2022-07-07 11:17:45 | PLAN REVIEW BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| BU1635 BN4338 |
| ASFPM CFM US-21-11935 |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| NFPA 70 2017 EDITION NEC 2017 |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. VALUE |
| PROVIDE AN ESTIMATED SQUARE FOOTAGE OF STUCCO. |
| |
| CITY OF WPB CHPT.1 VALUE |
| 109.3 BUILDING PERMIT VALUATIONS. |
| |
| 1A. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE |
| OF WORK. |
| 1B. THE PERMIT VALUATION AND PERMIT FEE MUST BE |
| COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED |
| CONTRACTOR WOULD PROVIDE. THIS INCLUDES ALL LABOR, |
| MATERIALS AND RENTALS OF EQUIPMENT TO PERFORM THE SCOPE |
| OF WORK. |
| 1C. YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY |
| THE OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT |
| RENTAL TO VERIFY VALUE. |
| FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| BUILDING OFFICIAL. |
| |
| 2.PROVIDE A DETAIL OF THE PROPOSED STUCCO SYSTEM TO BE |
| APPLIED. IDENTIFY WALL TYPE (WOOD/CMU). |
| EACH STUCCO SYSTEM SHALL INCLUDE THE FOLLOWING: |
| |
| R703.2WATER-RESISTIVE BARRIER. (HOUSE WRAP) |
| ONE LAYER OF NO. 15 ASPHALT FELT, FREE FROM HOLES AND |
| BREAKS, COMPLYING WITH ASTM D226 FOR TYPE 1 FELT OR |
| OTHER APPROVED WATER-RESISTIVE BARRIER SHALL BE APPLIED |
| OVER STUDS OR SHEATHING OF ALL EXTERIOR WALLS. NO. 15 |
| ASPHALT FELT SHALL BE APPLIED HORIZONTALLY, WITH THE |
| UPPER LAYER LAPPED OVER THE LOWER LAYER NOT LESS THAN 2 |
| INCHES (51 MM). WHERE JOINTS OCCUR, FELT SHALL BE |
| LAPPED NOT LESS THAN 6 INCHES (152 MM). OTHER APPROVED |
| MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| WATER-RESISTIVE BARRIER MANUFACTURER?S INSTALLATION |
| INSTRUCTIONS. THE NO. 15 ASPHALT FELT OR OTHER APPROVED |
| WATER-RESISTIVE BARRIER MATERIAL SHALL BE CONTINUOUS TO |
| THE TOP OF WALLS AND TERMINATED AT PENETRATIONS AND |
| BUILDING APPENDAGES IN A MANNER TO MEET THE |
| REQUIREMENTS OF THE EXTERIOR WALL ENVELOPE AS DESCRIBED |
| IN SECTION R703.1. THE WATER RESISTIVE BARRIER IS NOT |
| REQUIRED FOR DETACHED ACCESSORY BUILDINGS. |
| |
| R703.7.1LATH. (PAPER BACKED) |
| LATH AND LATH ATTACHMENTS SHALL BE OF |
| CORROSION-RESISTANT MATERIALS. EXPANDED METAL OR WOVEN |
| WIRE LATH SHALL BE ATTACHED WITH 11/2-INCH-LONG (38 |
| MM), 11 GAGE NAILS HAVING A 7/16-INCH (11.1 MM) HEAD, |
| OR 11/2-INCH-LONG (22.2 MM), 16 GAGE STAPLES, SPACED IN |
| ACCORDANCE WITH ASTM C1063 OR C1787, OR AS OTHERWISE |
| APPROVED. |
| |
| R703.7.2PLASTER. |
| PLASTERING WITH CEMENT PLASTER SHALL BE NOT LESS THAN |
| THREE COATS WHERE APPLIED OVER ANY TYPE OF |
| CODE-APPROVED LATH AND SHALL BE NOT LESS THAN TWO COATS |
| WHERE DIRECTLY APPLIED OVER MASONRY, CONCRETE, CLAY |
| BRICK, STONE OR TILE. IF THE PLASTER SURFACE IS |
| COMPLETELY COVERED BY VENEER OR OTHER FACING MATERIAL |
| OR IS COMPLETELY CONCEALED, PLASTER APPLICATION NEED BE |
| ONLY TWO COATS, PROVIDED THE TOTAL THICKNESS IS AS SET |
| FORTH IN TABLE R702.1(1). |
| ON WOOD-FRAME CONSTRUCTION WITH AN ON-GRADE FLOOR SLAB |
| SYSTEM, EXTERIOR PLASTER SHALL BE APPLIED TO COVER, BUT |
| NOT EXTEND BELOW, LATH, PAPER AND SCREED. CEMENT |
| PLASTER SHALL BE IN ACCORDANCE WITH ASTM C926. |
| |
| R703.7EXTERIOR PLASTER. |
| INSTALLATION OF THESE MATERIALS SHALL BE IN COMPLIANCE |
| WITH ASTM C926, ASTM C1063 OR ASTM C1787 AND THE |
| PROVISIONS OF THIS CODE. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |
| |
| |
| |