXTURES AND |
| APPLIANCES. INCLUDE REQUIRED CLEAR FLOOR SPACES FOR |
| ACCESSIBLE FIXTURES/APPLIANCES. PLEASE NOTE THAT IF |
| THERE ARE COOKING FACILITIES, PER FBC PL 1003.1, A |
| GREASE INTERCEPTOR WILL BE REQUIRED. |
| |
| 5. PER WPB FBC 107.2.1, PROVIDE THE FOLLOWING: |
| ***A) PLUMBING FIXTURE SCHEDULE LISTING THE REQUIRED |
| PLUMBING FIXTURES, QUANTITY REQUIRED AS REQUIRED BY FBC |
| PL TABLE 403.1 AND ACTUAL FURNISHED. |
| ***B) EXISTING/DEMO FLOOR PLAN PLUMBING SHOWING THE |
| PLUMBING FACILITIES AND ANY DEMO REQUIREMENTS OF |
| EXISTING FIXTURES AND PIPING. |
| ***C) PROPOSED PLUMBING AND ARCHITECTURAL FLOOR PLAN |
| SHOWING ALL PROPOSED PLUMBING FIXTURES AND PIPING |
| ***D) PROVIDE PLUMBING RISER DIAGRAMS OF NEW WATER AND |
| SANITARY PIPING |
| ***E) PROVIDE HOT WATER SOURCE. COMPLY WITH FBC PL |
| CHAPTERS 5 AND 6. |
| ***F) PROVIDE BATHROOM AND JANITOR ROOM WALL FINISHES |
| ADJACENT TO WATER CLOSETS AND SERVICE SINKS SHOWING |
| COMPLIANCE WITH THE FLORIDA BUILDING CODE 2020 7TH |
| EDITION, SECTION 1210.2.2. IF A BATHTUB OR SHOWER IS |
| PROVIDED, SHOW COMPLIANCE WITH SECTION 1210.2.3. |
| ***G) INDICATE ACCESSIBLE RESTROOM(S) COMPLYING WITH |
| THE FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| ***H) PROVIDE DETAILS, PLAN VIEW AND ELEVATION OF |
| ACCESSIBLE PLUMBING FIXTURES SHOWING COMPLIANCE WITH |
| FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION, CHAPTERS |
| 2, 3, 6 AND 8. A FULLY DIMENSIONED FLOOR PLAN OF |
| ACCESSIBLE BATHROOM WITH DIMENSIONED CLEAR FLOOR SPACES |
| AND TURNING SPACE IS REQUIRED. |
| ***I) IF NEW UNDERGROUND PIPING IS REQUIRED, THEN A |
| SLAB REPAIR DETAIL IS REQUIRED. SHOW THE WIDTH OF THE |
| REPAIR, THE MINIMUM THICKNESS AND PSI OF THE CONCRETE |
| TO BE REPLACED. SHOW SIZE, LENGTH, SPACING (ON CENTER), |
| MINIMUM EMBEDMENT AND ANCHORING/ADHESIVE MATERIAL FOR |
| DOWELS. THE REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT |
| OF THE SOIL AS WELL AS THE REQUIRED VAPOR BARRIER OVER |
| WELL COMPACTED SOIL. |
| ***J) PROVIDE PIPING MATERIAL SPEC FOR EACH SYSTEM TO |
| INCLUDE PIPE, VALVES, FITTINGS AND JOINTS. COMPLY WITH |
| FBC PL CHAPTERS 3, 6, 7, 9 AND 11. ALL COMPONENTS IN |
| THE DOMESTIC WATER SYSTEM SHALL BE LEAD FREE IN |
| ACCORDANCE WITH FBC PL 605.2 AND 605.2.1. |
| |
| 6. PER 107.1, PLANS SHALL BE SIGNED AND SEALED BY A |
| REGISTERED DESIGN OFFICIAL IN ACCORDANCE WITH A |
| REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY |
| CHAPTER 471, FLORIDA STATUTES AND 61G15, FLORIDA |
| ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES |
| AND 61G1, FLORIDA ADMINISTRATIVE CODE. |
| IF THE PLANS ARE NOT SIGNED AND SEALED BY A |
| PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN |
| IN ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR THE |
| PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION |
| NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR |
| LICENSED IN THAT TRADE. |
| |
| 7. WPB FBC 109.1; THE VALUATION APPEARS LOW. PROVIDE AN |
| ACCURATE VALUATION OF ALL WORK AND COST. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. |
| |
| END OF COMMENTS. |
| |
| A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| THIS TIME. COMMENTS ABOVE ARE PRELIMINARY AND MAY NOT |
| BE ALL INCLUSIVE. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS |
| AND A RESPONSE NARRATIVE ADDRESSING THE PLUMBING |
| COMMENTS FROM THE FIRST REVIEW. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER PX928 |
| PLUMBING INSPECTOR BN2148 |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| MOBILE 561-246-0882 |
| PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| THURSDAYS |
| |