Plan Review Stops For Permit 22041540 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
P |
Date |
2022-08-10 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2022-08-10 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2022-08-10 |
Time |
11:27 |
Sent To |
|
|
Notes |
2022-08-10 11:28:07 | PASSED PER RESPONCE TO COMMENTS. |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2022-05-24 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2022-05-24 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2022-05-24 |
Time |
09:50 |
Sent To |
|
|
Notes |
2022-05-24 09:52:04 | ARE OTHER SUITES EFFECTED BY THIS EXPANISION. PLLEASE | | PROVIDE A FLOOR PLAN SHOWING EVERY SUITE ON THAT FLOOR. | | PLEASE EMAIL TO [email protected] FOR FURTHER | | QUESTIONS YOU CAN ALSO CALL 561-805-6659 |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
3 |
Status |
P |
Date |
2022-09-14 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-09-14 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-09-14 |
Time |
15:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
2 |
Status |
F |
Date |
2022-08-23 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-08-23 |
Time |
16:48 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-08-23 |
Time |
16:48 |
Sent To |
|
|
Notes |
2022-08-23 16:49:11 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | CAN BE FOUND ON THEIR WEBSITE: | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2022-07-22 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-07-22 |
Time |
11:40 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-07-22 |
Time |
11:25 |
Sent To |
|
|
Notes |
2022-07-22 11:40:37 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | CAN BE FOUND ON THEIR WEBSITE: | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2022-08-23 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-08-23 |
Time |
16:47 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-08-23 |
Time |
16:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-07-22 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-07-22 |
Time |
11:44 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-07-22 |
Time |
11:25 |
Sent To |
|
|
Notes |
2022-07-22 11:44:51 | BUILDOUT | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE SHOW MOP SINK WALL FINISH TO COMPLY WITH FBC | | 1210.2.2 WALLS AND PARTITIONS. | | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE | | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, | | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS | | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT | | CONSIDERED A HARD SURFACE) | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2022-09-01 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-09-01 |
Time |
15:32 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-09-01 |
Time |
13:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2022-06-30 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-06-30 |
Time |
14:55 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-06-30 |
Time |
14:50 |
Sent To |
|
|
Notes |
2022-06-30 14:57:33 | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | | | 1) VALUE OF PERMIT SHOWN IS LOW PLEASE SUBMIT A COST | | BREAK DOWN OF ALL MATERIALS AND LABOR FOR THE COMPLETRE | | JOB. | | | | 2) CONFERENCE ROOM OUTLETS AND FLOOR OUTLETS NOT PER | | 210.71 | | | | 210.71(B) RECEPTACLE OUTLETS REQUIRED. THE TOTAL NUMBER | | OF RECEPTACLE OUTLETS, INCLUDING FLOOR OUTLETS AND | | RECEPTACLE OUTLETS IN FIXED FURNITURE, SHALL NOT BE | | LESS THAN AS DETERMINED IN (1) AND (2). THESE | | RECEPTACLE OUTLETS SHALL BE PERMITTED TO BE LOCATED AS | | DETERMINED BY THE DESIGNER OR BUILDING OWNER. | | (1) RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE | | OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH | | 210.52(A)(1) THROUGH (A)(4). | | (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM THAT IS AT | | LEAST 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF | | AT LEAST 20 M2 (215 FT2) SHALL HAVE AT LEAST ONE | | RECEPTACLE OUTLET LOCATED IN THE FLOOR AT A DISTANCE | | NOT LESS THAN 1.8 M (6 FT) FROM ANY FIXED WALL FOR EACH | | 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR SPACE. | | |
|
|
Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
Rev No |
1 |
Status |
P |
Date |
2022-09-01 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-09-01 |
Time |
15:33 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-09-01 |
Time |
15:33 |
Sent To |
|
|
Notes |
2022-09-01 15:33:38 | VOICE DATA AND TV AS PER PLANS JLEAHY |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2022-08-08 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2022-08-08 |
Time |
|
Rev Time |
0.00 |
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2022-08-08 09:21:04 | FIRE PROVISO: | | | | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE | | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS. | | | | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING | | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP | | DRAWINGS. | | | | C. WALKER | | | | 561-804-4762 | | | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2022-05-27 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-05-27 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-05-27 |
Time |
13:09 |
Sent To |
|
|
Notes |
2022-05-27 13:13:20 | FIRE PROVISO: | | | | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE | | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS | | | | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING | | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP | | DRAWINGS. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
P |
Date |
2022-09-01 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-09-01 |
Time |
15:33 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-08-06 |
Time |
06:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-07-22 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-07-22 |
Time |
11:47 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-05-24 |
Time |
08:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
N |
Date |
2022-07-22 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-07-22 |
Time |
11:40 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-07-22 |
Time |
11:40 |
Sent To |
|
|
Notes |
2022-07-22 11:41:57 | NO CHANGE OF OCCUPANCY TYPE - NO ADDED SQUARE FOOTAGE |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2022-08-19 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-08-19 |
Time |
16:17 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-08-19 |
Time |
16:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2022-06-17 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-06-17 |
Time |
15:19 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-06-17 |
Time |
15:19 |
Sent To |
|
|
Notes |
2022-06-17 15:24:19 | THE MECHANICAL EQUIPMENT SIZING CALCULATIONS SHOULD | | REFLECT THE CITY OF WEST PALM BEACH AND NOT MIAMI. FBC | | 107.2.1 | | | | PROVIDE THE ENERGY CALCULATIONS FOR THE ADDED SPACE. | | FEC 101.5.1.1.2 | | | | PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON THE | | OCCUPANCY CLASSIFICATIONS FOR EACH USE OF SPACE FROM | | FMC TABLE 403.3.1.1 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
1 |
Status |
P |
Date |
2022-07-22 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-07-22 |
Time |
11:34 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-07-22 |
Time |
11:34 |
Sent To |
|
|
Notes |
2022-07-22 11:39:48 | NOT A SUBSTANTIAL IMPROVEMENT | | | | AE 14 | | | | BUILDING VALUE = 8,289,522.00 / 2 = 4,144,761.00 | | | | JOB VALUE = 75,000.00 | | | | 5YR CUMULATIVE = 75,000.00 | | | | TOTAL JOB VALUE OVER 5 YRS = 150,000.00 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2022-08-22 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-08-22 |
Time |
10:43 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-08-22 |
Time |
08:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2022-06-14 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-06-14 |
Time |
14:57 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-06-14 |
Time |
11:44 |
Sent To |
|
|
Notes |
2022-06-14 16:19:01 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT-22041540 | | 6/14/2022 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEETS A0.0 & P0.1: PROVIDE PLUMBING FIXTURE | | CALCULATIONS IN COMPLIANCE WITH SEC. 810.1 FBC EX, AND | | TABLE 403.1 FBC P. PROVIDE A SCHEDULE INDICATING THE | | REQUIRED AND PROVIDED NUMBER OF FIXTURES. | | | | 2) P-1.1: THE 1/2-INCH HW SUPPLY PIPES ARE EXCEEDING | | THE 0.5 FT. MAXIMUM ALLOWABLE LENGTHS TO THE LAVATORY | | FAUCETS- TABLE C404.5.1 FBC EC. A RECIRCULATION PUMP | | FOR THE HW SYSTEM OR POINT OF USE WATER HEATERS ARE | | REQUIRED. | | | | 3) P-1.1: TEMPERED OR COLD WATER SHALL BE DELIVERED | | FROM THE NEW LAVATORIES- SEC. 419.4 FBC P. PROVIDE ASSE | | 1070 APPROVED MIXING VALVES- SEC. 607.1.2 FBC P. | | | | 4) P-1.1: A MEANS OF LIMITING THE HW DELIVERY | | TEMPERATURES TO THE MOP SINK AND BREAK ROOM SINK IS | | REQUIRED PER SEC. 607.1.1 FBC P. | | | | 5) P-1.1: THE MOP SINK FIXTURE DRAIN SHALL DISCHARGE | | DOWNSTREAM OF THE BATHROOM HORIZONTAL WET VENT- SEC. | | 912.1 FBC P. | | | | 6) P-1.1: PROVIDE A WATER HAMMER ARRESTOR AND BACKFLOW | | PREVENTER FOR THE WATER SUPPLY LINE TO THE | | REFRIGERATOR- SEC. 604.9 AND 608.3 FBC P. | | | | 7) A-3.0: PROVIDE CLEAR FLOOR SPACE DIAGRAMS AND | | DIMENSIONS FOR THE ACCESSIBLE WATER CLOSETS AND | | LAVATORIES- SECS. 604.3 & 606.2 FBC ACC. | | | | 8) A-3.0: THE SPECIFIED PAINTED GYPSUM WALL BOARD FOR | | THE FIXTURE SURROUNDS IN THE BATHROOMS AND AT THE MOP | | SINK IS NOT IN COMPLIANCE WITH SEC. 310.3 FBC P AND | | SEC. 1210.2.2 FBC B- GYPSUM WALL BOARD IS NOT A HARD, | | NONABSORBENT MATERIAL. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | 2022-06-14 14:58:16 | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2022-08-19 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-08-19 |
Time |
16:19 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-08-19 |
Time |
16:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2022-07-22 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-07-22 |
Time |
11:47 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-07-22 |
Time |
11:47 |
Sent To |
|
|
Notes |
2022-06-30 14:59:08 | ELECTRICAL PAGES SIGNATURE IS APPROVED JLEAHY |
|
|