Plan Review Details - Permit 22041387
Plan Review Stops For Permit 22041387
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-14 Cont ID  
Sent By lmarchan Date 2022-12-14 Time 15:56 Rev Time 0.00
Received By lmarchan Date 2022-12-09 Time 08:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-23 Cont ID  
Sent By lmarchan Date 2022-05-23 Time 08:02 Rev Time 0.00
Received By lmarchan Date 2022-05-18 Time 04:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-09 Cont ID  
Sent By aoliver Date 2022-05-09 Time 13:00 Rev Time 0.00
Received By aoliver Date 2022-05-02 Time 06:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-12-12 Cont ID  
Sent By rwbrown Date 2022-12-12 Time 10:06 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-05-18 Cont ID  
Sent By rwbrown Date 2022-05-18 Time 13:04 Rev Time 0.00
Received By rwbrown Date 2022-05-18 Time 13:04 Sent To  
Notes
2022-05-18 13:04:452ND PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. NOT ADDRESSED - IS THIS FOR FIRE OR POTABLE WATER? I
 NEED THE SPECIFICATIONS SHEET, NOT THE INSTALLATION
 INSTRUCTIONS.
 2017 WPB AMEND - 107.2.1 - PLEASE PROVIDE A BACKFLOW
 SPECIFICATION SHEET. I HAVE PLACED A COPY OF THE
 BACKFLOW REQUIREMENTS IN THE SUPPORTING DOCUMENTS ON
 PROJECTDOX. YOU CAN REVIEW IT THERE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-05-09 Cont ID  
Sent By rwbrown Date 2022-05-03 Time 06:55 Rev Time 0.00
Received By rwbrown Date 2022-05-03 Time 06:55 Sent To  
Notes
2022-05-09 14:26:421ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND - 107.2.1 - PLEASE PROVIDE A BACKFLOW
 SPECIFICATION SHEET. I HAVE PLACED A COPY OF THE
 BACKFLOW REQUIREMENTS IN THE SUPPORTING DOCUMENTS ON
 PROJECTDOX. YOU CAN REVIEW IT THERE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop PU PUBLIC UTILITIES
Rev No 3 Status P Date 2022-12-14 Cont ID  
Sent By lmarchan Date 2022-12-14 Time 15:56 Rev Time 0.00
Received By lmarchan Date 2022-12-14 Time 15:56 Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 2 Status F Date 2022-05-20 Cont ID  
Sent By aoliver Date 2022-05-20 Time 14:50 Rev Time 0.00
Received By aoliver Date 2022-05-20 Time 14:50 Sent To  
Notes
2022-05-20 16:29:372017 WPB AMEND - 107.2.1 - PLEASE PROVIDE THE BACKFLOW
 SPECIFICATION SHEET. MUST BE LEAD FREE.

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date 2022-05-09 Cont ID  
Sent By aoliver Date 2022-05-09 Time 13:00 Rev Time 0.00
Received By aoliver Date 2022-05-09 Time 13:00 Sent To  
Notes
2022-05-09 14:23:592017 WPB AMEND - 107.2.1 - PLEASE PROVIDE THE BACKFLOW
 SPECIFICATION SHEET.