Plan Review Details - Permit 22040976
Plan Review Stops For Permit 22040976
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-26 Cont ID  
Sent By aoliver Date 2022-05-26 Time 11:54 Rev Time 0.00
Received By aoliver Date 2022-05-24 Time 10:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-11 Cont ID  
Sent By lmarchan Date 2022-05-11 Time 12:46 Rev Time 0.00
Received By lmarchan Date 2022-05-10 Time 06:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-05-25 Cont ID  
Sent By ccole Date 2022-05-25 Time 07:10 Rev Time 0.00
Received By ccole Date 2022-05-25 Time 07:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-05-11 Cont ID  
Sent By ccole Date 2022-05-11 Time 07:28 Rev Time 0.00
Received By ccole Date 2022-05-11 Time 07:25 Sent To  
Notes
2022-05-11 08:22:161ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22040976
 5/11/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED SPEC SHEET FOR THE WILKINS 975 X RPZ
 DOES NOT SHOW THAT THE DEVICE IS LEAD FREE (0.25% MAX
 WEIGHTED AVERAGE LEAD CONTENT.)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PU PUBLIC UTILITIES
Rev No 2 Status P Date 2022-05-26 Cont ID  
Sent By aoliver Date 2022-05-26 Time 11:54 Rev Time 0.00
Received By aoliver Date 2022-05-26 Time 11:53 Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date 2022-05-11 Cont ID  
Sent By lmarchan Date 2022-05-11 Time 12:47 Rev Time 0.00
Received By lmarchan Date 2022-05-11 Time 12:47 Sent To  
Notes
2022-05-11 12:47:22PER RJENKINS - SPECIFICATIONS MUST BE (0.25% MAX.
 WEIGHTED AVERAGE LEAD CONTENT) NORMALLY WILKINS 975XL2


Account Summary | Usage Policy | Privacy Policy