Plan Review Details - Permit 22031379
Plan Review Stops For Permit 22031379
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-08-22 Cont ID  
Sent By cthroop Date 2022-08-22 Time 08:42 Rev Time 0.00
Received By cthroop Date 2022-08-22 Time 06:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-07-27 Cont ID  
Sent By cthroop Date 2022-07-27 Time 07:14 Rev Time 0.00
Received By cthroop Date 2022-07-27 Time 06:07 Sent To  
Notes
2022-07-27 07:15:49DEFERRAL ON COVER PAGE: SUBMIT WINDOW AND DOOR PRODUCT
 APPROVALS AND ICC-ES REPORT FOR REVIEW AND APPROVAL
 PRIOR TO INSTALLATION. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-25 Cont ID  
Sent By cthroop Date 2022-05-25 Time 14:52 Rev Time 0.00
Received By cthroop Date 2022-05-16 Time 10:10 Sent To  
Notes
2022-05-25 14:57:02PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT
 APPROVAL, APPROVED UNDER THE 2020 FBC, FOR THE PROPOSED
 WINDOWS AND DOORS TO BE INSTALLED.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 2. PROVIDE THE ICC-ES REPORT FOR THE SPRAY APPLIED FOAM
 INSULATION.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 3. PLACE THE INSULATION TYPE AND R VALUE ON THE PLANS.
 R401.2COMPLIANCE.
 PROJECTS SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1. 1.SECTIONS R401 THROUGH R404.
 2. 2.SECTION R405 AND THE PROVISIONS OF SECTIONS R401
 THROUGH R404 LABELED ?MANDATORY.?
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-08-15 Cont ID  
Sent By jleahy Date 2022-08-15 Time 11:09 Rev Time 0.00
Received By jleahy Date 2022-08-15 Time 09:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2022-08-04 Cont ID  
Sent By mpeterso Date 2022-08-04 Time 13:13 Rev Time 0.00
Received By mpeterso Date 2022-08-04 Time 13:13 Sent To  
Notes
2022-08-04 13:13:49SEE SIGNATURE REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-06-27 Cont ID  
Sent By mpeterso Date 2022-06-27 Time 15:28 Rev Time 0.00
Received By mpeterso Date 2022-06-27 Time 15:28 Sent To  
Notes
2022-06-27 15:28:58SEE SIGNATURE REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-04-19 Cont ID  
Sent By mpeterso Date 2022-04-19 Time 09:43 Rev Time 0.00
Received By mpeterso Date 2022-04-19 Time 09:42 Sent To  
Notes
2022-04-19 09:51:48ELECTRIC REVIEW FAILED
 1) PLEASE CORRECT PLAN DESCRIPTION FOR SHEET E3.1 TO
 DELETE PANEL SCHEDULES, AND, CORRECT PLAN DESCRIPTION
 FOR SHEET E4.1 TO STATE PANEL SCHEDULES. FBC 107.2
 2) PLEASE INCLUDE A NOTE STATING POOLS,GENERATORS AND
 LOW VOLTAGE WIRING REQUIRE A SEPERATE PERMIT
 3) PLEASE DETAIL ON DRAWINGS INDICATING WHAT THE GREYED
 OUT AREAS ON ELECTRICAL FLOOR PLANS DESCRIBES . FBS
 107.2
 4) PLEASE HAVE THE ENGINEER/ ARCHITECT OF RECORD SIGN
 AND SEAL ALL DRAWINGS AS REQUIRED.FS471/FS481
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2022-04-19 Cont ID  
Sent By mpeterso Date 2022-04-19 Time 09:51 Rev Time 0.00
Received By mpeterso Date 2022-04-19 Time 09:51 Sent To  
Notes
2022-04-19 09:54:24PASSED LOW VOLTAGE FOR TVS AND TELEPHONE WIRING ONLY

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-08-01 Cont ID  
Sent By rwbrown Date 2022-08-01 Time 06:05 Rev Time 0.00
Received By rwbrown Date 2022-08-01 Time 06:04 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2022-04-04 Cont ID  
Sent By lcrespo Date 2022-04-04 Time 12:27 Rev Time 0.00
Received By lcrespo Date 2022-04-04 Time 11:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-08-22 Cont ID  
Sent By cthroop Date 2022-08-22 Time 08:42 Rev Time 0.00
Received By cthroop Date 2022-08-06 Time 07:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-05 Cont ID  
Sent By aoliver Date 2022-08-05 Time 07:16 Rev Time 0.00
Received By aoliver Date 2022-07-29 Time 08:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-27 Cont ID  
Sent By cthroop Date 2022-07-27 Time 07:15 Rev Time 0.00
Received By cthroop Date 2022-06-16 Time 14:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-25 Cont ID  
Sent By cthroop Date 2022-05-25 Time 14:57 Rev Time 0.00
Received By cthroop Date 2022-04-01 Time 10:52 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-08-08 Cont ID  
Sent By lmarchan Date 2022-08-08 Time 13:38 Rev Time 0.00
Received By lmarchan Date 2022-08-01 Time 12:45 Sent To  
Notes
2022-08-08 13:38:51RECEIPT MU-2022-036106 - $0.00 DUE
2022-08-01 12:45:288/01/22 EMAILED IMPACT FOR REVIEW-AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-05-25 Cont ID  
Sent By cthroop Date 2022-05-25 Time 10:22 Rev Time 0.00
Received By cthroop Date 2022-05-25 Time 10:21 Sent To  
Notes
2022-05-25 10:22:53IMPACT FEE QUESTIONNAIRE
  
 PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT
 LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO
 THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF.
 THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ
 B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
 UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE
 RECEIPT TO PROJECT DOX OR EMAIL IT TO
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-08-02 Cont ID  
Sent By hmoser Date 2022-08-02 Time 09:00 Rev Time 0.00
Received By hmoser Date 2022-08-02 Time 09:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-06-17 Cont ID  
Sent By medwards Date 2022-06-17 Time 07:53 Rev Time 0.00
Received By medwards Date 2022-06-17 Time 07:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-04-08 Cont ID  
Sent By medwards Date 2022-04-08 Time 16:28 Rev Time 0.00
Received By medwards Date 2022-04-08 Time 16:28 Sent To  
Notes
2022-04-08 16:29:061ST REVIEW FMC
 PERMIT: 22031379
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) KEYNOTE 5 IS FOR A MOTORIZED BACKDRAFT DAMPER IN AN
 ACCESSIBLE LOCATION. PLEASE VERIFY THAT THIS
 INSTALLATION WILL MEET FRC M1502.3 AND BE INSTALLED AT
 THE DUCT TERMINATION LOCATION. A BACKDRAFT DAMPER SHALL
 NOT BE INSTALLED IN THE DRYER DUCT SYSTEM.
  
 2) PLEASE SHOW THE CONDENSATION DRAIN AND TERMINATION
 LOCATION. FRC M1411.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-08-01 Cont ID  
Sent By rwbrown Date 2022-08-01 Time 06:04 Rev Time 0.00
Received By rwbrown Date 2022-08-01 Time 06:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-04-04 Cont ID  
Sent By lcrespo Date 2022-04-04 Time 12:27 Rev Time 0.00
Received By lcrespo Date 2022-04-04 Time 11:59 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2022-05-25 Cont ID  
Sent By cthroop Date 2022-05-25 Time 14:29 Rev Time 0.00
Received By cthroop Date 2022-05-25 Time 14:29 Sent To  
Notes
2022-05-25 14:30:09PROVISO ON PLAN PAGE A2.1: A SEPERATE ROOFING PERMIT IS
 REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-08-15 Cont ID  
Sent By jleahy Date 2022-08-15 Time 11:09 Rev Time 0.00
Received By jleahy Date 2022-08-15 Time 10:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-08-04 Cont ID  
Sent By mpeterso Date 2022-08-04 Time 13:13 Rev Time 0.00
Received By mpeterso Date 2022-08-04 Time 13:13 Sent To  
Notes
2022-08-04 13:17:09SIGNATURE REVIEW FAILED
 1) ALL PLANS TITLED WITH A DO NOT HAVE THE REQUIRED
 SEAL AND SIGNATURE
  
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-06-27 Cont ID  
Sent By mpeterso Date 2022-06-27 Time 15:29 Rev Time 0.00
Received By mpeterso Date 2022-06-27 Time 15:29 Sent To  
Notes
2022-06-27 15:31:08SIGNATURE REVIEW FAILED
 ALL PLANS DO NOT SHOW THE REQUIRED SEAL AND SIGNATURE
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-05-25 Cont ID  
Sent By cthroop Date 2022-05-25 Time 10:55 Rev Time 0.00
Received By cthroop Date 2022-05-16 Time 10:10 Sent To  
Notes
2022-05-25 10:57:17SIGNATURE REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 1ST REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  
2022-04-08 16:30:15MECHANICAL DOCUMENT SHOULD BE DIGITALLY SIGNED BY THE
 DESIGNER. ME

Review Stop Z ZONING
Rev No 3 Status P Date 2022-08-15 Cont ID  
Sent By asangele Date 2022-08-15 Time   Rev Time 0.00
Received By asangele Date 2022-08-15 Time 16:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-06-27 Cont ID  
Sent By asangele Date 2022-06-27 Time 13:17 Rev Time 0.00
Received By asangele Date 2022-06-27 Time 13:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-04-11 Cont ID  
Sent By asangele Date 2022-04-11 Time 14:18 Rev Time 0.00
Received By asangele Date 2022-04-11 Time 14:18 Sent To  
Notes
2022-04-11 14:27:174/11/2022
 FAILED
 * PLEASE SHOW BUIDLING HEIGHT ON THE ELEVATION SITE MAP
 HEIGHT IS MEASURE FROM FINISHED FLOOR GRADE CANNOT
 EXCEED 30FT IN HEIGHT.
 SEPARATE PERMIT REQUIRED FOR: (POOL/POOL DECK, POOL
 EQUIPMENT,DRIVEWAY/WALKWAY)
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]
  