Plan Review Details - Permit 22040982
Plan Review Stops For Permit 22040982
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-07-28 Cont ID  
Sent By rmcphers Date 2022-07-28 Time 11:44 Rev Time 0.00
Received By rmcphers Date 2022-07-28 Time 11:44 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-07-01 Cont ID  
Sent By rmcphers Date 2022-07-01 Time 14:33 Rev Time 0.00
Received By rmcphers Date 2022-07-01 Time 14:04 Sent To  
Notes
2022-07-01 14:34:11PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT
 "THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND NOTIFICATION WILL BE GIVEN
 TIMELY"
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-07-28 Cont ID  
Sent By rmcphers Date 2022-07-28 Time 11:39 Rev Time 0.00
Received By rmcphers Date 2022-07-28 Time 11:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-01 Cont ID  
Sent By rmcphers Date 2022-07-01 Time 14:34 Rev Time 0.00
Received By rmcphers Date 2022-07-01 Time 14:04 Sent To  
Notes
2022-07-01 14:43:29OFFICE BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A0.02 SHOWS NEW CORRIDOR WALL AS 1 HOUR FIRE
 RATED - DRAWING A1.11 SHOWS NEW CORRIDOR WALL AS
 DESIGNATION "S2" - DRAWING A5.11 SHOWS WALL DESIGNATION
 "S2" AS NON-FIRE RATED. PLEASE CLARIFY.
  
 2) DOOR 001 SHOULD BE FIRE RATED FOR A 1 HR FIRE RATED
 WALL PER FBC 716.5 - - DOOR GLAZING NEEDS TO COMPLY
 WITH FBC 716.2

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-07-29 Cont ID  
Sent By jleahy Date 2022-07-29 Time 07:13 Rev Time 0.00
Received By jleahy Date 2022-07-29 Time 07:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-06-10 Cont ID  
Sent By jleahy Date 2022-06-10 Time 09:47 Rev Time 0.00
Received By jleahy Date 2022-06-10 Time 09:09 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2022-07-29 Cont ID  
Sent By jleahy Date 2022-07-29 Time 07:13 Rev Time 0.00
Received By jleahy Date 2022-07-29 Time 07:13 Sent To  
Notes
2022-07-29 07:14:25VOICE AND DATA AS PER PLANS JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-07-21 Cont ID  
Sent By pleduc Date 2022-07-21 Time   Rev Time 0.00
Received By pleduc Date 2022-07-21 Time 13:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-05-26 Cont ID  
Sent By pleduc Date 2022-05-26 Time   Rev Time 0.00
Received By pleduc Date 2022-05-25 Time 12:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-29 Cont ID  
Sent By jleahy Date 2022-07-29 Time 07:14 Rev Time 0.00
Received By jleahy Date 2022-07-19 Time 16:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-01 Cont ID  
Sent By rmcphers Date 2022-07-01 Time 14:44 Rev Time 0.00
Received By rmcphers Date 2022-05-24 Time 06:04 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-07-01 Cont ID  
Sent By rmcphers Date 2022-07-01 Time 14:43 Rev Time 0.00
Received By rmcphers Date 2022-07-01 Time 14:43 Sent To  
Notes
2022-07-01 14:44:11NO ADDED SQUARE FOOTAGE - NO CHANGE OF OCCUPANCY TYPE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-07-20 Cont ID  
Sent By medwards Date 2022-07-20 Time 10:07 Rev Time 0.00
Received By medwards Date 2022-07-20 Time 10:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-05-27 Cont ID  
Sent By medwards Date 2022-05-27 Time 16:23 Rev Time 0.00
Received By medwards Date 2022-05-27 Time 16:23 Sent To  
Notes
2022-05-27 16:38:41PROVIDE THE OUTDOOR AIT CALCULATIONS FOR THIS TENANT
 SPACE. FMC 403.3.1.1
  
 REVISE THE MECHANICAL PLAN TO SHOW THE CONDENSATE
 PIPING MATERIAL SIZE AND TERMINATION LOCATION. FMC 307
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-07-21 Cont ID  
Sent By ccole Date 2022-07-21 Time 11:50 Rev Time 0.00
Received By ccole Date 2022-07-21 Time 11:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-06-01 Cont ID  
Sent By ccole Date 2022-06-01 Time 14:06 Rev Time 0.00
Received By ccole Date 2022-06-01 Time 12:44 Sent To  
Notes
2022-06-01 14:07:431ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22040982
 6/1/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A4.22 DETAIL 1: SHOW THE CLEAR FLOOR SPACE
 DIMENSIONS FOR THE WATER CLOSET AND LAVATORY- SECS.
 604.3 & 606.2 FBC ACC. PLEASE NOTE THAT THE DOOR SHALL
 NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR THE
 LAVATORY- SEC. 603.2.3 FBC ACC.
  
 2) P0.1: THE BOARDROOM SINK FIXTURE DRAIN SHALL NOT
 CONNECT INTO THE BATHROOM WET VENT, AND SHALL DISCHARGE
 DOWNSTREAM OF THE VENT- SEC. 912.1 FBC P.
  
 3) P2.1: INSTALLATION OF NEW DRAIN OUTLETS MAY REQUIRE
 THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE
 REINFORCING STEEL OR POST STRESSED FLOOR TENDONS.
 PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE
 WILL BE MET- SECTION 107.2.1 WPB.
  
 4) P2.1: NEW DRAIN PIPE PENETRATIONS OF THE EXISTING
 SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR
 SPACE AROUND THE PIPING. PROVIDE A UL TESTED AND
 APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN-
 SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-07-28 Cont ID  
Sent By rmcphers Date 2022-07-28 Time 11:46 Rev Time 0.00
Received By rmcphers Date 2022-07-28 Time 11:46 Sent To  
Notes
2022-07-20 10:08:24MECHANICAL DIGITAL SIGNATURES APPROVED ME
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-01 Cont ID  
Sent By rmcphers Date 2022-07-01 Time 14:44 Rev Time 0.00
Received By rmcphers Date 2022-07-01 Time 14:44 Sent To  
Notes
2022-06-10 09:47:11ELECTRICAL SIGNATURE APPROVED JLEAHY
2022-05-27 16:39:56DIGITAL SIGNATURES FOR MECHANICAL APPROVED ME