Plan Review Stops For Permit 22040906 |
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
3 |
Status |
P |
Date |
2022-10-24 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-10-24 |
Time |
15:25 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-10-24 |
Time |
15:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
2 |
Status |
F |
Date |
2022-09-16 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-09-16 |
Time |
09:37 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-09-16 |
Time |
09:37 |
Sent To |
|
|
Notes |
2022-09-16 09:37:34 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | CAN BE FOUND ON THEIR WEBSITE: | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2022-05-09 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-05-09 |
Time |
16:26 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-05-09 |
Time |
16:26 |
Sent To |
|
|
Notes |
2022-05-09 16:27:17 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | CAN BE FOUND ON THEIR WEBSITE: | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2022-10-26 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-10-26 |
Time |
08:04 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-10-26 |
Time |
08:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2022-10-24 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-10-24 |
Time |
15:22 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-10-24 |
Time |
15:22 |
Sent To |
|
|
Notes |
2022-10-24 15:23:14 | CONDO REMODEL | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED: | | | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. | | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING | | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY | | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP | | CEILING DESCRIPTION) | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP | | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING | | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED | | DROP CEILING DESCRIPTION) | | | | YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO VERIFY | | THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING TO | | PROJECTDOX ( [email protected] ) | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2022-09-16 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-09-16 |
Time |
09:35 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-09-16 |
Time |
09:35 |
Sent To |
|
|
Notes |
2022-09-16 09:36:12 | CONDO REMODEL | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED: | | | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. | | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING | | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY | | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP | | CEILING DESCRIPTION) | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP | | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING | | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED | | DROP CEILING DESCRIPTION) | | | | YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO VERIFY | | THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING TO | | PROJECTDOX ( [email protected] ) | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-05-09 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-05-09 |
Time |
16:27 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-05-09 |
Time |
16:27 |
Sent To |
|
|
Notes |
2022-05-09 16:28:18 | CONDO REMODEL | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - | | | | 1) FOR THE FLOORING - THE FOLLOWING ACUSTICAL TEST | | REPORTS ARE REQUIRED: | | | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. | | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING | | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY | | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP | | CEILING DESCRIPTION) | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP | | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING | | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED | | DROP CEILING DESCRIPTION) | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS | | ATTACHED TO THE FLOORING) | | | | 2). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO | | VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING | | TO PROJECTDOX ( [email protected] ) | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2022-09-08 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2022-09-08 |
Time |
|
Rev Time |
0.00 |
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2022-04-26 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2022-04-26 |
Time |
|
Rev Time |
|
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2022-04-26 11:32:54 | FIRE COMMENTS: | | PROVIDE SPECIFICATIONS ON THE FLOORING TO BE INSTALLED | | TO INCLUDE THE FIRE PERFORMANCE OF THE MATERIALS TO | | INCLUDE THE CRITICAL RADIANT FLUX. NFPA 101 10.2.7 | | PROVIDE DETAILS ON THE FLOOR PLAN, THAT ANY FIRE RATED | | WALL WILL HAVE THE RATING MAINTAINED IF APPLICABLE. | | C. WALKER | | 561-804-4762 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2022-10-24 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-10-24 |
Time |
15:25 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-10-11 |
Time |
14:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-09-16 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-09-16 |
Time |
10:48 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-09-07 |
Time |
15:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-05-09 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-05-09 |
Time |
16:28 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-04-20 |
Time |
15:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2022-09-15 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2022-09-15 |
Time |
07:06 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2022-04-29 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2022-04-29 |
Time |
13:22 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2022-04-29 |
Time |
13:22 |
Sent To |
|
|
Notes |
2022-04-29 13:21:54 | | | | | 1ST PLUMBING REVIEW | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. 2017 WPB AMENDS 107.2.1 - PLEASE CLARIFY THE SCOPE | | OF WORK. IF CHANGING FIXTURE LOCATIONS, PROVIDE A | | DRAWING OF THE EXISTING AND PROPOSED LOCATIONS AND | | OTHER SUPPORTING INFORMATION SUCH AS RISERS AND | | ISOMETRICS. IF THE FIXTURES ARE REMAINING IN THE SAME | | LOCATION AND ARE BEING CHANGED OUT "LIKE FOR LIKE", | | PLEASE NOTE IT SOMEWHERE ON THE PLANS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
N |
Date |
2022-05-09 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-05-09 |
Time |
16:28 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-05-09 |
Time |
16:28 |
Sent To |
|
|
Notes |
|
|