Plan Review Details - Permit 22041501
Plan Review Stops For Permit 22041501
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 6 Status P Date 2023-01-25 Cont ID  
Sent By lmarchan Date 2023-01-25 Time 13:49 Rev Time 0.00
Received By lmarchan Date 2023-01-25 Time 13:49 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 5 Status F Date 2023-01-25 Cont ID  
Sent By lmarchan Date 2023-01-25 Time 09:31 Rev Time 0.00
Received By lmarchan Date 2023-01-25 Time 09:31 Sent To  
Notes
2023-01-25 09:31:37LETTER NEEDS TO STATE FOLLOWING:
  
 "THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY"

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status F Date 2023-01-11 Cont ID  
Sent By lmarchan Date 2023-01-11 Time 08:02 Rev Time 0.00
Received By lmarchan Date 2023-01-11 Time 08:02 Sent To  
Notes
2023-01-11 08:02:24PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT
  
 "THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY"
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2022-10-17 Cont ID  
Sent By rmcphers Date 2022-10-17 Time 16:01 Rev Time 0.00
Received By rmcphers Date 2022-10-17 Time 16:01 Sent To  
Notes
2022-10-17 16:01:47PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT
  
 "THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY"
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-08-01 Cont ID  
Sent By rmcphers Date 2022-08-01 Time 15:03 Rev Time 0.00
Received By rmcphers Date 2022-08-01 Time 15:03 Sent To  
Notes
2022-08-01 15:03:47PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT
  
 "THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY"
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-06-29 Cont ID  
Sent By rmcphers Date 2022-06-29 Time 10:48 Rev Time 0.00
Received By rmcphers Date 2022-06-29 Time 10:45 Sent To  
Notes
2022-06-29 10:46:43PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT
  
 "THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY"
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-10-17 Cont ID  
Sent By rmcphers Date 2022-10-17 Time 15:58 Rev Time 0.00
Received By rmcphers Date 2022-10-17 Time 15:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-01 Cont ID  
Sent By rmcphers Date 2022-08-01 Time 15:02 Rev Time 0.00
Received By rmcphers Date 2022-08-01 Time 15:02 Sent To  
Notes
2022-08-01 15:02:31CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 2ND REVIEW
  
 CORRECTIONS NEEDED -
  
 FOR THE 2ND FLOOR - PLEASE SHOW THE TYPE OF FLOORING TO
 BE INSTALLED IN EACH ROOM
  
 1) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 2). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO
 VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING
 TO PROJECTDOX ( [email protected] )
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-06-29 Cont ID  
Sent By rmcphers Date 2022-06-29 Time 10:49 Rev Time 0.00
Received By rmcphers Date 2022-06-29 Time 10:46 Sent To  
Notes
2022-06-29 10:48:51CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 FOR THE 2ND FLOOR - PLEASE SHOW THE TYPE OF FLOORING TO
 BE INSTALLED IN EACH ROOM
  
 1) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 2). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO
 VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING
 TO PROJECTDOX ( [email protected] )
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2023-01-25 Cont ID  
Sent By mpeterso Date 2023-01-25 Time 13:25 Rev Time 0.00
Received By mpeterso Date 2023-01-25 Time 13:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-10-18 Cont ID  
Sent By mpeterso Date 2022-10-18 Time 10:27 Rev Time 0.00
Received By mpeterso Date 2022-10-17 Time 16:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-08-02 Cont ID  
Sent By mpeterso Date 2022-08-02 Time 08:03 Rev Time 0.00
Received By mpeterso Date 2022-08-02 Time 08:02 Sent To  
Notes
2022-08-02 08:03:31PREVIOUS COMMENTS NOT ADDRESSED

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-06-09 Cont ID  
Sent By mpeterso Date 2022-06-09 Time 09:18 Rev Time 0.00
Received By mpeterso Date 2022-06-08 Time 16:08 Sent To  
Notes
2022-06-09 09:19:31ELECTRIC REVIEW FAILED
  
 1)VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PLEASE PROVIDE A BREAKDOWN OF ALL MATERIALS AND
 LABOR, OR, AT YOUR DISCRETION, PROVIDE A SIGNED
 CONTRACTOR OR PROVIDE A REASONABLE VALUE. WPB F.B.C.
 109.3
 2) APARTMENT RISER DIAGRAMS DETAIL (4) INDIVIDUAL
 SERVICES. THIS DOES NOT COMPLY WITH NEC 230.2 A
 BUILDING OR OTHER STRUCTURE SERVED
 SHALL BE SUPPLIED BY ONLY ONE SERVICE. PLEASE CORRECT
 AS APPLICABLE.
 3) SMOKE ALARMS ARE NOT DETAILED AS PER FBC R314.3
 LOCATION AND FBC 314.3.1 INSTALLATION NEAR COOKING
 APPLIANCES. PLEASE CORRECT AS APPLICABLE.
 4) COMMON AREA ELECTRIC (LIGHTING, WASHER, DRYER ETC.)
 POWER SUPPLY IS NOT SHOWN ON PLANS OR PANEL SCHEDULES.
 FBC 107.2. PLEASE CORRECT AS APPLICABLE.
 5)PLEASE PROVIDE LOCATION OF MAIN ELECTRIC SERVICE ON A
 SITE PLAN. FBC 107.2
 6) EXTERIOR LIGHT AT DOOR WAY ON UNIT B DOES NOT DETAIL
 ANY CONTROLLING SWITCH. PLEASE CORRECT AS APPLICABLE.
 7) PLEASE PROVIDE A SITE AND FLOOR PLAN DETAILING
 EXISTING CONDITIONS. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-10-11 Cont ID  
Sent By pleduc Date 2022-10-11 Time   Rev Time 0.00
Received By pleduc Date 2022-10-11 Time 11:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-07-27 Cont ID  
Sent By pleduc Date 2022-07-27 Time   Rev Time 0.00
Received By pleduc Date 2022-07-27 Time 11:40 Sent To  
Notes
2022-07-27 11:53:08THE PREVIOUS FAILED FIRE COMMENTS DO NOT SEEM TO BE
 ADDRESSED ION THE RESUBMITTAL.
  
 THE IS A NOTE # 5 ON THE 1ST AND 2ND FLOOR PLANS
 STATING NEW FLOORING AND PAINT.
  
 THERE IS NO INDICATION OF WHAT THAT FLOORING TYPE(S) IS
 NOR WHERE IT WILL BE LOCATED.
  
 PLEASE REVIEW AND ADDRESS THE COMMENTS.
  
 THE COMMENTS ARE RESUBMITTED BELOW:
  
  
  
 *******************************************************
 **************************
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF NEW FLOORING, BUT NO
 INDICATION OF WHAT TYPE OF FLOORING.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE TYPE OF
 FINISH FLOORING PRODUCT AND PRODUCT NAME AND SPEC SHEET
 THAT INDICATES THE FIRE BEHAVIOR RATING.
  
 FYI.....IF THE PROPOSED IS PORCELAIN OR CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, SPEC SHEETS WOULD
 NOT BE REQUIRED.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-05-27 Cont ID  
Sent By pleduc Date 2022-05-27 Time   Rev Time 0.00
Received By pleduc Date 2022-05-27 Time 15:50 Sent To  
Notes
2022-05-27 16:00:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF NEW FLOORING, BUT NO
 INDICATION OF WHAT TYPE OF FLOORING.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE TYPE OF
 FINISH FLOORING PRODUCT AND PRODUCT NAME AND SPEC SHEET
 THAT INDICATES THE FIRE BEHAVIOR RATING.
  
 FYI.....IF THE PROPOSED IS PORCELAIN OR CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, SPEC SHEETS WOULD
 NOT BE REQUIRED.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-01-25 Cont ID  
Sent By mpeterso Date 2023-01-25 Time 13:25 Rev Time 0.00
Received By mpeterso Date 2023-01-23 Time 06:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-01-11 Cont ID  
Sent By medwards Date 2023-01-11 Time 08:02 Rev Time 0.00
Received By lmarchan Date 2023-01-09 Time 16:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-11-18 Cont ID  
Sent By lmarchan Date 2022-11-18 Time 11:04 Rev Time 0.00
Received By lmarchan Date 2022-10-08 Time 18:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-02 Cont ID  
Sent By mpeterso Date 2022-08-02 Time 08:03 Rev Time 0.00
Received By mpeterso Date 2022-07-26 Time 12:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-29 Cont ID  
Sent By rmcphers Date 2022-06-29 Time 10:50 Rev Time 0.00
Received By rmcphers Date 2022-05-26 Time 06:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2023-01-24 Cont ID  
Sent By medwards Date 2023-01-24 Time 11:57 Rev Time 0.00
Received By medwards Date 2023-01-24 Time 11:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2023-01-10 Cont ID  
Sent By medwards Date 2023-01-10 Time 10:37 Rev Time 0.00
Received By medwards Date 2023-01-10 Time 10:37 Sent To  
Notes
2023-01-10 10:42:12THE REVISED DRAWING STILL SHOWS A/C WALL UNITS. THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS SPECIFY PTAC
 UNITS AND ROOM UNITS. THE DRAWING SHOOULD INDICATE
 THESE PTAC UNITS. THE SPECS FOR THE PTAC UNITS SHOULD
 ALSO BE SUBMITTED ON THE DRAWING. FBC 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-10-11 Cont ID  
Sent By medwards Date 2022-10-11 Time 08:45 Rev Time 0.00
Received By medwards Date 2022-10-11 Time 08:45 Sent To  
Notes
2022-10-11 08:46:093RD REVIEW FMC
 PERMIT: 22041501
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 01 NOW INDICATES EACH UNIT TO HAVE AN A/C WALL
 UNIT IN EACH AREA. PLEASE SHOW THAT THESE THROUGH THE
 WALL UNITS MEET THE HEATING REQUIREMENTS OF FMC 309.1
 309.1 SPACE-HEATING SYSTEMS.
 INTERIOR SPACES INTENDED FOR HUMAN OCCUPANCY SHALL BE
 PROVIDED WITH ACTIVE OR PASSIVE SPACE-HEATING SYSTEMS
 CAPABLE OF MAINTAINING AN INDOOR TEMPERATURE OF NOT
 LESS THAN 68??F (20??C) AT A POINT 3 FEET (914 MM)
 ABOVE FLOOR ON THE DESIGN HEATING DAY. THE INSTALLATION
 OF PORTABLE SPACE HEATERS SHALL NOT BE USED TO ACHIEVE
 COMPLIANCE WITH THIS SECTION.
  
 EXCEPTIONS:
 1. INTERIOR SPACES WHERE THE PRIMARY PURPOSE IS NOT
 ASSOCIATED WITH HUMAN COMFORT.
 2. GROUP F, H, S AND U OCCUPANCIES.
  
  
 2) THE ENERGY CALCULATIONS WILL NEED TO BE UPDATED TO
 REFLECT THE NEWLY REVISED MECHANICAL SYSTEMS. FEC
 101.5.1.1 AND C403.2.1
  
 3) SHEET M1 STILL SHOWS THE AHU???S AND DUCTWORK. THE
 MECHANICAL DRAWING SHOULD REFLECT THE SYSTEMS BEING
 INSTALLED. IF THIS M1 SHEET IS NOT WHAT IS TO BE
 INSTALLED THEN RESUBMIT SHEET M1 THAT REFLECTS THE
 DESIGN THAT WILL BE USED TO INSTALL ALL OF THE
 MECHANICAL WORK BEING COMPLETED UNDER THIS PERMIT.
 PLEASE INCLUDE THE BATH EXHAUST DUCT, DRYER DUCT AND
 KITCHEN HOODS FOR EACH UNIT. IF THESE ARE TO BE
 EXISTING TO REMAIN PLEASE ADD A NOTE STATING THIS. FBC
 107.3.5
  
 4) SHEET M1 ALSO REFLECTS THAT AHU???S 3 AND 4 ARE
 INSTALLED IN THE ATTIC OF THIS COMMERCIAL BUILDING.
 THIS IS PROHIBITED IN A COMMERCIAL BUILDING. PLEASE
 CORRECT THIS IF AHU???S ARE TO BE USED.
  
 C403.2.9.6 AIR-HANDLING UNITS. AIR-HANDLING UNITS SHALL
 NOT BE ALLOWED IN ATTICS OF COMMERCIAL BUILDINGS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-07-27 Cont ID  
Sent By medwards Date 2022-07-27 Time 08:20 Rev Time 0.00
Received By medwards Date 2022-07-27 Time 08:20 Sent To  
Notes
2022-07-27 08:21:502ND REVIEW FMC
 PERMIT: 22041501
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 01 INDICATES THAT THE MECHANICAL UNITS FOR
 THIS 2 STORY 4 UNIT COMMERCIAL APARTMENT BUILDING WILL
 BE MINI SPLIT SYSTEMS. SHEET M1 INDICATES THAT EACH
 APARTMENT HAS AN AHU AND A CONDENSING UNIT. THE DUCT
 WORK APPEARS TO STILL BE IN THE FIRE RATED FLOOR
 CEILING ASSEMBLY. THE BATH EXHAUST DUCT ALSO STILL
 APPEARS TO BE IN THE RATED FLOOR CEILING ASSEMBLY.
 PLEASE ADDRESS 1ST CYCLE COMMENTS AND MAKE SURE THE
 DRAWINGS ARE CONSISTENT.
  
 2) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS ARE FOR
 RESIDENTIAL, THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS SHOULD BE SIZED IN ACCORDANCE TO FEC
 C403.2.1. THE CALCULATIONS SHOULD ALSO INCLUDE THE
 APARTMENT THAT EACH UNIT IS SIZED TO CONDITION.
  
 3) THE COMMON HALL OF THIS COMMERCIAL BUILDING SHOULD
 HAVE VENTILATION. PLEASE SHOW THE CALCULATIONS FOR THE
 VENTILATION. FMC TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-05-27 Cont ID  
Sent By medwards Date 2022-05-27 Time 08:45 Rev Time 0.00
Received By medwards Date 2022-05-27 Time 08:45 Sent To  
Notes
2022-05-27 08:45:421ST REVIEW FMC
 PERMIT: 22041501
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REVISE THE MECHANICAL PLAN TO PROVIDE DETAIL
 DRAWINGS OF ALL MECHANICAL SYSTEMS INSIDE THE
 FLOOR/CEILING ASSEMBLY AND HOW THE FIRE SEPARATION WILL
 BE PROTECTED. FMC 607.6.2
  
 2) REVISE MECHANICAL DRAWING TO SHOW HOW THE COMMON
 HALL WILL BE VENTILATED. FMC TABLE 403.3.1.1
  
 3) REVISE THE MECHANICAL DRAWING TO SHOW HOW THE
 BATHROOM EXHAUST DUCT THAT IS SHARED BETWEEN TENANTS
 WILL NOT RECIRCULATE BACK INTO TENANT SPACES. FMC
 403.3.1.1 FOOTNOTE G
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-07-27 Cont ID  
Sent By rwbrown Date 2022-07-27 Time 08:07 Rev Time 0.00
Received By rwbrown Date 2022-07-27 Time 08:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-05-28 Cont ID  
Sent By rwbrown Date 2022-05-28 Time 07:54 Rev Time 0.00
Received By rwbrown Date 2022-05-28 Time 07:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2023-01-24 Cont ID  
Sent By medwards Date 2023-01-24 Time 12:50 Rev Time 0.00
Received By medwards Date 2023-01-24 Time 12:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-01-10 Cont ID  
Sent By medwards Date 2023-01-10 Time 10:46 Rev Time 0.00
Received By medwards Date 2023-01-10 Time 10:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-10-17 Cont ID  
Sent By rmcphers Date 2022-10-17 Time 16:00 Rev Time 0.00
Received By rmcphers Date 2022-10-17 Time 16:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-07-27 Cont ID  
Sent By rwbrown Date 2022-07-27 Time 08:09 Rev Time 0.00
Received By rwbrown Date 2022-07-27 Time 08:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-29 Cont ID  
Sent By rmcphers Date 2022-06-29 Time 10:50 Rev Time 0.00
Received By rmcphers Date 2022-06-29 Time 10:50 Sent To  
Notes
2022-05-27 08:46:33DIGITAL SIGNATURE FOR MECHANICAL DRAWING APPROVED ME

Review Stop Z ZONING
Rev No 2 Status P Date 2022-11-17 Cont ID  
Sent By amhamilt Date 2022-11-17 Time 14:51 Rev Time 0.00
Received By amhamilt Date 2022-11-17 Time 14:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-06-07 Cont ID  
Sent By amhamilt Date 2022-06-07 Time 10:26 Rev Time 0.00
Received By amhamilt Date 2022-06-07 Time 10:26 Sent To  
Notes
***NONE***