Plan Review Details - Permit 22041236
Plan Review Stops For Permit 22041236
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-07-08 Cont ID  
Sent By rmcphers Date 2022-07-08 Time 09:47 Rev Time 0.00
Received By rmcphers Date 2022-07-08 Time 09:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-11 Cont ID  
Sent By rmcphers Date 2022-05-11 Time 14:25 Rev Time 0.00
Received By rmcphers Date 2022-05-11 Time 12:34 Sent To  
Notes
2022-05-11 14:24:59TRASH COMPACTOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DEMO OF THE STRUCTURAL (WALL, SLABS ETC) ITEMS NEED
 TO BE A SEPARATE PERMIT.
  
 2) PLEASE SHOW THE STAIR RISER HEIGHT AND TREAD DEPTH
 PER FBC 1011.5.2
  
 3) PLEASE SHOW THE RAMP SLOPE PER FBC A 405.2
  
 4) PLEASE SHOW THE RAMP LANDING SIZE AT THE CHANGE IN
 DIRECTION PER FBC A 405.7.4
  
 5) PLEASE SHOW THE STAIR HANDRAIL DETAILS - FBC 1014
  
 6) PLEASE SHOW THE HANDRAILS ARE REQUIRED ON BOTH SIDES
 OF THE STAIR FBC 1011.11

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-05-27 Cont ID  
Sent By jleahy Date 2022-05-27 Time 07:55 Rev Time 0.00
Received By jleahy Date 2022-05-27 Time 07:33 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2022-07-05 Cont ID  
Sent By rrossano Date 2022-07-05 Time   Rev Time 0.00
Received By rrossano Date 2022-07-05 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-06-28 Cont ID  
Sent By pleduc Date 2022-06-28 Time   Rev Time 0.00
Received By pleduc Date 2022-06-28 Time 10:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-04-29 Cont ID  
Sent By pleduc Date 2022-04-29 Time   Rev Time 0.00
Received By pleduc Date 2022-04-27 Time 15:47 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2022-06-28 Cont ID  
Sent By ccole Date 2022-06-28 Time 08:55 Rev Time 0.00
Received By ccole Date 2022-06-28 Time 08:12 Sent To  
Notes
2022-06-28 08:56:20GAS PIPING AND METER RELOCATION TO BE UNDER A SEPARATE
 PERMIT.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-05-25 Cont ID  
Sent By ccole Date 2022-05-25 Time 11:23 Rev Time 0.00
Received By ccole Date 2022-05-25 Time 11:23 Sent To  
Notes
2022-05-25 11:29:441ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22041236
 5/25/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 3: THE PLAN SHOWS THE GAS METER IS BEING
 RELOCATED. PLEASE PROVIDE A GAS PIPING PLAN AND
 ISOMETRIC DRAWING- SEC. 107.2.1 & 107.3.5.1.3 WPB.
 PLEASE NOTE A GAS-SUBMIT APPLICATION IS REQUIRED IF THE
 GAS WORK WILL BE COMPLETED UNDER THIS PERMIT. THE GAS
 WORK CAN BE DONE UNDER A SEPARATE PERMIT IF PREFERRED-
 SEC. 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-21 Cont ID  
Sent By aoliver Date 2022-07-21 Time 08:51 Rev Time 0.00
Received By aoliver Date 2022-06-27 Time 13:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-02 Cont ID  
Sent By jleahy Date 2022-06-02 Time 09:47 Rev Time 0.00
Received By aoliver Date 2022-04-27 Time 06:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-06-28 Cont ID  
Sent By ccole Date 2022-06-28 Time 09:21 Rev Time 0.00
Received By ccole Date 2022-06-28 Time 08:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-05-25 Cont ID  
Sent By ccole Date 2022-05-25 Time 11:21 Rev Time 0.00
Received By ccole Date 2022-05-25 Time 11:21 Sent To  
Notes
2022-05-25 11:22:591ST REVIEW FBC-2020 PLUMBING
 PERMIT-22041236
 5/25/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET E-1: PLEASE PROVIDE A SEPARATE PLUMBING PLAN
 AND ISOMETRIC DRAWING SHOWING THE NEW COMPACTOR DRAIN
 LOCATION AND CONNECTION TO THE EXISTING SANITARY
 SYSTEM- SECS. 107.2.1 & 107.3.5.1.3 WPB. A) PLEASE NOTE
 AN OIL INTERCEPTOR IS REQUIRED- SEC. 1003.4 FBC P.
 PROVIDE ENLARGED PIPING DETAILS AND SUBMIT
 MANUFACTURER?S SPECIFICATIONS- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-06-28 Cont ID  
Sent By ccole Date 2022-06-28 Time 09:24 Rev Time 0.00
Received By ccole Date 2022-06-28 Time 08:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-05-11 Cont ID  
Sent By rmcphers Date 2022-05-11 Time 14:34 Rev Time 0.00
Received By rmcphers Date 2022-05-11 Time 14:34 Sent To  
Notes
2022-05-11 14:39:50SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS SIGNED AND SEALED BY ADAM SWANEY P.E. IN
 THE "SIGNATURES" FOLDER AND THE "DRAWINGS" FOLDER DO
 NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN VERIFIABLE ELECTRONIC OR DIGITAL SIGNATURE
 - YOU CAN DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-07-20 Cont ID  
Sent By ckimmerl Date 2022-07-20 Time 13:45 Rev Time 0.00
Received By ckimmerl Date 2022-07-20 Time 13:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-06-01 Cont ID  
Sent By ckimmere Date 2022-06-01 Time 15:47 Rev Time 0.00
Received By ckimmerl Date 2022-06-01 Time 15:41 Sent To  
Notes
2022-06-01 15:47:031. PLEASE PROVIDE A SURVEY
  
 2. RESTRIPE/PAVING/MILLING REQUIRES A SEPARATE PERMIT.
 - RE-STRIPING OF THE PARKING LOT NEEDS TO MEET CITY
 PARKING STALL DIMENSIONS AND STRIPING DETAILS OF SEC.
 94-485. - GENERAL PROVISIONS.
  
 3. WHAT IS THE PROPOSED CMU WALL HEIGHT TO SCREEN
 COMPACTOR?
  
 4, PLANS NEED TO MATCH THOSE OF THE MINOR SITE PLAN
 AMENDMENT APPROVAL FOR PB 1117D.
  
 CHRIS KIMMERLY
 CKIMMERLY@ WPB.ORG 822-1426
  