Plan Review Details - Permit 22050542
Plan Review Stops For Permit 22050542
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-05-31 Cont ID  
Sent By shill Date 2022-05-31 Time 13:35 Rev Time 0.00
Received By shill Date 2022-05-31 Time 13:35 Sent To  
Notes
2022-05-31 13:36:07ISSUED AT APPLICANT'S RISK
 A CURSORY REVIEW HAS BEEN DONE ON THE EXIT STRATEGY,
 REMOTENESS OF EXITS
 NO REVIEW WAS DONE OF THE DISTANCE TO PROPERTY LINE AND
 PERCENTAGE OF OPENINGS. REDUCED OPENINGS OR FIRE RATED
 OPENINGS MAY BE REQUIRED UPON A THOROUGH BUILDING
 REVIEW
 PROVISO: WHEN RESUBMITTING OR SUBMITTING ANY PAGES,
 PLEASE INCLUDE THE THRESHOLD STATEMENT AS REQUIRED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-05-31 Cont ID  
Sent By shill Date 2022-05-31 Time 12:24 Rev Time 0.00
Received By shill Date 2022-05-26 Time 06:15 Sent To  
Notes
2022-05-26 06:20:30SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THIS REVIEW IS BEING DONE UNDER BUILDING SO THE
 THRESHOLD REVIEW CAN BE FOCUSED ON THE SPECIAL
 INSPECTOR AGREEMENT.
  
 FS553.79(9)(D):
  
 (D)?ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS CHAPTER AND CHAPTER 633.
  
 FOR 300 BANYAN, BLISSY & NYITRAY (STRUCTURAL ENGINEERS)
 HAS THIS STATEMENT ON THIS OFFICE HIGH RISE:
  
 TO THE BEST OF THE STRUCTURAL ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODE.
  
 I UNDERSTAND THAT THE STRUCTURAL ENGINEER MAY OBJECT TO
 STATING COMPLIANCE WITH A CODE THAT THEY DO NOT KNOW
 (FS633), SO IT APPEARS THAT THIS WOULD BE REQUIRED OF
 THE ARCHITECT.
  
 TO RESOLVE - FOR THE FOUNDATION PERMIT, PLEASE REVISE
 **ONE** PAGE TO INCLUDE THE THRESHOLD STATEMENT AND
 EMAIL TO ME. PLEASE DO NOT SELECT A PAGE THAT HAS BEEN
 STAMPED BY ANOTHER DISCIPLINE. THIS REVIEW WILL THEN BE
 PASSED WITH PROVISOS:
  
 ISSUED AT APPLICANT'S RISK
 A CURSORY REVIEW HAS BEEN DONE ON THE EXIT STRATEGY,
 REMOTENESS OF EXITS
 NO REVIEW WAS DONE OF THE DISTANCE TO PROPERTY LINE AND
 PERCENTAGE OF OPENINGS. REDUCED OPENINGS OR FIRE RATED
 OPENINGS MAY BE REQUIRED UPON A THOROUGH BUILDING
 REVIEW
 PROVISO: WHEN RESUBMITTING OR SUBMITTING ANY PAGES,
 PLEASE INCLUDE THE THRESHOLD STATEMENT AS REQUIRED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-31 Cont ID  
Sent By shill Date 2022-05-31 Time 12:26 Rev Time 0.00
Received By shill Date 2022-05-24 Time 10:19 Sent To  
Notes
2022-05-24 10:20:17SEE REVIEW #2

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-05-12 Cont ID  
Sent By jleahy Date 2022-05-12 Time 14:51 Rev Time 0.00
Received By jleahy Date 2022-05-12 Time 11:47 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2022-05-26 Cont ID  
Sent By rrossano Date 2022-05-26 Time   Rev Time 0.00
Received By rrossano Date 2022-05-26 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-05-23 Cont ID  
Sent By rrossano Date 2022-05-23 Time   Rev Time  
Received By rrossano Date 2022-05-23 Time   Sent To  
Notes
2022-05-23 11:49:48UNDER FORMAL ENGINEERING SUBMITTAL REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-05-12 Cont ID  
Sent By pleduc Date 2022-05-12 Time   Rev Time 0.00
Received By pleduc Date 2022-05-12 Time 11:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-06-01 Cont ID  
Sent By shill Date 2022-06-01 Time 16:32 Rev Time 0.00
Received By shill Date 2022-05-31 Time 16:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-31 Cont ID  
Sent By pvalenti Date 2022-05-31 Time 16:16 Rev Time 0.00
Received By pvalenti Date 2022-05-25 Time 08:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-24 Cont ID  
Sent By shill Date 2022-05-24 Time 11:01 Rev Time 0.00
Received By shill Date 2022-05-12 Time 09:00 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2022-05-25 Cont ID  
Sent By shill Date 2022-05-25 Time 12:38 Rev Time 0.00
Received By shill Date 2022-05-25 Time 12:38 Sent To  
Notes
2022-05-25 12:38:54IMPACT FEES DEFERRED, TO BE PAID PRIOR TO ISSUANCE OF A
 VERTICAL CONSTRUCTION PERMIT
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-05-24 Cont ID  
Sent By shill Date 2022-05-24 Time 11:00 Rev Time 0.00
Received By shill Date 2022-05-24 Time 11:00 Sent To  
Notes
2022-05-24 11:01:26PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION WILL OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE EMAIL THE RECEIPT
 TO [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-31 Cont ID  
Sent By shill Date 2022-05-31 Time 13:37 Rev Time 0.00
Received By shill Date 2022-05-31 Time 13:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-05-24 Cont ID  
Sent By shill Date 2022-05-24 Time 11:00 Rev Time 0.00
Received By shill Date 2022-05-24 Time 10:59 Sent To  
Notes
2022-05-24 11:00:44ARCHITECTURAL PAGES APPEAR OK
 STRUCTURAL PAGES ARE NOT DIGITALLY SIGNED. FS471,
 DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS.
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2022-06-03 Cont ID  
Sent By shill Date 2022-06-03 Time 14:16 Rev Time 0.00
Received By shill Date 2022-06-03 Time 14:16 Sent To  
Notes
2022-06-03 14:17:12AN UPDATED SI AGREEMENT WAS RECEIVED VIA EMAIL. THE
 SI'S SIGNATURE IS NOTARIZED RATHER THAN SEALED.
  
 PROVISO: PROVIDE AN AGREEMENT EITHER DIGITALLY SIGNED
 BY THE SI OR DROP OFF AN ORIGINAL.
  
  
 UNIVERSAL ENGINEERING SERVICES
 SI - RODOLFO A GOZEMBACH, PE 45226
 SHANKER RAJBHANDARI, BN 6096
 CARLTON CROOK, BN3909
  
 CARY LYLE SHIPPERT, CGC1511537

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2022-06-01 Cont ID  
Sent By shill Date 2022-06-01 Time 15:53 Rev Time 0.00
Received By shill Date 2022-06-01 Time 15:53 Sent To  
Notes
2022-06-01 16:12:48SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 UNIVERSAL ENGINEERING SERVICES
 SI - RODOLFO A GOZEMBACH, PE 45226
 SHANKER RAJBHANDARI, BN 6096
 MAYRON MONTOYA, BN7899
 CARLTON CROOK, BN3909
 GASTON ALONSO, BN6390
  
 CARY LYLE SHIPPERT, CGC1511537
  
  
 THE SI AGREMENT IS A CONTRACT. THE PDF UPLOADED STARTS
 ON PAGE 7, 7, THEN 6, ETC. THE PDF SHOULD INCLUDE ALL
 PAGES, INCLUDING PAGES 1-6 WHICH INCLUDES WHAT THE
 INSPECTORS, CONTRACTOR, AND OWNER ARE AGREEING TO. THE
 SI AGREEMENT HAS OTHER DOCUMENTS INSERTED, PLEASE
 REMOVE. IT SHOULD BE ONE PDF WHICH INCLUDES ALL
 REQUIRED SIGNATURES AND EXCLUDES PAGES NOT IN OUR SI
 AGREEMENT. IT IS TO BE SIGNED BY ALL PARTIES.
  
 THE OWNER'S SIGNATURE IS IN THE DOCUMENT TWICE. EACH
 PAGE SHOULD BE UNIQUE OTHER THAN INSPECTORS,
  
 IT APPEARS THAT SOME INSPECTORS SIGNED THE SI AGREEMENT
 (TITLED "THRESHOLD/SPECIAL INSPECTOR AGREEMENT OF
 UNDERSTANDING") AND OTHERS SIGNED THE RESIDENT
 INSPECTOR AGREEMENT (TITLED "RESIDENT/SPECIAL
 INSPECTORS AGREMENT OF UNDERSTANDING"). NOT THAT THIS
 IS PAGE 15 OF THE RESIDENT INSPECTOR AGREMENT. SINCE
 THE SIGNED PAGES HAVE BEEN DETACHED FROM THE AGREEMENT,
 THE AGREEMENT ITSELF DOESN'T MAKE SENSE BECUASE THEY
 AREN'T AGREEING TO ANYTHING, SEE THE LANGUAGE "THIS
 AGREEMENT" ON EACH PAGE.
  
 THE SI PAGE PROPOSES RODOLFO A GOZEMBACH, PE 45226 AS
 THE SI, THE RESIDENT INSPECTOR AGREEMENT PROPOSES
 HECTOR VERGARA, PE25764. THE RESIDENT INSPECTOR PAGES
 SHOULD NOT BE SUBMITTED, ALL PARTIES SHOULD SIGN THE SI
 AGREEMENT, BUT ENSURE THAT THE CORRECT SI SIGNS THE
 AGREEMENT.
  
 THE PAGES WHERE THE INSPECTORS SIGNED ON THE
 CONTRACTOR'S PAGE ON THE RESIDENT INSPECTOR AGREEMENT
 ARE STILL IN THE PDF, REMOVE.
  
 REMOVE ALL DOCUMENTS THAT ARE NOT A PART OF THE CITY'S
 SI AGREEMENT. COPIES OF LICENSES CAN BE SUBMITTED IN A
 SINGLE SEPARATE PDF. RESUMES ARE NOT REQUIRED.
  
 PER FLORIDA BOARD OF PROFESSIONAL ENGINEERS, WHEN
 SIGNING AS AN ENGINEER, THE ENGINEER IS REQUIRED TO
 COMPLY WITH THE REQUIREMENT FOR AN ORIGINAL SIGNATURE
 AND SEAL. IF THE ENGINEER DOES NOT HAVE A DIGITAL
 SIGNATURE, PLEASE SCAN AND DROP OFF AN ORIGINAL TO THE
 BUILDING DIVISION. THE DESCRIPTION ON THE SUBMITTAL
 FORM SHOULD BE "SIGNATURE PAGE FOR SI AGREEMENT".
 ORIGINAL SIGNATURES FOR OTHERS IS NOT REQUIRED.
  
 IF YOU NEED A CLEAN PDF, PLEASE EMAIL
 [email protected] AND REQUEST THE SI AGREEMENT.
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2022-05-31 Cont ID  
Sent By pvalenti Date 2022-05-31 Time 14:51 Rev Time 0.00
Received By pvalenti Date 2022-05-26 Time 06:20 Sent To  
Notes
2022-05-31 14:52:55PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
  
 THRESHOLD REVIEW DENIED:
  
 1.) THE PAGES TITLED RESIDENT/SPECIAL INSPECTORS
 AGREEMENT OF UNDERSTANDING AT TOP OF PAGES ARE NOT
 APPLICABLE.
 2.) THE (4) STATE LICENSED FS 468 INSPECTORS (BN 3909,
 BN6096, BN 6390, & BN 7899) HAVE COMPLETED THE CORRECT
 SECTIONS OF THRESHOLD/SPECIAL INSPECTORS AGREEMENT OF
 UNDERSTANDING. (OK)
 3.) THRESHOLD INSPECTOR RODOLFO A. GONZEMBACH, PE
 45226/SI 1065, DID NOT PROVIDE ENGINEER'S SEAL UNDER
 HIS SIGNATURE AS REQUIRED ON THRESHOLD/SPECIAL
 INSPECTOR AGREEMENT OF UNDERSTANDING. PLEASE PROVIDE
 CORRECT INFORMATION.
 4.) THRESHOLD INSPECTOR HECTOR VERGARA, PE 25764/SI
 0283, DID NOT DID NOT PROVIDE ENGINEER'S SEAL UNDER HIS
 SIGNATURE AS REQUIRED ON THRESHOLD/SPECIAL INSPECTOR
 AGREEMENT OF UNDERSTANDING. ALSO, THE RESIDENT/SPECIAL
 INSPECTOR FORM IS NOT APPLICABLE. PLEASE PROVIDE
 CORRECT INFORMATION.
 5.) THE FLORIDA LICENSED CONTRACTOR SECTION ON THE
 THRESHOLD/SPECIAL INSPECTOR AGREEMENT OF UNDERSTANDING
 MUST BE COMPLETED BY THE CONTRACTOR.
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2022-05-18 Cont ID  
Sent By aaponte Date 2022-05-18 Time 16:56 Rev Time 0.00
Received By aaponte Date 2022-05-18 Time 16:56 Sent To  
Notes
***NONE***