Plan Review Details - Permit 22040494
Plan Review Stops For Permit 22040494
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-04-13 Cont ID  
Sent By cpuell Date 2022-04-13 Time 14:33 Rev Time 0.00
Received By cpuell Date 2022-04-13 Time 14:33 Sent To  
Notes
2022-04-13 14:33:24ADDRESS APPROPRIATE FOR PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-08-01 Cont ID  
Sent By rmcphers Date 2022-08-01 Time 13:36 Rev Time 0.00
Received By rmcphers Date 2022-08-01 Time 13:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-07-08 Cont ID  
Sent By rmcphers Date 2022-07-08 Time 14:24 Rev Time 0.00
Received By rmcphers Date 2022-07-08 Time 14:24 Sent To  
Notes
2022-07-08 14:30:26DRAWING C1 DOES NOT SHOW AS ELECTRONICALLY SIGNED -
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-26 Cont ID  
Sent By rmcphers Date 2022-05-26 Time 08:21 Rev Time 0.00
Received By rmcphers Date 2022-05-25 Time 16:15 Sent To  
Notes
2022-05-26 08:21:09NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE PRODUCT APPROVALS FOR THE OVERHEAD
 DOORS AND ROOFING SYSTEMS.
  
 2) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB
 107.3.4
  
 3) PLEASE PROVIDE A STORM WATER DRAINAGE PLAN OR
 INCLUDE SITE DRAINAGE ON THE SITE PLAN - FBC WPB
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT
 SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES)

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-07-25 Cont ID  
Sent By mpeterso Date 2022-07-25 Time 13:56 Rev Time 0.00
Received By mpeterso Date 2022-07-25 Time 13:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-07-08 Cont ID  
Sent By mpeterso Date 2022-07-08 Time 15:37 Rev Time 0.00
Received By mpeterso Date 2022-07-08 Time 15:37 Sent To  
Notes
2022-07-08 15:37:59PREVIOUS COMMENTS NOT ADDRESSED

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-05-06 Cont ID  
Sent By mpeterso Date 2022-05-06 Time 09:53 Rev Time 0.00
Received By mpeterso Date 2022-05-06 Time 09:48 Sent To  
Notes
2022-05-06 09:55:41ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE AN ELECTRIC RISER DIAGRAM AND LOAD
 CALCULATIONS AS PER NEC 215.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop G GAS REVIEW
Rev No 4 Status N Date 2023-01-19 Cont ID  
Sent By rwbrown Date 2023-01-19 Time 06:57 Rev Time 0.00
Received By rwbrown Date 2023-01-19 Time 06:57 Sent To  
Notes
2023-01-19 06:57:32GAS PERMIT 23010663

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2022-07-22 Cont ID  
Sent By rwbrown Date 2022-07-22 Time 08:25 Rev Time 0.00
Received By rwbrown Date 2022-07-22 Time 08:24 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-07-05 Cont ID  
Sent By rwbrown Date 2022-07-05 Time 06:37 Rev Time 0.00
Received By rwbrown Date 2022-07-05 Time 06:37 Sent To  
Notes
2022-07-05 06:45:002ND GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. NEW COMMENT - 2017 WPB AMENDS 107.3.5.3(13) - THE
 GAS RISER MUST INCLUDE DETAILS INCLUDING THE TYPE OF
 GAS BEING USED, THE PIPING MATERIAL USED, THE SIZE OF
 EACH LENGTH OF PIPE, THE LENGTHS OF EACH SECTION, THE
 PRESSURES BETWEEN EACH REGULATOR, AND THE BTU LOADS
 USED TO CALCULATE THE SYSTEM'S PIPE SIZES. ALSO INCLUDE
 COMBUSTION AIR CALCULATIONS WHERE NEEDED AND SET BACKS
 FROM STRUCTURE OPENINGS FOR OUTSIDE APPLIANCES,
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-05-26 Cont ID  
Sent By rwbrown Date 2022-05-26 Time 12:04 Rev Time 0.00
Received By rwbrown Date 2022-05-26 Time 12:04 Sent To  
Notes
2022-05-26 12:04:451ST GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.3(13) - PLEASE INCLUDE THE
 GAS RISER AND DETAILS IN THE PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-01 Cont ID  
Sent By rmcphers Date 2022-08-01 Time 13:37 Rev Time 0.00
Received By rmcphers Date 2022-07-21 Time 14:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-08 Cont ID  
Sent By mpeterso Date 2022-07-08 Time 15:38 Rev Time 0.00
Received By mpeterso Date 2022-07-01 Time 16:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-26 Cont ID  
Sent By rwbrown Date 2022-05-26 Time 12:04 Rev Time 0.00
Received By rwbrown Date 2022-04-13 Time 07:02 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-08-23 Cont ID  
Sent By aoliver Date 2022-08-23 Time 10:03 Rev Time 0.00
Received By aoliver Date 2022-08-01 Time 13:55 Sent To  
Notes
2022-08-08 12:57:29RECEIPT MU-2022-036164-0000 -$22.46 PAID AO
2022-08-01 13:56:048/1/22 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-05-26 Cont ID  
Sent By rmcphers Date 2022-05-26 Time 08:21 Rev Time 0.00
Received By rmcphers Date 2022-05-26 Time 08:21 Sent To  
Notes
2022-05-26 08:22:35PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-07-22 Cont ID  
Sent By medwards Date 2022-07-22 Time 13:27 Rev Time 0.00
Received By medwards Date 2022-07-22 Time 13:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-07-05 Cont ID  
Sent By medwards Date 2022-07-05 Time 11:51 Rev Time 0.00
Received By medwards Date 2022-07-05 Time 11:51 Sent To  
Notes
2022-07-05 11:51:532ND REVIEW FMC
 PERMIT: 22040494
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGY CALCULATIONS WERE NOT IN THE RESUBMITTED
 DOCUMENTS. PROVIDE THE ENERGY CALCULATIONS. FEC
 101.5.1.1.2
  
 2) REVISE THE DRAWING TO SHOW THE REQUIRED BATH EXHAUST
 FAN IN THE MASTER SHOWER AREA. FRC R303.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-05-02 Cont ID  
Sent By medwards Date 2022-05-02 Time 09:32 Rev Time 0.00
Received By medwards Date 2022-05-02 Time 09:32 Sent To  
Notes
2022-05-02 09:32:361ST REVIEW FMC
 PERMIT: 22040494
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS. FEC
 101.5.1.1.2
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC R403.7.1
  
 3) PLEASE SHOW THE BATH EXHAUST FANS AND THE EXHAUST
 TERMINATION LOCATION FOR EACH. FRC M1507.4
  
 4) PLEASE SHOW THE DRYER DUCT SIZE, MATERIAL AND
 TERMINATION LOCATION. FRC M1502.3
  
 5) PLEASE PROVIDE A DETAIL DRAWING OF THE OUTDOOR
 APPLIANCE ANCHORING. FRC M1307.2
  
 6) PLEASE SHOW THE CONDENSATE PIPE SIZE, MATERIAL AND
 TERMINATION LOCATION. FRC M1411.3
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-07-22 Cont ID  
Sent By rwbrown Date 2022-07-22 Time 08:17 Rev Time 0.00
Received By rwbrown Date 2022-07-22 Time 08:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-07-05 Cont ID  
Sent By rwbrown Date 2022-07-05 Time 06:21 Rev Time 0.00
Received By rwbrown Date 2022-07-05 Time 06:21 Sent To  
Notes
2022-07-05 06:34:282ND PLUMBING REVIEW
  
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. SHEET A-5 - BATHROOM NEAR CLUB ROOM - 2020 FRC
 P3108.1 - THE BAR SINK IN THE CLUB ROOM SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT SYSTEM. ONLY BATHROOM GROUP
 FIXTURES ARE ALLOWED TO DISCHARGE WITHIN THE WET VENT.
 ALL OTHER FIXTURES MUST DISCHARGE DOWNSTREAM OF THE WET
 VENT SYSTEM. PLEASE RECONFIGURE AND RESUBMIT.
 CORRECTIONS DO NOT COMPLY. THE BAR SINK MUST DISCHARGE
 DOWNSTREAM OF THE SHOWER IN ORDER TO "WET VENT" THE
 SHOWER AND/OR WATER CLOSET.
  
  
 2. DONE
  
 3. DONE
  
 4. SHEET A-5 - POWDER BATH - 2020 FRC P3108.1 - THE
 LAUNDRY TUB AND THE AUTOMATIC CLOTHES WASHER ARE
 DISHCHARGING INTO THE WET VENT FOR THE POWDER BATH.
 ONLY BATHROOM GROUP FIXTURES ARE ALLOWED TO DISCHARGE
 WITHIN THE WET VENT. ALL OTHER FIXTURES MUST DISCHARGE
 DOWNSTREAM OF THE WET VENT SYSTEM. PLEASE RECONFIGURE
 AND RESUBMIT.
 CORRECTIONS DO NOT COMPLY. - WATER CLOSET IS STILL
 BEING VENTED BY LAUNDRY TUB, WASHER AND BAR SINK. ONLY
 BATHROOM GROUP FIXTURES CAN BE INCLUDED IN THE WET VENT
 FOR OTHER BATHROOM GROUP FIXTURES. ALSO, LOOP VENT IS
 MIS-LABELED. THIS IS NOT A LOOP VENT, BUT RATHER A
 BRANCH VENT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-04-25 Cont ID  
Sent By rwbrown Date 2022-04-25 Time 13:34 Rev Time 0.00
Received By rwbrown Date 2022-04-25 Time 13:15 Sent To  
Notes
2022-04-25 13:34:361ST PLUMBING REVIEW
  
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. SHEET A-5 - BATHROOM NEAR CLUB ROOM - 2020 FRC
 P3108.1 - THE BAR SINK IN THE CLUB ROOM SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT SYSTEM. ONLY BATHROOM GROUP
 FIXTURES ARE ALLOWED TO DISCHARGE WITHIN THE WET VENT.
 ALL OTHER FIXTURES MUST DISCHARGE DOWNSTREAM OF THE WET
 VENT SYSTEM. PLEASE RECONFIGURE AND RESUBMIT.
  
 2. SHEET A-5 - BATHROOM BETWEEN BDRM 2 AND BDRM 3 -
 2020 FRC P3108.2.1 - THE TUB AND WATER CLOSET ARE BOTH
 UPSTREAM OF THE VENTED FIXTURE CONNECTION. NOT MORE
 THAN ONE WET VENTED FIXTURE DRAIN CAN DISCHARGE
 UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN CONNECTION.
 PLEASE RECONFIGURE AND RESUBMIT.
  
 3. SHEET A-5 - MASTER BATH - 2020 FRC P3108.1 - TWO
 SHOWER TRAPS AND THE WATER CLOSET ARE BOTH UPSTREAM OF
 THE VENTED FIXTURE CONNECTION. NOT MORE THAN ONE WET
 VENTED FIXTURE DRAIN CAN DISCHARGE UPSTREAM OF THE
 DRY-VENTED FIXTURE DRAIN CONNECTION. PLEASE RECONFIGURE
 AND RESUBMIT.
  
 4. SHEET A-5 - POWDER BATH - 2020 FRC P3108.1 - THE
 LAUNDRY TUB AND THE AUTOMATIC CLOTHES WASHER ARE
 DISHCHARGING INTO THE WET VENT FOR THE POWDER BATH.
 ONLY BATHROOM GROUP FIXTURES ARE ALLOWED TO DISCHARGE
 WITHIN THE WET VENT. ALL OTHER FIXTURES MUST DISCHARGE
 DOWNSTREAM OF THE WET VENT SYSTEM. PLEASE RECONFIGURE
 AND RESUBMIT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2022-07-08 Cont ID  
Sent By rmcphers Date 2022-07-08 Time 14:25 Rev Time 0.00
Received By rmcphers Date 2022-07-08 Time 14:25 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-05-26 Cont ID  
Sent By rmcphers Date 2022-05-26 Time 08:22 Rev Time 0.00
Received By rmcphers Date 2022-05-26 Time 08:22 Sent To  
Notes
2022-05-26 08:23:05SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-07-22 Cont ID  
Sent By rwbrown Date 2022-07-22 Time 08:14 Rev Time 0.00
Received By rwbrown Date 2022-07-22 Time 08:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-07-08 Cont ID  
Sent By rmcphers Date 2022-07-08 Time 14:30 Rev Time 0.00
Received By rmcphers Date 2022-07-08 Time 14:30 Sent To  
Notes
2022-07-08 14:30:52DRAWING C1 DOES NOT SHOW AS ELECTRONICALLY SIGNED -
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-05-26 Cont ID  
Sent By rmcphers Date 2022-05-26 Time 08:28 Rev Time 0.00
Received By rmcphers Date 2022-05-26 Time 08:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-07-08 Cont ID  
Sent By afowlkes Date 2022-07-08 Time 09:27 Rev Time 0.00
Received By afowlkes Date 2022-07-08 Time 09:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-04-18 Cont ID  
Sent By afowlkes Date 2022-04-18 Time 15:11 Rev Time 0.00
Received By afowlkes Date 2022-04-18 Time 15:10 Sent To  
Notes
2022-04-18 15:11:4604/18/21 - SEE MARKUPS ON SITE PLAN, NEED TO KNOW HOW
 FAR THE MECHANICAL EQUIPMENT EXTENDS INTO THE SETBACKS