Plan Review Details - Permit 22040747
Plan Review Stops For Permit 22040747
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-06-06 Cont ID  
Sent By rmcphers Date 2022-06-06 Time 14:53 Rev Time 0.00
Received By rmcphers Date 2022-06-06 Time 14:53 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-05-10 Cont ID  
Sent By rmcphers Date 2022-05-10 Time 15:32 Rev Time 0.00
Received By rmcphers Date 2022-05-10 Time 14:40 Sent To  
Notes
2022-05-10 15:32:51PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-09-16 Cont ID  
Sent By rmcphers Date 2022-09-16 Time 09:40 Rev Time 0.00
Received By rmcphers Date 2022-09-16 Time 09:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-07-05 Cont ID  
Sent By rmcphers Date 2022-07-05 Time 12:46 Rev Time 0.00
Received By rmcphers Date 2022-07-05 Time 12:46 Sent To  
Notes
2022-07-05 12:48:03BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 2ND REVIEW
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS AND DOORS
 THAT ARE LISTED ON THE DRAWINGS. MAKING SURE THAT THEY
 ARE THE CURRENT REVISION 14218- R7 HAS BEEN REVISED
 (14218 - R12)
  
 2) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET PAPER
 HOLDER LOCATION DIMENSIONS FROM THE FACE OF THE TOILET
 AND FROM THE FLOOR FBC A 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-06-06 Cont ID  
Sent By rmcphers Date 2022-06-06 Time 14:54 Rev Time 0.00
Received By rmcphers Date 2022-06-06 Time 14:54 Sent To  
Notes
2022-06-06 14:56:09BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 2ND REVIEW
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS AND DOORS
 THAT ARE LISTED ON THE DRAWINGS.
  
 2) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET PAPER
 HOLDER LOCATION DIMENSIONS FROM THE FACE OF THE TOILET
 AND FROM THE FLOOR FBC A 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-10 Cont ID  
Sent By rmcphers Date 2022-05-10 Time 15:51 Rev Time 0.00
Received By rmcphers Date 2022-05-10 Time 14:40 Sent To  
Notes
2022-05-10 15:44:06BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS AND DOORS -
 ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE DESIGNER OF RECORD IF NOT LISTED ON THE
 DRAWINGS BY PRODUCT APPROVAL NUMBER. FBC WPB 107.3.4
  
 2) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET GRAB
 BAR HEIGHT PER FBC A 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  
 3) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET PAPER
 HOLDER LOCATION DIMENSIONS FROM THE FACE OF THE TOILET
 AND FROM THE FLOOR FBC A 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-09-29 Cont ID  
Sent By jleahy Date 2022-09-29 Time 17:16 Rev Time 0.00
Received By jleahy Date 2022-09-29 Time 16:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-05-09 Cont ID  
Sent By jleahy Date 2022-05-09 Time 15:29 Rev Time 0.00
Received By mpeterso Date 2022-05-09 Time 15:52 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2022-09-29 Cont ID  
Sent By jleahy Date 2022-09-29 Time 17:16 Rev Time 0.00
Received By jleahy Date 2022-09-29 Time 17:16 Sent To  
Notes
2022-09-29 17:17:18VOICE DATA AS PER PLANS JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2022-09-07 Cont ID  
Sent By pleduc Date 2022-09-07 Time   Rev Time 0.00
Received By pleduc Date 2022-09-07 Time 16:11 Sent To  
Notes
2022-09-07 16:11:30FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-06-27 Cont ID  
Sent By pleduc Date 2022-06-27 Time   Rev Time 0.00
Received By pleduc Date 2022-06-27 Time 11:06 Sent To  
Notes
2022-06-27 11:07:14FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-31 Cont ID  
Sent By pleduc Date 2022-05-31 Time   Rev Time 0.00
Received By pleduc Date 2022-05-31 Time 11:30 Sent To  
Notes
2022-05-31 11:32:28FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-04-18 Cont ID  
Sent By pleduc Date 2022-04-18 Time   Rev Time 0.00
Received By pleduc Date 2022-04-18 Time 13:43 Sent To  
Notes
2022-04-18 14:01:55FIRE PROVISO:
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-09-29 Cont ID  
Sent By jleahy Date 2022-09-29 Time 17:17 Rev Time 0.00
Received By jleahy Date 2022-09-07 Time 12:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-11 Cont ID  
Sent By aoliver Date 2022-07-11 Time 07:06 Rev Time 0.00
Received By aoliver Date 2022-06-25 Time 07:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-10 Cont ID  
Sent By aoliver Date 2022-06-10 Time 07:09 Rev Time 0.00
Received By aoliver Date 2022-05-27 Time 11:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-10 Cont ID  
Sent By rmcphers Date 2022-05-10 Time 16:02 Rev Time 0.00
Received By rmcphers Date 2022-04-15 Time 06:01 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-05-10 Cont ID  
Sent By rmcphers Date 2022-05-10 Time 15:57 Rev Time 0.00
Received By rmcphers Date 2022-05-10 Time 15:57 Sent To  
Notes
2022-05-10 15:58:18NO CHANGE OF OCCUPANCY CLASSIFICATION - NO ADDED SQUARE
 FOOTAGE

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-09-14 Cont ID  
Sent By medwards Date 2022-09-14 Time 07:41 Rev Time 0.00
Received By medwards Date 2022-09-08 Time 15:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-05-31 Cont ID  
Sent By medwards Date 2022-05-31 Time 10:54 Rev Time 0.00
Received By medwards Date 2022-05-31 Time 10:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-05-03 Cont ID  
Sent By medwards Date 2022-05-03 Time 14:28 Rev Time 0.00
Received By medwards Date 2022-05-03 Time 14:28 Sent To  
Notes
2022-05-03 14:28:341ST REVIEW FMC
 PERMIT: 22040747
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THE HEAT AND COOLING LOADS. FEC
 C403.2.1
  
 2) HOW ARE THESE AC UNITS PRODUCING THE REQUIRED HEAT
 FOR THIS TENANT SPACE? FMC 309.1
  
 3) PLEASE PROVIDE A ROOF DRAWING DETAILING THE
 LOCATIONS OF THE CONDENSING UNITS. FBC 107.2.1
  
 3) SHEET M100: KEYNOTE 3 INDICATES THE CONDENSATE TO BE
 ROUTED TO THE NEW MOP SINK. THE CONDENSATE CANNOT BE
 DRAINED INTO THE SANITARY SEWER. WEST PALM BEACH
 MUNICIPAL CODE SEC. 90-126: A) GENERALLY. USERS SHALL
 NOT DISCHARGE POLLUTANTS INTO THE WWF UNLESS IN
 ACCORDANCE WITH THIS ARTICLE.
 (B) DISCHARGE PROHIBITIONS. NO USER SHALL DISCHARGE
 INTO THE WWF ANY WASTE OR WASTEWATER WHICH MAY CAUSE
 PASS THROUGH OR INTERFERE WITH THE OPERATION OR
 PERFORMANCE OF THE WWF. NO USER SHALL DISCHARGE INTO
 THE WWF OR ANY CONNECTED SYSTEM ANY WASTE OR WASTEWATER
 CONTAINING ANY OF THE FOLLOWING:
 (5) STORMWATER, SURFACE WATER, GROUNDWATER, ARTESIAN
 WELL WATER, ROOF RUNOFF, SUBSURFACE DRAINAGE, SWIMMING
 POOL DISCHARGES, UNCONTAMINATED COOLING WATER,
 UNPOLLUTED INDUSTRIAL PROCESS WATERS, AIR CONDITIONING
 CONDENSATE, UNLESS SPECIFICALLY AUTHORIZED BY THE CITY
 IN WRITING.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-09-15 Cont ID  
Sent By rwbrown Date 2022-09-15 Time 07:08 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-06-27 Cont ID  
Sent By rwbrown Date 2022-06-27 Time 14:24 Rev Time 0.00
Received By rwbrown Date 2022-06-27 Time 14:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-05-31 Cont ID  
Sent By rwbrown Date 2022-05-31 Time 11:59 Rev Time 0.00
Received By rwbrown Date 2022-05-31 Time 11:54 Sent To  
Notes
2022-05-31 11:59:052ND PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. 2020 FPC 607.1/607.1.1/607.1.2 - PLEASE DETAILS FOR
 HOT WATER DELIVERY AS WELL AS TEMPERED WATER DELIVERY
 THAT COMPLIES WITH 607.1. TEMPERED WATER DELIVERY MUST
 BE LIMITED BY A DEVICE THAT COMPLIES WITH ASSE 1070. A
 THERMOSTAT CONTOL ON THE WATER HEATER SHALL NOT SERVE
 AS THE TERMPERATURE LIMITING MEANS FOR HOT WATER
 DELIVERY.
  
 TEMPERED WATER SHALL BE LIMITED BY A DEVICE THAT MEETS
 ASSE 1070, THE DETAILS MUST BE SHOWN.
  
 HOT WATER CANNOT BE LIMITED BY THE THERMOSTAT ON THE
 WATER HEATER. A DEVICE MUST BE SHOWN.
  
 SIMPLY SETTING THE THERMOSTAT DOES NOT COMPLY WITH
 EITHER OF THESE REQUIREMENTS.
  
 3. DONE
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-04-27 Cont ID  
Sent By rwbrown Date 2022-04-27 Time 09:29 Rev Time 0.00
Received By rwbrown Date 2022-04-27 Time 09:02 Sent To  
Notes
2022-04-27 09:29:211ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.1.3 #3,4 - MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS - PLEASE SHOW THE
 ISOMETRICS FOR THE WATER SUPPLY PIPING AND THE DRAIN,
 WASTE, AND VENT PIPING FOR YOUR INTENDED CONNECTION.
  
 2. 2020 FPC 607.1/607.1.1/607.1.2 - PLEASE DETAILS FOR
 HOT WATER DELIVERY AS WELL AS TEMPERED WATER DELIVERY
 THAT COMPLIES WITH 607.1. TEMPERED WATER DELIVERY MUST
 BE LIMITED BY A DEVICE THAT COMPLIES WITH ASSE 1070. A
 THERMOSTAT CONTOL ON THE WATER HEATER SHALL NOT SERVE
 AS THE TERMPERATURE LIMITING MEANS FOR HOT WATER
 DELIVERY.
  
 3. 2020 FPC 403.1 - PLEASE PROVIDE A SERVICE SINK AS
 REQUIRED BY 403.1 - MINIMUM NUMBER OF FIXTURES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status F Date 2023-02-13 Cont ID  
Sent By jbaker Date 2023-02-13 Time 11:37 Rev Time 0.00
Received By jbaker Date 2023-02-13 Time 11:34 Sent To  
Notes
2023-02-13 12:04:48IN THE DESCRIPTION OF OPERATIONS /LOCATIONS/VEHICLES
 BOX AT BOTTOM OF COI FORM PROVIDE VERBIAGE:
  
 PERFORMANCE OF INSPECTIONS PURSUANT TO FS 553.791
 FIRM NAME:
 PRIVATE PROVIDER: NAME AND ALL DULY AUTHORIZED
 REPRESENTATIVES
  
 IN OTHER WORDS NEEDS TO MEET INTENT OF FS 553.791 4(B)
 DEMONSTRATING THAT PROFESSIONAL LIABILITY INSURANCE
 COVERAGE IS IN PLACE FOR THE PRIVATE PROVIDER???S FIRM,
 THE PRIVATE PROVIDER, AND ANY DULY AUTHORIZED
 REPRESENTATIVE IN THE AMOUNTS REQUIRED BY THIS SECTION.
2023-02-13 11:40:46PROVIDE DESCRIPTION OF OPERATIONS/VEHICLES NARRATIVE IN
 THE BOX PROVIDED ON THE COI FORM.
 SHALL DESCRIBE DUTIES TO BE PERFORMED PURSUANT TO FS
 553.791; FIRM'S NAME WITH PRIVATE PROVIDER AND ALL DULY
 AUTHORIZED REPRESENTATIVES

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2022-12-16 Cont ID  
Sent By dbattles Date 2022-12-08 Time 09:10 Rev Time 0.00
Received By dbattles Date 2022-12-08 Time 09:10 Sent To  
Notes
2022-12-16 08:27:16NEED REVISED COI
 SENT EMAIL TO PRIVATE PROVIDER
2022-12-08 09:11:20INSPECTIONS
 PAPERWORK SENT TO FILENET

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-09-15 Cont ID  
Sent By rwbrown Date 2022-09-15 Time 07:11 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-09-08 15:27:38MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-06-27 Cont ID  
Sent By rwbrown Date 2022-06-27 Time 14:26 Rev Time 0.00
Received By rwbrown Date 2022-06-27 Time 14:26 Sent To  
Notes
2022-06-27 14:27:18ELECTRICAL PAGES NOT SIGNED
  
 ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR
 ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH
 61G1-16 AND 61G15, F.A.C

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-06-06 Cont ID  
Sent By rmcphers Date 2022-06-06 Time 14:59 Rev Time 0.00
Received By rmcphers Date 2022-06-06 Time 14:59 Sent To  
Notes
2022-06-06 15:00:01SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) THE SIGNED AND SEALED ELECTRICAL DRAWINGS DO NOT
 SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  
2022-05-31 10:55:17DIGITAL SIGNATURES FOR MECHANICAL APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-05-10 Cont ID  
Sent By rmcphers Date 2022-05-10 Time 16:00 Rev Time 0.00
Received By rmcphers Date 2022-05-10 Time 16:00 Sent To  
Notes
2022-05-10 16:02:14SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) THE SIGNED AND SEALED ELECTRICAL DRAWINGS DO NOT
 SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
2022-05-03 14:29:47MECHANICAL DIGITAL SIGNATURES OK.ME

Review Stop Z ZONING
Rev No 4 Status P Date 2022-09-22 Cont ID  
Sent By ckimmerl Date 2022-09-22 Time 16:11 Rev Time 0.00
Received By ckimmerl Date 2022-09-22 Time 16:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2022-07-08 Cont ID  
Sent By ckimmerl Date 2022-07-08 Time 12:25 Rev Time 0.00
Received By ckimmerl Date 2022-07-08 Time 12:21 Sent To  
Notes
2022-07-08 12:23:20REPEATED UPDATE COMMENT:
  
 1. DETERMINATION WITH PLANNING STAFF AND CITY ATTORNEY
 HAS COME TO THE CONCLUSION AND FINAL ZONING
 INTERPRETATION:
 SHOULD THE "BACK-WALL" OF THE DISPENSARY USE OR
 TENANT'S OPERATION FALL WITHIN THE 500 FT. BUFFER FROM
 THE SCHOOL, THE USE OR OCCUPATION OF THIS SPACE FOR A
 MEDICAL MARIJUANA DISPENSARY IS NOT PERMITTED. ANY
 DISPENSARY USE WOULD HAVE TO FALL OUTSIDE OF THIS 500
 FT. BUFFER AND TERMINATE AT THE BOUNDARY. IT APPEARS
 THAT MORE THAN HALF OF THE STORE IS NOT COMPLIANT.
  
 PLEASE PROVIDE PROOF/DIMENSIONS SHOWING THAT THE
 PORTION OF THE COMMERICIAL SPACE THAT HOUSES THE
 DISPENSARY USE/FUNCTION FALLS OUTSIDE OF THE 500 FT.
 BUFFER (SHOW THE DEPTH OF THE DISPENSARY). GROUND FLOOR
 PLAN WILL HAVE TO BE ADJUSTED TO REFLECT CODE
 REQUIREMENT.
  
 PREVIOUS REPEAT COMMENT:
  
 PER ARTICLE IV. - DOWNTOWN MASTER PLAN URBAN
 REGULATIONS WITHIN THE CITY CODE, SEC. 94-106. -
 GENERAL USES WITH SPECIAL REQUIREMENTS. SPECIFIES THE
 FOLLOWING:
  
 MEDICAL MARIJUANA DISPENSARIES. MEDICAL MARIJUANA
 DISPENSARIES SHALL BE PERMITTED WITHIN THE URBAN CORE
 PLANNING AREA, SPECIAL DISTRICT PLANNING AREA, AND
 RESIDENTIAL ENCLAVE PLANNING AREA, EXCEPT NWD-R-C1,
 BPD-R, PPD-PO AND PPD-R, PROVIDED THE FOLLOWING
 CONDITIONS ARE MET: SEPARATION DISTANCE. A MEDICAL
 MARIJUANA DISPENSARY SHALL NOT BE LOCATED WITHIN 500
 FEET OF THE REAL PROPERTY THAT COMPRISES A PUBLIC OR
 PRIVATE ELEMENTARY SCHOOL, MIDDLE SCHOOL, OR SECONDARY
 SCHOOL, UNLESS WAIVED BY THE CITY COMMISSION PURSUANT
 TO F.S. 381.986.
  
 1. THERE IS A SCHOOL (BILGRAV SCHOOL - 307 EVERNIA
 STREET, 2ND FLOOR) LOCATED WITHIN THE 500-FOOT
 PROXIMITY THAT PROHIBITS THE USE OF A MEDICAL MARIJUANA
 DISPENSARY FROM OCCUPYING AND OPERATING WITHIN THIS
 PROPERTY/LOCATION.
  
  
 CHRIS KIMMERLY, URBAN DESIGN PLANNER
 [email protected] 822-1426
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-06-09 Cont ID  
Sent By ckimmerl Date 2022-06-09 Time 17:00 Rev Time 0.00
Received By ckimmerl Date 2022-06-09 Time 16:53 Sent To  
Notes
2022-06-09 16:59:55REPEAT COMMENT:
  
 PER ARTICLE IV. - DOWNTOWN MASTER PLAN URBAN
 REGULATIONS WITHIN THE CITY CODE, SEC. 94-106. -
 GENERAL USES WITH SPECIAL REQUIREMENTS. SPECIFIES THE
 FOLLOWING:
  
 MEDICAL MARIJUANA DISPENSARIES. MEDICAL MARIJUANA
 DISPENSARIES SHALL BE PERMITTED WITHIN THE URBAN CORE
 PLANNING AREA, SPECIAL DISTRICT PLANNING AREA, AND
 RESIDENTIAL ENCLAVE PLANNING AREA, EXCEPT NWD-R-C1,
 BPD-R, PPD-PO AND PPD-R, PROVIDED THE FOLLOWING
 CONDITIONS ARE MET: SEPARATION DISTANCE. A MEDICAL
 MARIJUANA DISPENSARY SHALL NOT BE LOCATED WITHIN 500
 FEET OF THE REAL PROPERTY THAT COMPRISES A PUBLIC OR
 PRIVATE ELEMENTARY SCHOOL, MIDDLE SCHOOL, OR SECONDARY
 SCHOOL, UNLESS WAIVED BY THE CITY COMMISSION PURSUANT
 TO F.S. 381.986.
  
 1. THERE IS A SCHOOL (BILGRAV SCHOOL - 307 EVERNIA
 STREET, 2ND FLOOR) LOCATED WITHIN THE 500-FOOT
 PROXIMITY THAT PROHIBITS THE USE OF A MEDICAL MARIJUANA
 DISPENSARY FROM OCCUPYING AND OPERATING WITHIN THIS
 PROPERTY/LOCATION.
  
  
  
 UPDATE COMMENT:
  
 1. DETERMINATION WITH PLANNING STAFF AND CITY ATTORNEY
 HAS COME TO THE CONCLUSION AND FINAL ZONING
 INTERPRETATION:
 SHOULD THE "BACK-WALL" OF THE DISPENSARY USE OR
 TENANT'S OPERATION FALL WITHIN THE 500 FT. BUFFER FROM
 THE SCHOOL, THE USE OR OCCUPATION OF THIS SPACE FOR A
 MEDICAL MARIJUANA DISPENSARY IS NOT PERMITTED. ANY
 DISPENSARY USE WOULD HAVE TO FALL OUTSIDE OF THIS 500
 FT. BUFFER AND TERMINATE AT THE BOUNDARY.
  
 PLEASE PROVIDE PROOF/DIMENSIONS SHOWING THAT THE
 PORTION OF THE COMMERICIAL SPACE THAT HOUSES THE
 DISPENSARY USE/FUNCTION FALLS OUTSIDE OF THE 500 FT.
 BUFFER (SHOW THE DEPTH OF THE DISPENSARY). GROUND FLOOR
 PLAN WILL HAVE TO BE ADJUSTED TO REFLECT CODE
 REQUIREMENT.
  
  
  
 CHRIS KIMMERLY, URBAN DESIGN PLANNER
 [email protected] 822-1426
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-04-26 Cont ID  
Sent By ckimmerl Date 2022-04-26 Time 15:38 Rev Time 0.00
Received By ckimmerl Date 2022-04-26 Time 15:35 Sent To  
Notes
2022-04-26 15:38:46PER ARTICLE IV. - DOWNTOWN MASTER PLAN URBAN
 REGULATIONS WITHIN THE CITY CODE, SEC. 94-106. -
 GENERAL USES WITH SPECIAL REQUIREMENTS. SPECIFIES THE
 FOLLOWING:
  
 MEDICAL MARIJUANA DISPENSARIES. MEDICAL MARIJUANA
 DISPENSARIES SHALL BE PERMITTED WITHIN THE URBAN CORE
 PLANNING AREA, SPECIAL DISTRICT PLANNING AREA, AND
 RESIDENTIAL ENCLAVE PLANNING AREA, EXCEPT NWD-R-C1,
 BPD-R, PPD-PO AND PPD-R, PROVIDED THE FOLLOWING
 CONDITIONS ARE MET: SEPARATION DISTANCE. A MEDICAL
 MARIJUANA DISPENSARY SHALL NOT BE LOCATED WITHIN 500
 FEET OF THE REAL PROPERTY THAT COMPRISES A PUBLIC OR
 PRIVATE ELEMENTARY SCHOOL, MIDDLE SCHOOL, OR SECONDARY
 SCHOOL, UNLESS WAIVED BY THE CITY COMMISSION PURSUANT
 TO F.S. ? 381.986.
  
 1. THERE IS A SCHOOL (BILGRAV SCHOOL ? 307 EVERNIA
 STREET, 2ND FLOOR) LOCATED WITHIN THE 500-FOOT
 PROXIMITY THAT PROHIBITS THE USE OF A MEDICAL MARIJUANA
 DISPENSARY FROM OCCUPYING AND OPERATING WITHIN THIS
 PROPERTY/LOCATION.
  
 CHRIS KIMMERLY, URBAN DESIGN PLANNER
 [email protected] 822-1426
  