Plan Review Details - Permit 22050577
Plan Review Stops For Permit 22050577
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-06-14 Cont ID  
Sent By cpuell Date 2022-06-14 Time 10:54 Rev Time 0.00
Received By cpuell Date 2022-06-14 Time 10:54 Sent To  
Notes
2022-06-14 10:54:55WORK TO BE DONE ON SUITES 500, 530, 550 AND 580,
 UPDATED PERMIT

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-06-06 Cont ID  
Sent By cpuell Date 2022-06-06 Time 16:57 Rev Time 0.00
Received By cpuell Date 2022-06-06 Time 16:57 Sent To  
Notes
2022-06-06 16:59:09PLEASE CONTACT [email protected] TO BE ISSUED
 ADDRESSES FOR THE NEW SUITES. PLEASE EMAIL A FLOOR PLAN
 SHOWING THE CURRENT SUITES ON THE FLOOR AND ANOTHER
 FLOOR PLAN SHOWING THE NEW SUITES ON THE FLOOR.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-07-27 Cont ID  
Sent By jwitmer Date 2022-07-27 Time 09:51 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-08-10 Cont ID  
Sent By jwitmer Date 2022-08-10 Time 07:38 Rev Time 0.00
Received By jwitmer Date 2022-08-10 Time 07:15 Sent To  
Notes
2022-08-10 07:38:13SHEET A-3. BUILDING PROVISO: MICROWAVES MUST MEET 2020
 FBC-
 ACCESSIBILITY REQUIREMENTS: 308 REACH RANGES.
 308.2 FORWARD REACH. / 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH
 . 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN
 ONE OR MORE OF THE REACH RANGES SPECIFIED IN 308. 309.4
 OPERATION. OPERABLE
 PARTS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT
 REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS
 SHALL BE 5 POUNDS MAXIMUM.
 JAMES A. WITMER BN, PX, SFP, CBO 8/10/2022
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-07-27 Cont ID  
Sent By jwitmer Date 2022-07-27 Time 10:22 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-07-27 10:22:28SHEET A-3. BUILDING PROVISO: MICROWAVES MUST MEET 2020
 FBC-
 ACCESSIBILITY REQUIREMENTS: 308 REACH RANGES.
 308.2 FORWARD REACH. / 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH
 . 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN
 ONE OR MORE OF THE REACH RANGES SPECIFIED IN 308. 309.4
 OPERATION. OPERABLE
 PARTS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT
 REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS
 SHALL BE 5 POUNDS MAXIMUM.
 JAMES A. WITMER BN, PX, SFP, CBO 7/27/2022
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-08-23 Cont ID  
Sent By jleahy Date 2022-08-23 Time 13:45 Rev Time 0.00
Received By jleahy Date 2022-08-23 Time 13:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-07-13 Cont ID  
Sent By jleahy Date 2022-07-13 Time 14:58 Rev Time 0.00
Received By jleahy Date 2022-07-13 Time 10:04 Sent To  
Notes
2022-07-13 15:05:48FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER DIAGRAM IS INCOMPLETE
  
 PLEASE SHOW SIZE OF CONDUCTORS SIZES, OVER CURRENT
 PROTECTION.
  
 PANELBOARDS FED BY TRANSFORMERS SHALL HAVE A MAIN
 DICONNECT OR MAIN CIRCUIT BREAKER ON THE LSECONDARY
 SIDE PER 408.36

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2022-07-13 Cont ID  
Sent By jleahy Date 2022-07-13 Time 15:20 Rev Time 0.00
Received By jleahy Date 2022-07-13 Time 15:20 Sent To  
Notes
2022-07-13 15:21:21VOICE AND DATA ONLY AS PER PLANS JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-06-14 Cont ID  
Sent By cwalker Date 2022-06-14 Time   Rev Time 0.00
Received By cwalker Date 2022-06-09 Time 12:48 Sent To  
Notes
2022-06-14 13:22:56FIRE PROVISO COMMENTS:
 ALL DOOR HARDWARE WITH LOCKS SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE SIDE OF EGRESS. NFPA 101, 7.2.1.5.3
 FINISH FLOOR MATERIALS (CARPET AND LVT) SHALL MEET
 ESTABLISHED REQUIREMENTS FOR FIRE PERFORMANCE. NFPA
 101, 10.2.7
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-09-01 Cont ID  
Sent By medwards Date 2022-09-01 Time 16:27 Rev Time 0.00
Received By medwards Date 2022-08-29 Time 16:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-23 Cont ID  
Sent By jleahy Date 2022-08-23 Time 13:45 Rev Time 0.00
Received By jleahy Date 2022-07-27 Time 15:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-27 Cont ID  
Sent By jwitmer Date 2022-07-27 Time 10:23 Rev Time 0.00
Received By jwitmer Date 2022-06-06 Time 09:15 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-07-27 Cont ID  
Sent By jwitmer Date 2022-07-27 Time 09:51 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-09-01 Cont ID  
Sent By medwards Date 2022-09-01 Time 08:55 Rev Time 0.00
Received By medwards Date 2022-09-01 Time 08:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-07-28 Cont ID  
Sent By medwards Date 2022-07-28 Time 11:45 Rev Time 0.00
Received By medwards Date 2022-07-28 Time 11:45 Sent To  
Notes
2022-07-28 11:49:56THE OCCUPANT COUNT FOR THE OUTDOOR AIR CALCULATIONS
 MUST MEET THE MINIMUM OCCUPANT COUNT FROM FMC TABLE
 403.3.1.1. PROVIDE THE OUTDOOR AIR CALCULATIONS BASED
 ON THE OCCUPANT COUNT FOR EACH USE OF SPACE FROM TABLE
 403.3.1.1.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-06-29 Cont ID  
Sent By medwards Date 2022-06-29 Time 06:23 Rev Time 0.00
Received By medwards Date 2022-06-29 Time 06:23 Sent To  
Notes
2022-06-29 06:23:511ST REVIEW FMC
 PERMIT: 22050577
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A MECHANICAL DEMO DRAWING. FBC 107.2.1
  
 2) THE NEW CORRIDOR FOR THIS FLOOR HAS 1-HOUR RATED
 WALLS. SHOW HOW YOU ARE PROTECTING THE PENETRATIONS
 WHERE THE DUCTWORK PASSES THROUGH THESE NEW WALLS. FMC
 607
  
 3) SHOW THE RETURN AIR PATH FOR THE RETURN GRILLS IN
 THE CORRIDORS NEAR THE ELEVATORS. FMC 607
  
 4) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH TENANT
 AND EACH SPACE IN THE TENANT SPACE. YOU MUST PROVIDE
 THE OUTDOOR AIR CALCULATIONS BASED ON EACH USE OF SPACE
 IN EACH TENANT SPACE ACCORDING TO FMC 403.3.1.1 AND
 TABLE 403.3.1.
  
 5) THE VAV BOX SCHEDULE IS ONLY SHOWING VAV-1, PROVIDE
 INFORMATION ON ALL VAV?S USED IN THIS PROJECT. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-08-01 Cont ID  
Sent By ccole Date 2022-08-01 Time 11:52 Rev Time 0.00
Received By ccole Date 2022-08-01 Time 11:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-06-27 Cont ID  
Sent By ccole Date 2022-06-27 Time 14:32 Rev Time 0.00
Received By ccole Date 2022-06-27 Time 12:45 Sent To  
Notes
2022-06-27 14:34:021ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22050577
 6/27/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A1 & A3: ACCESSIBLE BREAK ROOM SINK DETAILS
 MISSING PER SEC. 212.3 FBC ACC.
  
 A) SHOW THE CLEAR FLOOR SPACE DIAGRAMS WITH DIMENSIONS
 POSITIONED FOR EITHER A FORWARD OR PARALLEL APPROACH-
 SEC. 606.2.
  
 B) SHOW THE HEIGHTS OF THE SINK RIMS OR COUNTER
 SURFACES WHICHEVER IS THE HIGHEST- SEC. 606.3.
  
 C) SHOW THE KNEE AND TOES CLEARANCES FOR ACCESSIBLE
 SINKS AND CABINETS DESIGNED FOR FORWARD APPROACHES-
 FIGURES 306.2 & 306.3.
  
 2) P0-1: CORRECT THE PUBLIC LAVATORY LABELING IN THE
 WATER HEATER DETAIL TO INDICATE BREAKROOM SINK- SEC.
 107.2.1 WPB.
  
 3) P0-1: THE ASSE 1070 MIXING VALVE SHOWN IN THE DETAIL
 MUST BE REPLACED WITH A MIXING VALVE THAT WILL LIMIT
 HOT WATER TEMPERATURE- SEC. 607.1.1 FBC P.
  
 4) P0-1: CORRECT THE SUMP PUMP DETAIL SPECIFYING THE
 INSTALLATION LOCATION AT THE BOTTOM OF THE ELEVATOR AND
 PROVIDE ACCURATE INSTALLATION DETAILS- SEC. 107.2.1
 WPB.
  
 5) P0-1: CORRECT THE SUMP PUMP DETAIL TO SHOW THE
 CORRECT LOCATIONS OF THE REQUIRED FULL OPEN VALVE AND
 CHECK VALVE- SEC. 712.2 FBC P.
  
 6) PP5.1: THE ISOMETRIC DRAWINGS SHOWING VENTS TO RIDGE
 CONFLICTS WITH NOTE 1 ON P2.1. WIICH SHOWS CONNECTIONS
 INTO EXISTING VENT PIPE RUNS IN THE SPACE- SEC. 107.2.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-09-01 Cont ID  
Sent By medwards Date 2022-09-01 Time 16:26 Rev Time 0.00
Received By medwards Date 2022-09-01 Time 16:26 Sent To  
Notes
2022-09-01 09:10:21MECHANICAL DRAWINGS MUST HAVE THE DESIGNERS ORIGINAL
 DIGITAL SIGNATURE. FS 471/481.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-08-01 Cont ID  
Sent By ccole Date 2022-08-01 Time 11:53 Rev Time 0.00
Received By ccole Date 2022-08-01 Time 11:53 Sent To  
Notes
2022-07-28 11:50:55MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-25 Cont ID  
Sent By rwbrown Date 2022-06-25 Time 08:27 Rev Time 0.00
Received By rwbrown Date 2022-06-25 Time 08:27 Sent To  
Notes
***NONE***