Plan Review Details - Permit 22040505
Plan Review Stops For Permit 22040505
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-06-29 Cont ID  
Sent By rmcdouga Date 2023-06-29 Time 09:17 Rev Time 0.00
Received By rmcdouga Date 2023-06-29 Time 08:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-04-10 Cont ID  
Sent By rmcdouga Date 2023-04-10 Time 15:25 Rev Time 0.00
Received By rmcdouga Date 2023-04-10 Time 15:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-06-23 Cont ID  
Sent By rmcdouga Date 2022-06-23 Time 14:20 Rev Time 0.00
Received By rmcdouga Date 2022-06-23 Time 12:15 Sent To  
Notes
2022-06-23 12:13:39PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SITE SHOWN ON THE COVER SHEET PL0.00 IS NOT THE
 LOCATION OF THIS PROJECT. THIS PROJECT IS LOCATED AT
 4334 N. FLAGLER DRIVE, WEST PALM BEACH, FLORIDA, FBC
 AMENDMENTS 107.2.1
  
 2) SUBMIT A COPY OF THE MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE ADA POOL LIFT.
 FBC 107.2.1
  
 3) POOL IS SHOWN WITH A WATER DEPTH OF LESS THAN 4
 FEET. FBC 454.1.2.2.4 POOL DEPTHS. THE MINIMUM WATER
 DEPTH SHALL BE 3 FEET (914 MM) IN SHALLOW AREAS AND 4
 FEET (1219 MM) IN DEEP AREAS.
  
 4) SHOW THAT THERE IS ADEQUATE CLEARANCE AT THE POOL
 LIFT. FBC 454.1.2.5.6 DISABLED ACCESS. PERMANENT OR
 PORTABLE STEPS, RAMPS, HANDRAILS, LIFTS OR OTHER
 DEVICES DESIGNED TO ACCOMMODATE HANDICAPPED INDIVIDUALS
 IN SWIMMING POOLS MAY BE PROVIDED. LIFTS MOUNTED INTO
 THE POOL DECK SHALL HAVE A MINIMUM 4-FOOT-WIDE (1219
 MM) DECK BEHIND THE LIFT MOUNT.
  
 5) SHOW COMPLIANCE WITH FBC 454.1.3.1.3. POOL WET DECKS
 SHALL HAVE A MINIMUM UNOBSTRUCTED WIDTH OF 4 FEET (1219
 MM) AROUND THE PERIMETER OF THE POOL, POOL CURB,
 LADDERS, HANDRAILS, DIVING BOARDS, DIVING TOWERS AND
 SLIDES.
  
 6) SHOW COMPLIANCE WITH FBC 454.1.3.1.5. WALKWAYS SHALL
 BE PROVIDED BETWEEN THE POOL AND THE SANITARY
 FACILITIES, AND SHALL BE CONSTRUCTED OF CONCRETE OR
 OTHER NONABSORBENT MATERIAL HAVING A SMOOTH
 SLIP-RESISTANT FINISH FOR THE FIRST 15 FEET (4572 MM)
 OF THE WALKWAY MEASURED FROM THE NEAREST POOL WATER'S
 EDGE. A HOSE BIBB WITH A VACUUM BREAKER SHALL BE
 PROVIDED TO ALLOW THE DECK TO BE WASHED DOWN WITH
 POTABLE WATER.
  
 7) SHOW COMPLIANCE WITH FBC 454.1.6.1 SANITARY
 FACILITIES. SWIMMING POOLS WITH A BATHING LOAD OF 20
 PERSONS OR LESS MAY UTILIZE A UNISEX RESTROOM. POOLS
 WITH BATHING LOADS OF 40 PERSONS OR LESS MAY UTILIZE
 TWO UNISEX RESTROOMS OR MEET THE REQUIREMENTS OF TABLE
 454.1.6.1. UNISEX RESTROOMS SHALL MEET ALL THE
 REQUIREMENTS FOR MATERIALS, DRAINAGE AND SIGNAGE AS
 INDICATED IN SECTIONS 454.1.6.1.1 THROUGH 454.1.6.1.4.
 EACH SHALL INCLUDE A WATER CLOSET, A DIAPER CHANGE
 TABLE, A URINAL AND A LAVATORY. POOLS WITH A BATHING
 LOAD LARGER THAN 40 PERSONS SHALL PROVIDE SEPARATE
 SANITARY FACILITIES LABELED FOR EACH SEX. THE ENTRY
 DOORS OF ALL RESTROOMS SHALL BE LOCATED WITHIN A
 200-FOOT (60 960 MM) WALKING DISTANCE OF THE NEAREST
 WATER'S EDGE OF EACH POOL SERVED BY THE FACILITIES.
 EXCEPTION: WHERE A SWIMMING POOL SERVES ONLY A
 DESIGNATED GROUP OF RESIDENTIAL DWELLING UNITS
 INCLUDING HOTEL ROOMS AND NOT THE GENERAL PUBLIC,
 POOLSIDE SANITARY FACILITIES ARE NOT REQUIRED IF ALL
 LIVING UNITS ARE WITHIN A 200-FOOT (60 960 MM)
 HORIZONTAL RADIUS OF THE NEAREST WATER'S EDGE, ARE NOT
 OVER THREE STORIES IN HEIGHT UNLESS SERVICED BY AN
 ELEVATOR, AND ARE EACH EQUIPPED WITH PRIVATE SANITARY
 FACILITIES.
  
 8) A LIFE SAFTEY PLAN WAS SUBMITTED FOR LEVEL 1 (THE
 GROUND FLOOR). SUBMIT A LIFE SAFETY PLAN FOR THE ROOF
 TOP POOL LEVEL. FBC 107.2.1
  
 9) SHOW COMPLIANCE WITH FBC 454.1.6.2 RINSE SHOWER. A
 MINIMUM OF ONE RINSE SHOWER SHALL BE PROVIDED ON THE
 POOL DECK OF ALL OUTDOOR POOLS WITHIN THE PERIMETER OF
 THE FENCE.
  
 10) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-04-11 Cont ID  
Sent By fgiaquin Date 2023-04-11 Time 19:58 Rev Time 0.00
Received By fgiaquin Date 2023-04-10 Time 21:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-05-16 Cont ID  
Sent By fgiaquin Date 2022-05-16 Time 19:15 Rev Time 0.00
Received By fgiaquin Date 2022-05-12 Time 20:03 Sent To  
Notes
2022-05-16 19:15:42ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONALPROVIDE
 CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1
  
 PLAN TO INCLUDE POOL EQUIPMENT WIRING, BONDING, PANEL
 SCHEDULES, SIZE OF FEEDERS, OCP, ETC.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2023-06-14 Cont ID  
Sent By ccole Date 2023-06-14 Time 12:48 Rev Time 0.00
Received By ccole Date 2023-06-14 Time 12:00 Sent To  
Notes
2023-06-14 12:49:11GAS APPROVED UNDER PERMIT 21060844.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-04-07 Cont ID  
Sent By ccole Date 2023-04-07 Time 18:05 Rev Time 0.00
Received By ccole Date 2023-04-05 Time 12:08 Sent To  
Notes
2023-04-07 18:06:011ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22040505
 4/7/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) FUEL GAS FOR THE BUILDING WAS REVIEWED UNDER THE
 MASTER PERMIT 18100526 WHICH IS STILL AN OPEN PERMIT.
 ALL REVISIONS TO THE GAS PIPING SHALL BE SUBMITTED AS A
 REVISON TO THE MASTER. GAS WILL NOT BE REVIEWED UNDER
 THIS PERMIT AND WILL REMAIN FAILED UNTIL REVISIONS ARE
 SUBMITTED FOR REVIEW. WHEN YOU HAVE SUBMITTED THE
 REVISIONS, PLEASE EMAIL ME AT [email protected] AND I WILL
 REMOVE THE FAILED REVIEW.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-29 Cont ID  
Sent By rmcdouga Date 2023-06-29 Time 09:18 Rev Time 0.00
Received By rmcdouga Date 2023-06-09 Time 08:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-11 Cont ID  
Sent By fgiaquin Date 2023-04-11 Time 19:58 Rev Time 0.00
Received By fgiaquin Date 2023-03-30 Time 15:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-23 Cont ID  
Sent By rmcdouga Date 2022-06-23 Time 14:21 Rev Time 0.00
Received By rmcdouga Date 2022-04-19 Time 09:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-06-14 Cont ID  
Sent By ccole Date 2023-06-14 Time 12:45 Rev Time 0.00
Received By ccole Date 2023-06-14 Time 11:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-04-07 Cont ID  
Sent By ccole Date 2023-04-07 Time 17:54 Rev Time 0.00
Received By ccole Date 2023-04-05 Time 12:07 Sent To  
Notes
2023-04-07 17:58:24 
 2ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22040505
 4/7/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. THE ARCHITECT'S NARRATIVE
 RESPONSES INDICATE THE CLASSIFICATION OF THE SOUTH
 ROOFTOP POOL HAS BEEN CHANGED TO A PRIVATE RESIDENTIAL
 POOL FOR THE PENTHOUSE APARTMENT HOWEVER THE PLANS DO
 NOT APPEAR TO REFLECT THE CHANGE. I AM UNABLE TO LOCATE
 ANY PLAN WHICH LABELS THE POOL AS A PRIVATE RESIDENTIAL
 POOL FOR PENTHOUSE RESIDENT USE ONLY. THE REPEATED
 STATEMENT IN THE NARRATIVE THAT THE POOL ENTRY IS
 ACCESS CONTROLLED DOES NOT APPEAR RELEVANT TO POOL
 CLASSSIFICATIONS AS DEFINED IN SECS. 454.1.1& 454.2.2
 FBC B.
 FAILED 1ST REVIEW COMMENTS ARE LISTED BELOW WITH
 ADDITIONAL NOTES.
  
 1) FAILED. SHEET PL0.21: PLEASE PROVIDE A SITE UTILITY
 PLAN FOR THE ROOF TOP POOL- SEC. 107.2.1 WPB. SHOW THE
 POINTS OF CONNECTIONS TO WATER SUPPLY LINE, WASTE AND
 STORM DRAIN LINES, GAS PIPING, AND ELECTRICAL SERVICE.
 PLEASE NOTE THAT THE WATER SUPPLY TO THE POOL SHALL BE
 PROTECTED AGAINST BACKFLOW WITH AN RPZ TYPE BACKFLOW
 PREVENTER WHICH SHALL BE INSTALLED UNDER A SEPARATE
 PERMIT. SHOW THE LOCATION OF THE DEVICE AND PROVIDE
 NOTES TO INDICATE COMPLIANCE- SEC. 105.1, 107.2.1 WPB,
 AND WPB UTILITIES CROSS-CONNECTION MANUAL.
 THE ARCHITECT'S NARRATIVE REFERENCES SHEET P5.03S AND
 SS/19 FOR POOL BACKWASH INTO FUNNEL DRAIN. PLEASE NOTE
 THE DRAINAGE SHALL NOT DISCHARGE INTO THE SANITARY
 SEWER- SEC. 90-126 (5) WPB CODE OF ORDINANCES.
  
 2) FAILED. PL0.21: PROVIDE PLUMBING FIXTURE
 CALCULATIONS FOR THE POOL AND SHOW THE LOCATIONS OF THE
 SANITARY FACILITIES- TABLE 454.1.6.1 AND SECS.
 454.1.6.1- 454.6.1.2 FBC B. IF CLAIMING THE EXCEPTION
 UNDER SEC. 454.1.6.1 PLEASE PROVIDE NOTES AND DETAILS
 ON THE PLAN TO VERIFY COMPLIANCE. THE SUBMITTED PLANS
 DO NOT CLEARLY INDICATE THE LOCATIONS OF THE POOL
 BATHROOMS AND WHICH BATHROOMS ARE DESIGNATED FOR USERS
 OF THE POOL AND DECK AREAS. PROVIDE COMPLIANCE DETAILS
 AND INFORMATION AS REQUIRED BY SECS. 454.1.6.1.1-
 454.1.6.1.4 FBC B. PLEASE NOTE THE REQUIRED SANITARY
 FACILITIES AND PLUMBING FIXTURES REQUIRED FOR THE POOL
 AREA (BATHROOM FIXTURES, HOSE BIBS, POOL SHOWERS) AND
 IN THE EQUIPMENT ROOM- SHALL BE INSTALLED UNDER
 SEPARATE PERMITS- SECS. 105.1 & 107.2.1 WPB.
 THE ARCHITECT'S NARRATIVE INDICATES THE ROOFTOP POOL IS
 FOR PRIVATE USE HOWEVER THE PLANS DO NOT APPEAR TO
 REFLECT THE CHANGE. I AM UNABLE TO LOCATE ANY PLAN
 WHICH LABELS THE POOL AS A PRIVATE RESIDENTIAL POOL FOR
 PENTHOUSE RESIDENT USE ONLY. ALL NOTES, DETAILS,
 SPECIFICATIONS, ETC. INDICATE A COMMERCIAL, PUBLIC USE
 POOL- SEE SECS. 454.2, 454.2.2 FBC B.
  
  
 5) FAILED. SHEET PL2.00: INDICATE THE BATHING LOAD TO
 BE BASED ON TRANSIENT OR NON-TRANSIENT USE- SEC.
 454.1.1.1 FBC B.
 THE ARCHITECT'S NARRATIVE INDICATES THE ROOFTOP POOL IS
 FOR PRIVATE USE HOWEVER THE PLANS DO NOT APPEAR TO
 REFLECT THE CHANGE. I AM UNABLE TO LOCATE ANY PLAN
 WHICH LABELS THE POOL AS A PRIVATE RESIDENTIAL POOL FOR
 PENTHOUSE RESIDENT USE ONLY. ALL NOTES, DETAILS,
 SPECIFICATIONS, ETC. INDICATE A COMMERCIAL, PUBLIC USE
 POOL- SEE SECS. 454.2, 454.2.2 FBC B.
  
  
 7) FAILED. PL2.15 & PL2.30: THE WASTE WATER FROM THE
 POOL VIA THE SUMP PUMP IN THE EQUIPMENT ROOM SHALL NOT
 DRAIN INTO THE SANITARY SYSTEM. WASTEWATER FROM THE
 POOL AND THE POOL EQUIPMENT SHALL BE DECHLORINATED AND
 DISCHARGED THROUGH AN AIR GAP IN THE INTO THE STORM
 DRAINAGE SYSTEM- SEC. 454.1.6.5.15 & SEC. 90-126(5) WPB
 CODE OF ORDINANCES. THE WASTEWATER SHALL NOT DISCHARGE
 INTO THE SANITARY SYSTEM. PLEASE REVIEW WPB BUILDING
 DEPT. GUIDELINES FOR POOL WATER DISPOSAL. THE ENGINEER
 OF RECORD SHALL SHOW THE DECHLORINATION SYSTEM ON THE
 PLAN AND PROVIDE SPECIFICATIONS FOR ALL EQUIPMENT.
 PLEASE SEE GUIDELINES BELOW-
  
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL
 OWNER'S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 E) FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS,
 PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 THE ARCHITECT'S RESPONSE REFERENCES SHEET P2.07S FOR
 POOL WASTEWATER RECEIVING LOCATION. NOTES 12 & 14
 INDICATE FUNNEL DRAINS FOR POOL BACKWASH. PLEASE SHOW
 DISPOSAL LOCATION OF THE BACKWASH- SANITARY OR STORM,
 AND PLEASE IDENTIFY ALL OTHER DRAINS CONVEYING POOL
 WASTEWATER AND THEIR RESPECTIVE DISPOSAL LOCATIONS.
  
 8) FAILED. PL2.10: A WALL INLET IS REQUIRED DIRECTLY
 ACROSS FROM THE SKIMMER- SEC. 454.1.6.5.3.2.4 FBC B.
 THE ARCHITECT???S NARRATIVE INDICATES THE ROOFTOP POOL
 IS FOR PRIVATE USE HOWEVER THE PLANS DO NOT APPEAR TO
 REFLECT THE CHANGE. I AM UNABLE TO LOCATE ANY PLAN
 WHICH LABELS THE POOL AS A PRIVATE RESIDENTIAL POOL FOR
 PENTHOUSE RESIDENT USE ONLY. ALL NOTES, DETAILS,
 SPECIFICATIONS, ETC. INDICATE A COMMERCIAL, PUBLIC USE
 POOL- SEE SECS. 454.2, 454.2.2 FBC B.
  
 9) FAILED. PL2.10: THE SPACING OF THE WALL INLETS DOES
 NOT APPEAR TO BE IN COMPLIANCE WITH SEC. 454.1.6.5.9.1
 FBC B- SPACING SHALL NOT EXCEED 20 FT.
 THE ARCHITECT'S NARRATIVE INDICATES THE ROOFTOP POOL IS
 FOR PRIVATE USE HOWEVER THE PLANS DO NOT APPEAR TO
 REFLECT THE CHANGE. I AM UNABLE TO LOCATE ANY PLAN
 WHICH LABELS THE POOL AS A PRIVATE RESIDENTIAL POOL FOR
 PENTHOUSE RESIDENT USE ONLY. ALL NOTES, DETAILS,
 SPECIFICATIONS, ETC. INDICATE A COMMERCIAL, PUBLIC USE
 POOL- SEE SECS. 454.2, 454.2.2 FBC B.
  
 10) FAILED. PL2.15 SYSTEM DESIGN: PLEASE VERIFY THAT
 THE DESIGN PATTERN OF THE RECIRCULATION FLOW SHALL BE
 100% THROUGH THE MAIN DRAIN PIPING, AND 60% THROUGH THE
 SKIMMER SYSTEM- SEC. 454.1.6.5.3 FBC B.
 THERE WAS NO PLAN NOTE OR DETAIL REFERENCED IN THE
 RESPONSE TO CONFIRM COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-05-03 Cont ID  
Sent By ccole Date 2022-05-03 Time 11:43 Rev Time 0.00
Received By ccole Date 2022-05-03 Time 08:46 Sent To  
Notes
2022-05-03 11:46:261ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22040505
 5/3/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET PL0.21: PLEASE PROVIDE A SITE UTILITY PLAN FOR
 THE ROOF TOP POOL- SEC. 107.2.1 WPB. SHOW THE POINTS OF
 CONNECTIONS TO WATER SUPPLY LINE, WASTE AND STORM DRAIN
 LINES, GAS PIPING, AND ELECTRICAL SERVICE. PLEASE NOTE
 THAT THE WATER SUPPLY TO THE POOL SHALL BE PROTECTED
 AGAINST BACKFLOW WITH AN RPZ TYPE BACKFLOW PREVENTER
 WHICH SHALL BE INSTALLED UNDER A SEPARATE PERMIT. SHOW
 THE LOCATION OF THE DEVICE AND PROVIDE NOTES TO
 INDICATE COMPLIANCE- SEC. 105.1, 107.2.1 WPB, AND WPB
 UTILITIES CROSS-CONNECTION MANUAL.
  
 2) PL0.21: PROVIDE PLUMBING FIXTURE CALCULATIONS FOR
 THE POOL AND SHOW THE LOCATIONS OF THE SANITARY
 FACILITIES- TABLE 454.1.6.1 AND SECS. 454.1.6.1-
 454.6.1.2 FBC B. IF CLAIMING THE EXCEPTION UNDER SEC.
 454.1.6.1 PLEASE PROVIDE NOTES AND DETAILS ON THE PLAN
 TO VERIFY COMPLIANCE. THE SUBMITTED PLANS DO NOT
 CLEARLY INDICATE THE LOCATIONS OF THE POOL BATHROOMS
 AND WHICH BATHROOMS ARE DESIGNATED FOR USERS OF THE
 POOL AND DECK AREAS. PROVIDE COMPLIANCE DETAILS AND
 INFORMATION AS REQUIRED BY SECS. 454.1.6.1.1-
 454.1.6.1.4 FBC B. PLEASE NOTE THE REQUIRED SANITARY
 FACILITIES AND PLUMBING FIXTURES REQUIRED FOR THE POOL
 AREA (BATHROOM FIXTURES, HOSE BIBS, POOL SHOWERS) AND
 IN THE EQUIPMENT ROOM- SHALL BE INSTALLED UNDER
 SEPARATE PERMITS- SECS. 105.1 & 107.2.1 WPB.
  
 3) PL0.21: PROVIDE A HOSE BIB ON THE POOL DECK AND
 INCLUDE PIPING DETAILS AND AN EQUIPMENT SCHEDULE- SEC.
 454.1.3.1.5 FBC B.
  
 4) PL0.21; PROVIDE AN ENLARGED POOL SHOWER SHOWING THE
 TYPE OF VALVE, VALVE AND SHOWER HEAD HEIGHTS FROM THE
 FINISHED FLOOR, AND SHOWER DRAINAGE LOCATION- SEC.
 107.2.1 WPB AND REQUIREMENT 2 FAIR HOUSING DESIGN
 GUIDELINES-FBC ACC.
  
 5) SHEET PL2.00: INDICATE THE BATHING LOAD TO BE BASED
 ON TRANSIENT OR NON-TRANSIENT USE- SEC. 454.1.1.1 FBC
 B.
  
 6) PL2.00 & PL2.05: THE POOL DEPTH SHALL BE 4 FT. IN
 THE DEEP AREA- SEC. 454.1.2.2.4 FBC B.
  
 7) PL2.15 & PL2.30: THE WASTE WATER FROM THE POOL VIA
 THE SUMP PUMP IN THE EQUIPMENT ROOM SHALL NOT DRAIN
 INTO THE SANITARY SYSTEM. WASTEWATER FROM THE POOL AND
 THE POOL EQUIPMENT SHALL BE DECHLORINATED AND
 DISCHARGED THROUGH AN AIR GAP IN THE INTO THE STORM
 DRAINAGE SYSTEM- SEC. 454.1.6.5.15 & SEC. 90-126(5) WPB
 CODE OF ORDINANCES. THE WASTEWATER SHALL NOT DISCHARGE
 INTO THE SANITARY SYSTEM. PLEASE REVIEW WPB BUILDING
 DEPT. GUIDELINES FOR POOL WATER DISPOSAL. THE ENGINEER
 OF RECORD SHALL SHOW THE DECHLORINATION SYSTEM ON THE
 PLAN AND PROVIDE SPECIFICATIONS FOR ALL EQUIPMENT.
 PLEASE SEE GUIDELINES BELOW-
  
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL
 OWNER'S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 E) FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS,
 PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 8) PL2.10: A WALL INLET IS REQUIRED DIRECTLY ACROSS
 FROM THE SKIMMER- SEC. 454.1.6.5.3.2.4 FBC B.
  
 9) PL2.10: THE SPACING OF THE WALL INLETS DOES NOT
 APPEAR TO BE IN COMPLIANCE WITH SEC. 454.1.6.5.9.1 FBC
 B- SPACING SHALL NOT EXCEED 20 FT.
  
 10) PL2.15 SYSTEM DESIGN: PLEASE VERIFY THAT THE DESIGN
 PATTERN OF THE RECIRCULATION FLOW SHALL BE 100% THROUGH
 THE MAIN DRAIN PIPING, AND 60% THROUGH THE SKIMMER
 SYSTEM- SEC. 454.1.6.5.3 FBC B.
  
 11) PL2.15: SHOW THE LOCATION OF THE AUTO FILL AT THE
 COLLECTOR TANK- SEC. 454.1.6.5.11 FBC B.
  
 12) PL2.30: A HOSE BIB WITH A VACUUM BREAKER SHALL BE
 INSTALLED IN THE EQUIPMENT ROOM- SEC. 454.1.5.9 FBC B.
 PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR
 INSTALLATION OF THE POOL HEATER AND GAS PIPING-
 SEC.105.1 WPB.
  
 13) PL.2.00: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE WALL RETURN FITTINGS, MAIN DRAIN ASSEMBLIES,
 SKIMMER, THE ADA LIFT, AND THE EQUALIZER ASSEMBLY- SEC.
 107.2.1 WPB.
  
 14) PL2.30: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 RECIRCULATION EQUIPMENT LISTED IN THE SCHEDULE- SEC.
 107.2.1 WPB.
  
 15) PL0.22 POOL LIFT: PLEASE PROVIDE ENLARGED
 DIMENSIONED DETAILS ON THE PLANS AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUAL
 FOR THE LIFT- SEC.107.2.1 WPB.. SHOW COMPLIANCE WITH
 THE FOLLOWING FBC ACC CODE SECTIONS:
 A) 1009.2.2 SEAT LOCATION.
 IN THE RAISED POSITION, THE CENTERLINE OF THE SEAT
 SHALL BE LOCATED OVER THE DECK AND 16 INCHES MINIMUM
 FROM THE EDGE OF THE POOL. THE DECK SURFACE BETWEEN THE
 CENTERLINE OF THE SEAT AND THE POOL EDGE SHALL HAVE A
 SLOPE NOT STEEPER THAN 1:48.
 B) 1009.2.3 CLEAR DECK SPACE.
 ON THE SIDE OF THE SEAT OPPOSITE THE WATER, A CLEAR
 DECK SPACE SHALL BE PROVIDED PARALLEL WITH THE SEAT.
 THE SPACE SHALL BE 36 INCHES WIDE MINIMUM AND SHALL
 EXTEND FORWARD 48 INCHES MINIMUM FROM A LINE LOCATED 12
 INCHES BEHIND THE REAR EDGE OF THE SEAT. THE CLEAR DECK
 SPACE SHALL HAVE A SLOPE NOT STEEPER THAN 1:48.
 C) 1009.2.4 SEAT HEIGHT.
 THE HEIGHT OF THE LIFT SEAT SHALL BE DESIGNED TO ALLOW
 A STOP AT 16 INCHES MINIMUM TO 19 INCHES MAXIMUM
 MEASURED FROM THE DECK TO THE TOP OF THE SEAT SURFACE
 WHEN IN THE RAISED (LOAD) POSITION.
 D) 1009.2.6 FOOTRESTS AND ARMRESTS.
 FOOTRESTS SHALL BE PROVIDED AND SHALL MOVE WITH THE
 SEAT. IF PROVIDED, THE ARMREST POSITIONED OPPOSITE THE
 WATER SHALL BE REMOVABLE OR SHALL FOLD CLEAR OF THE
 SEAT WHEN THE SEAT IS IN THE RAISED (LOAD) POS
 E) 1009.2.7 OPERATION.
 THE LIFT SHALL BE CAPABLE OF UNASSISTED OPERATION FROM
 BOTH THE DECK AND WATER LEVELS. CONTROLS AND OPERATING
 MECHANISMS SHALL BE UNOBSTRUCTED WHEN THE LIFT IS IN
 USE AND SHALL COMPLY WITH 309.4.
 F) 1009.2.8 SUBMERGED DEPTH.
 THE LIFT SHALL BE DESIGNED SO THAT THE SEAT WILL
 SUBMERGE TO A WATER DEPTH OF 18 INCHES MINIMUM BELOW
 THE STATIONARY WATER LEVEL.
 G) 1009.2.9 LIFTING CAPACITY.
 SINGLE PERSON POOL LIFTS SHALL HAVE A WEIGHT CAPACITY
 OF 300 POUNDS MINIMUM AND BE CAPABLE OF SUSTAINING A
 STATIC LOAD OF AT LEAST ONE AND A HALF TIMES THE RATED
 LOAD.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-04-20 Cont ID  
Sent By shill Date 2022-04-20 Time 17:17 Rev Time 0.00
Received By shill Date 2022-04-20 Time 17:17 Sent To  
Notes
2022-04-20 17:17:59MASTER
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-06-29 Cont ID  
Sent By rmcdouga Date 2023-06-29 Time 09:18 Rev Time 0.00
Received By rmcdouga Date 2023-06-29 Time 08:37 Sent To  
Notes
2023-06-14 12:56:50NEW PLANS UPLOADED 6/8/23 PASSED SIGNATURE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-04-10 Cont ID  
Sent By rmcdouga Date 2023-04-10 Time 15:26 Rev Time 0.00
Received By rmcdouga Date 2023-04-10 Time 15:26 Sent To  
Notes
2023-04-10 15:39:16[ THE ENGINEER'S DIGITAL SIGNATURE ON THE ROOF TOP
 POOLS STRUCTURAL CALCULATIONS COULD NOT BE VERIFIED.
 ELECTRONICALLY SUBMITTED DRAWINGS OR OTHER DOCUMENTS
 ARE REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S
 DIGITAL SIGNATURE ON THEM. FS 481 & FAC 61G1 OR FS 471
 & FAC 61G15 ] SUBMIT A CLEAN COPY OF THE ROOF TOP POOL
 CALCULATIONS WITH THE DELEGATE ENGINEER'S DIGITAL
 SIGNATURE THAT DOES NOT HAVE THE SHOP DRAWING REVIEW
 STAMPS,

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-06-23 Cont ID  
Sent By rmcdouga Date 2022-06-23 Time 14:21 Rev Time 0.00
Received By rmcdouga Date 2022-06-23 Time 14:21 Sent To  
Notes
2022-06-23 14:26:44SUBMIT A CLEAN COPY OF THE ROOF TOP POOL CALCULATIONS
 WITH THE DELEGATE ENGINEER'S DIGITAL SIGNATURE THAT
 DOES NOT HAVE THE SHOP DRAWING REVIEW STAMPS,

Review Stop Z ZONING
Rev No 3 Status P Date 2023-06-27 Cont ID  
Sent By eschneid Date 2023-06-27 Time 17:10 Rev Time 0.25
Received By eschneid Date 2023-06-27 Time 16:58 Sent To  
Notes
2023-06-27 16:59:20THIS REVIEW IS LIMITED TO THE ROOFTOP POOL ONLY AND HAS
 BEEN PASSED SUBJECT TO THE FOLLOWING PROVISOS:
  
 1. ALL DEVELOPMENT WITHIN THE MARINA COMMERCIAL MARINE
 PLANNED DEVELOPMENT (CMPD) SHALL BE SUBJECT TO ALL
 DEVELOPMENT ORDER CONDITIONS, DESIGN GUIDELINES, ETC.,
 AS OUTLINED IN RESOLUTION NO. 66-22, AND AS MAY BE
 AMENDED. ALL CONDITIONS OF APPROVAL IMPOSED BY THE
 DEVELOPMENT ORDER SHALL BE ADDRESSED WITHIN THE
 APPROPRIATE SPECIFIED TIMEFRAMES.
 _______________________________________________________
 _____________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 _______________________________________________________
 _____________
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2023-04-11 Cont ID  
Sent By ESchneid Date 2023-04-11 Time 17:10 Rev Time 0.25
Received By eschneid Date 2023-04-11 Time 16:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-05-19 Cont ID  
Sent By jroach Date 2022-05-19 Time 09:26 Rev Time 0.00
Received By jroach Date 2022-05-19 Time 09:26 Sent To  
Notes
2022-05-19 09:26:59THIS REVIEW IS LIMITED TO THE ROOFTOP POOL ONLY AND HAS
 BEEN PASSED SUBJECT TO THE FOLLOWING PROVISOS:
  
 1. ALL DEVELOPMENT WITHIN THE MARINA COMMERCIAL MARINE
 PLANNED DEVELOPMENT (CMPD) SHALL BE SUBJECT TO ALL
 DEVELOPMENT ORDER CONDITIONS, DESIGN GUIDELINES, ETC.,
 AS OUTLINED IN RESOLUTION NO. 66-22, AND AS MAY BE
 AMENDED. ALL CONDITIONS OF APPROVAL IMPOSED BY THE
 DEVELOPMENT ORDER SHALL BE ADDRESSED WITHIN THE
 APPROPRIATE SPECIFIED TIMEFRAMES.
 _______________________________________________________
 _____________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 _______________________________________________________
 _____________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 P: 561.822.1448 | E: [email protected]