Plan Review Details - Permit 22040970
Plan Review Stops For Permit 22040970
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-04-29 Cont ID  
Sent By cpuell Date 2022-04-29 Time 09:30 Rev Time 0.00
Received By cpuell Date 2022-04-29 Time 09:30 Sent To  
Notes
2022-04-29 09:30:23UPDATED PARCEL WITH SUITE NUMBERS

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-04-27 Cont ID  
Sent By cpuell Date 2022-04-27 Time 15:07 Rev Time 0.00
Received By cpuell Date 2022-04-27 Time 15:07 Sent To  
Notes
2022-04-27 15:07:51SUITE 300 IS NOT A RECOGNIZED SUITE NUMBER, PLEASE
 PROVIDE A FLOOR PLAN SHOWING EVERY SUITE ON THAT FLOOR.
 PLEASE EMAIL TO [email protected] FOR FURTHER QUESTIONS
 YOU CAN ALSO CALL 561-805-6659

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2022-04-20 Cont ID  
Sent By shill Date 2022-04-20 Time 17:15 Rev Time 0.00
Received By shill Date 2022-04-20 Time 17:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-06-24 Cont ID  
Sent By rmcphers Date 2022-06-24 Time 13:20 Rev Time 0.00
Received By rmcphers Date 2022-06-24 Time 13:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-11 Cont ID  
Sent By rmcphers Date 2022-05-11 Time 15:41 Rev Time 0.00
Received By rmcphers Date 2022-05-11 Time 14:50 Sent To  
Notes
2022-05-11 15:41:19OFFICE RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE HOURLY FIRE RATING FOR THE NEW
 CORRIDOR WALL AND DOOR (ERI) - FBC 701 AND 716

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-05-25 Cont ID  
Sent By mpeterso Date 2022-05-25 Time 16:37 Rev Time 0.00
Received By mpeterso Date 2022-05-25 Time 16:37 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2022-07-18 Cont ID  
Sent By fgiaquin Date 2022-07-18 Time 19:30 Rev Time 0.00
Received By fgiaquin Date 2022-07-18 Time 19:29 Sent To  
Notes
2022-07-18 19:30:41CAT6 DATA ONLY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-06-16 Cont ID  
Sent By cwalker Date 2022-06-16 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-06-16 10:09:53FIRE PROVISO COMMENTS:
 1.) ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE
 ALARM) SHALL BE PROTECTED FROM DAMAGE DURING DEMOTION
 AND CONSTRUCTION.
 2.) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) IN EXCESS OF 4 CONTINUOUS
 HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-04-28 Cont ID  
Sent By cwalker Date 2022-04-28 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-04-28 14:48:12FIRE PROVISO COMMENTS:
 1.) ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE
 ALARM) SHALL BE PROTECTED FROM DAMAGE DURING DEMO AND
 CONSTRUCTION.
 2.) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) IN EXCESS OF 4 CONTINUOUS
 HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-24 Cont ID  
Sent By rmcphers Date 2022-06-24 Time 13:20 Rev Time 0.00
Received By rmcphers Date 2022-06-15 Time 10:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-25 Cont ID  
Sent By mpeterso Date 2022-05-25 Time 16:37 Rev Time 0.00
Received By mpeterso Date 2022-04-27 Time 08:10 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-05-11 Cont ID  
Sent By rmcphers Date 2022-05-11 Time 15:41 Rev Time 0.00
Received By rmcphers Date 2022-05-11 Time 15:41 Sent To  
Notes
2022-05-11 15:42:19NO CHANGE OF OCCUPANCY - NO ADDED SQUARE FOOTAGE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-06-22 Cont ID  
Sent By medwards Date 2022-06-22 Time 15:34 Rev Time 0.00
Received By medwards Date 2022-06-22 Time 15:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-05-11 Cont ID  
Sent By medwards Date 2022-05-11 Time 14:25 Rev Time 0.00
Received By medwards Date 2022-05-11 Time 14:25 Sent To  
Notes
2022-05-11 14:25:341ST REVIEW FMC
 PERMIT: 22040970
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DEMO SHEET SHOWS THIS WAS MORE LIKE AN OPEN
 OFFICE. SHOW THE UNITS AND DUCTWORK THAT CONDITIONS THE
 AIR FOR THESE NEW ROOMS AND TENANT SPACE. FBC 107.2.1
  
 2) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON EACH
 USE OF SPACE AND THE OCCUPANCY CLASSIFICATION IN FMC
 TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-06-22 Cont ID  
Sent By ccole Date 2022-06-22 Time 16:03 Rev Time 0.00
Received By ccole Date 2022-06-22 Time 15:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-05-05 Cont ID  
Sent By ccole Date 2022-05-05 Time 09:18 Rev Time 0.00
Received By ccole Date 2022-05-05 Time 07:50 Sent To  
Notes
2022-05-05 09:24:431ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22040970
 5/5/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P0.1: LOCATION OF THE REQUIRED DEDICATED SHUT OFF
 VALVE FOR THE IWH UNDER THE SINK NOT SHOWN- SEC 503.1
 FBC P.
  
 2) P0.1, A1.1: PUBLIC LAVATORY LABELING AT THE SINK
 DETAIL INCORRECT. ACCORDING TO THE PLANS THE SINKS ARE
 IN THE COFFEE AND WELLNESS ROOMS - SEC. 107.2.1 WPB.
  
 3) P0.1: HOT WATER, NOT TEMPERED WATER IS REQUIRED AT
 THE SINKS. REMOVE THE TEMPERED WATER MIXING VALVE AND
 ALL REFERENCES TO TEMPERED WATER- SECS 419.5 AND
 607.1.2 FBC P. PROVIDE A MIXING VALVE THAT WILL LIMIT
 THE HOT WATER TEMPERATURE IN ACCORDANCE WITH SEC.
 607.1.1.
  
 4) P0.1: PROVIDE EQUIPMENT SCHEDULES FOR THE WATER
 HEATERS ON THE PLANS AND SUBMIT MANUFACTURER?S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS- SEC.
 502.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-06-22 Cont ID  
Sent By ccole Date 2022-06-22 Time 16:08 Rev Time 0.00
Received By ccole Date 2022-06-22 Time 16:05 Sent To  
Notes
2022-06-22 15:34:57DIGITAL SIGNATURE FOR MECHANICAL APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-05-11 Cont ID  
Sent By rmcphers Date 2022-05-11 Time 15:49 Rev Time 0.00
Received By rmcphers Date 2022-05-11 Time 15:49 Sent To  
Notes
2022-05-11 14:26:24DIGITAL SIGNATURES APPROVED FOR THE MECHANICAL
 DOCUMENTS. ME

Review Stop Z ZONING
Rev No 1 Status P Date 2022-05-10 Cont ID  
Sent By afowkles Date 2022-05-10 Time 12:24 Rev Time 0.00
Received By afowlkes Date 2022-05-10 Time 12:24 Sent To  
Notes
***NONE***