Plan Review Details - Permit 22040360
Plan Review Stops For Permit 22040360 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2022-12-15 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2022-12-15 |
Time |
19:07 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2022-12-14 |
Time |
21:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2022-05-25 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2022-05-25 |
Time |
23:34 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2022-05-25 |
Time |
21:35 |
Sent To |
|
|
Notes |
2022-05-25 23:33:44 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE RISER DIAGRAM OF EXISTING SERVICE AND | | GENERATOR FEEDERS, SHOWING WIRE SIZES, OCP, AND | | LOCATION OF GENERATOR. FBC 107.2.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-805-6744 | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2022-12-07 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2022-12-07 |
Time |
|
Rev Time |
0.00 |
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2022-05-04 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2022-05-04 |
Time |
|
Rev Time |
|
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2022-05-04 11:00:14 | FIRE COMMENTS: | | (1) PROVIDE A SITE PLAN FOR VERIFICATION OF THE | | GENERATOR LOCATION. NFPA 1, 1.14, NFPA 110 7.1.1 | | (2) PROVIDE MOUNTING DETAILS. NFPA 110 7.4 | | C. WALKER, SENIOR FIRE INSPECTOR | | 561-804-4762 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-12-15 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2022-12-15 |
Time |
19:07 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2022-12-06 |
Time |
15:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-05-25 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2022-05-25 |
Time |
23:36 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2022-05-04 |
Time |
05:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2022-12-15 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2022-12-15 |
Time |
19:07 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2022-05-25 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2022-05-25 |
Time |
23:36 |
Rev Time |
|
Received By |
fgiaquin |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2022-05-25 23:36:32 | WHEN PLANS ARE SUBMITTED MUST BE DESIGNED AND DIGITALLY | | SIGNED BY A DESIGN PROFESSIONAL. VALUE OF PROJECT IS | | OVER $125,000. FS 471.003(2)(H); 471.025; WPB FBC 107.1 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2022-12-14 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2022-12-14 |
Time |
10:10 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2022-12-14 |
Time |
10:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2022-05-10 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2022-05-10 |
Time |
15:11 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2022-05-10 |
Time |
15:11 |
Sent To |
|
|
Notes |
2022-05-10 15:12:58 | 5/10/2022 FAILED | | | | PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR: | | MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET | | INTO A REQUIRED SETBACK. WINDOW AIR-CONDITIONING UNITS | | MAY NOT PROJECT MORE THAN 18 INCHES INTO A REQUIRED | | SIDE SETBACK. | | | | PLEASE PROVIDE A SITE PLAN OR SURVAY THAT DEMONSTRATES | | THE PROPERTY LINES, LOCATION OF GENERATOR AND DISTANCES | | FORM THE LOT LINES | | | | VALENTINA BROGLIA | | ASSOCIATE PLANNER | | [email protected] | | |
|
|
|