2022-04-11 11:09:12 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected]. |
| |
| 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R35 |
| (HVHZ) COVERS MULTIPLE PRODUCT TYPES; ROOF COVER |
| OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE |
| COMBINATIONS, ALLOWABLE SUBSTRATES, ATTACHMENT |
| LIMITATIONS & INSTALLATION APPROVED ASSEMBLIES. SELECT; |
| ROOF COVER OPTIONS TABLE 1 PAGE #4, ALLOWABLE |
| UNDERLAYMENT/TILE-ADHESIVE COMBINATIONS TABLE 1A PAGE |
| #4, ALLOWABLE SUBSTRATES TABLE 2 PAGE #5 & |
| INSTALLATION: APPROVED ASSEMBLIES PAGES #6-#11. (OPTION |
| USE FL5259-R35 NON-HVHZ) |
| 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL14826-R6 COVERS MULTIPLE DESIGN PRESSURE |
| RATINGS. PLEASE SELECT CORRECT PLYWOOD SPECIES GROUP, |
| ANCHOR QUANTITY PAGE #1 OF THE INSTALLATION |
| INSTRUCTIONS THAT MEET OR EXCEED THE MINIMUM DESIGN |
| PRESSURE REQUIREMENT FOR ZONE 3 EXPOSURE CATEGORY C |
| AREAS. (-121.). ALL APPLICABLE DETAILS AND ATTACHMENTS |
| MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY |
| COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC |
| ENGINEERING |
| 3. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF |
| DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING |
| CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S), |
| MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW |
| POSITIVE DRAINAGE. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| |