Plan Review Details - Permit 22040242
Plan Review Stops For Permit 22040242
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-12-02 Cont ID  
Sent By rmcdouga Date 2022-12-02 Time 15:52 Rev Time 0.00
Received By rmcdouga Date 2022-12-02 Time 15:52 Sent To  
Notes
2022-12-02 15:53:53APPROVAL FOR WATERFALL FOUNTAIN ONLY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-06-22 Cont ID  
Sent By rmcdouga Date 2022-06-22 Time 08:34 Rev Time 0.00
Received By rmcdouga Date 2022-06-22 Time 07:38 Sent To  
Notes
2022-06-22 08:37:29PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE LOCATION OF THE WATER WALL FOUNTAIN IS NOT
 CLEARLY IDENTIFIED ON THE SITE PLAN. FBC 107.2.1

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2023-03-20 Cont ID  
Sent By jleahy Date 2023-03-20 Time 12:19 Rev Time 0.00
Received By jleahy Date 2023-03-20 Time 12:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-03-13 Cont ID  
Sent By jleahy Date 2023-03-13 Time 14:07 Rev Time 0.00
Received By jleahy Date 2023-03-13 Time 13:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-12-02 Cont ID  
Sent By jleahy Date 2022-12-02 Time 08:10 Rev Time 0.00
Received By jleahy Date 2022-12-02 Time 07:50 Sent To  
Notes
2022-12-02 08:12:41FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE SUBMIT A PLAN SHOWING THE SIZE OF THE CONDUCTORS
 AND PROTECTION FOR ALL PUMPS AND LIGHTS.
  
 PROVIDE CUT SHEETS FOR LIGHTS AND/OR TRANSFORMER.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-05-06 Cont ID  
Sent By jleahy Date 2022-05-06 Time 16:25 Rev Time 0.00
Received By jleahy Date 2022-05-06 Time 16:15 Sent To  
Notes
2022-05-06 16:26:45FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRICAL CONNECTION, CIRCUITS, BREAKERS OR WIRES
 SIZES SHOWN JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 4 Status P Date 2023-03-20 Cont ID  
Sent By jleahy Date 2023-03-20 Time 12:19 Rev Time 0.00
Received By jleahy Date 2023-03-15 Time 16:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-03-13 Cont ID  
Sent By jleahy Date 2023-03-13 Time 14:07 Rev Time 0.00
Received By jleahy Date 2023-03-02 Time 16:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-07 Cont ID  
Sent By cpuell Date 2022-12-07 Time 10:43 Rev Time 0.00
Received By cpuell Date 2022-11-08 Time 09:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-22 Cont ID  
Sent By rmcdouga Date 2022-06-22 Time 08:37 Rev Time 0.00
Received By rmcdouga Date 2022-04-14 Time 07:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2023-03-17 Cont ID  
Sent By ccole Date 2023-03-17 Time 15:51 Rev Time 0.00
Received By ccole Date 2023-03-17 Time 15:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-03-03 Cont ID  
Sent By ccole Date 2023-03-03 Time 11:03 Rev Time 0.00
Received By ccole Date 2023-03-03 Time 10:35 Sent To  
Notes
2023-03-03 11:03:523RD REVIEW FBC-2020 PLUMBING
 PERMIT- 22040242
 3/3/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 1) IN RESPONSE TO 1ST REVIEW COMMENT #2 BELOW, THE
 ARCHITECT???S NARRATIVE CALLS OUT SHEET PL0.24 HOWEVER
 IT WAS NOT UPLOADED FOR REVIEW. PLEASE PROVIDE THE PLAN
 SHEET- SEC. 107.2.1 WPB.
  
 2) PL0.25: SHOW THE TRENCH AND PIPING ROUTE FOR THE
 WATER FALL FOUNTAIN- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-11-17 Cont ID  
Sent By ccole Date 2022-11-17 Time 14:22 Rev Time 0.00
Received By ccole Date 2022-11-17 Time 14:07 Sent To  
Notes
2022-11-17 14:26:042ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22040242
 11/17/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW. 2ND REQUEST TO PLEASE
 COMPLY OR SUBMIT A RESPONSE TO CLARIFY.
  
  
 2) PL0.25: SHOW THE TRENCH AND PIPING ROUTE FOR THE
 WATER FALL FOUNTAIN- SEC. 107.2.1 WPB.
  
 4) PL7.15: THE PLAN INDICATES POOL WASTE LINE TO
 NEAREST AUTHORIZED OUTFALL. PLEASE SHOW THE WASTEWATER
 PIPING RUN AND DISPOSAL LOCATION. CONCERNING DISPOSAL
 OF POOL WASETWATER PLEASE NOTE THE FOLLOWING
 REQUIREMENTS:
 WASTEWATER SHALL BE DECHLORINATED AND DISCHARGED
 THROUGH AN AIR GAP IN THE INTO THE STORM DRAINAGE
 SYSTEM- SEC. 454.1.6.5.15 & SEC. 90-126(5) WPB CODE OF
 ORDINANCES. THE WASTEWATER SHALL NOT DISCHARGE INTO THE
 SANITARY SYSTEM. PLEASE REVIEW WPB BUILDING DEPT.
 GUIDELINES FOR POOL WATER DISPOSAL. THE ENGINEER OF
 RECORD SHALL SHOW THE DECHLORINATION SYSTEM ON THE PLAN
 AND PROVIDE SPECIFICATIONS FOR ALL EQUIPMENT. PLEASE
 SEE GUIDELINES BELOW-
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
  
 A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL
 OWNER'S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 E) FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS,
 PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 5) PL7.15: SHOW THE SOURCE OF WATER SUPPLY TO THE
 FOUNTAIN- SEC. 107.2.1 WPB. IF CONNECTED TO THE POTABLE
 WATER SERVICE BACKFLOW PROTECTION IS REQUIRED PER THE
 CITY OF WEST PALM BEACH UTILITIES CROSS-CONNECTION
 MANUAL. A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN
 A SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC.
 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 6) PL7.15: PROVIDE A CLEANING SYSTEM FOR THE WATERFALL
 FOUNTAIN- SEC. 107.2.1 WPB.
  
 7) PL7.15: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 RECIRCULATION AND TREATMENT EQUIPMENT INCLUDING THE
 PUMPS, FILTERS, CHEMICAL FEEDERS, AND DRAIN ASSEMBLIES-
 SEC. 107.2.1 WPB. PLEASE NOTE THE SPECS CAN BE DEFERRED
 SUBMITTALS IN ACCORDANCE WITH SEC. 107.3.4.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-04-27 Cont ID  
Sent By ccole Date 2022-04-27 Time 10:10 Rev Time 0.00
Received By ccole Date 2022-04-27 Time 07:57 Sent To  
Notes
2022-04-27 10:12:501ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22040242
 4/27/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS PL0.20 & PL0.26: PLEASE IDENTIFY THE LOCATION
 OF THE WATER FALL FOUNTAIN- SEC. 107.2.1 WPB.
  
 2) PL0.25: SHOW THE TRENCH AND PIPING ROUTE FOR THE
 WATER FALL FOUNTAIN- SEC. 107.2.1 WPB.
  
 3) PL0.20: THE PLANS APPEAR TO INDICATE THE WATER
 FOUNTAIN IS NOT FOR BATHING. PLEASE CLARIFY IF SIGNAGE
 WILL BE PROVIDED AT THE FOUNTAIN TO IDENTIFY THE USE
 AND RESTRICT BATHERS FROM OCCUPYING THE FOUNTAIN- SEC.
 107.2.1 WPB AND SEC. 454.1.2.3.5 FBC B.
  
 4) PL7.15: THE PLAN INDICATES POOL WASTE LINE TO
 NEAREST AUTHORIZED OUTFALL. PLEASE SHOW THE WASTEWATER
 PIPING RUN AND DISPOSAL LOCATION. CONCERNING DISPOSAL
 OF POOL WASETWATER PLEASE NOTE THE FOLLOWING
 REQUIREMENTS:
 WASTEWATER SHALL BE DECHLORINATED AND DISCHARGED
 THROUGH AN AIR GAP IN THE INTO THE STORM DRAINAGE
 SYSTEM- SEC. 454.1.6.5.15 & SEC. 90-126(5) WPB CODE OF
 ORDINANCES. THE WASTEWATER SHALL NOT DISCHARGE INTO THE
 SANITARY SYSTEM. PLEASE REVIEW WPB BUILDING DEPT.
 GUIDELINES FOR POOL WATER DISPOSAL. THE ENGINEER OF
 RECORD SHALL SHOW THE DECHLORINATION SYSTEM ON THE PLAN
 AND PROVIDE SPECIFICATIONS FOR ALL EQUIPMENT. PLEASE
 SEE GUIDELINES BELOW-
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
  
 A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL
 OWNER'S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 E) FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS,
 PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 5) PL7.15: SHOW THE SOURCE OF WATER SUPPLY TO THE
 FOUNTAIN- SEC. 107.2.1 WPB. IF CONNECTED TO THE POTABLE
 WATER SERVICE BACKFLOW PROTECTION IS REQUIRED PER THE
 CITY OF WEST PALM BEACH UTILITIES CROSS-CONNECTION
 MANUAL. A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN
 A SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC.
 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 6) PL7.15: PROVIDE A CLEANING SYSTEM FOR THE WATERFALL
 FOUNTAIN- SEC. 107.2.1 WPB.
  
 7) PL7.15: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 RECIRCULATION AND TREATMENT EQUIPMENT INCLUDING THE
 PUMPS, FILTERS, CHEMICAL FEEDERS, AND DRAIN ASSEMBLIES-
 SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-04-15 Cont ID  
Sent By shill Date 2022-04-15 Time 07:05 Rev Time 0.00
Received By shill Date 2022-04-15 Time 07:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-03-17 Cont ID  
Sent By ccole Date 2023-03-17 Time 15:51 Rev Time 0.00
Received By ccole Date 2023-03-17 Time 15:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-03-03 Cont ID  
Sent By ccole Date 2023-03-03 Time 11:04 Rev Time 0.00
Received By ccole Date 2023-03-03 Time 10:35 Sent To  
Notes
2023-03-03 11:11:43SIGNATURE REVIEW
 PERMIT- 22040242
 8/10/2022
  
 1) SHEETS E0.00, 55.06, P2.01S, AND C6.00 ARE NOT
 DIGITALLY SIGNED AND SEALED BY THE ENGINEERS OF RECORD-
 FL. STATUTE 471.025 AND SEC. 61G15-23.005 FLORIDA
 ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-17 Cont ID  
Sent By ccole Date 2022-11-17 Time 14:48 Rev Time 0.00
Received By ccole Date 2022-11-17 Time 14:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-22 Cont ID  
Sent By rmcdouga Date 2022-06-22 Time 07:39 Rev Time 0.00
Received By rmcdouga Date 2022-06-22 Time 07:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-12-07 Cont ID  
Sent By jroach Date 2022-12-07 Time 08:15 Rev Time 0.00
Received By jroach Date 2022-12-07 Time 08:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-05-19 Cont ID  
Sent By jroach Date 2022-05-19 Time 09:34 Rev Time 0.00
Received By jroach Date 2022-05-19 Time 09:33 Sent To  
Notes
2022-05-19 09:34:11ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 2022.05.19
 PERMIT NO.: 22040242
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. SITE PLAN SHALL CLEARLY IDENTIFY THE LOCATION OF THE
 PROPOSED SCOPE OF WORK. THE DESCRIPTION INDICATES THAT
 THE PERMIT IS FOR A WATERWALL, BUT THE SITE PLAN
 PROVIDED DOES NOT INDICATE THE LOCATION OF SUCH. PLEASE
 CLEARLY IDENTIFY AND LABEL THE AREA OF WORK THAT IS TO
 BE COVERED UNDER THIS PERMIT.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved