Plan Review Details - Permit 22030923
Plan Review Stops For Permit 22030923
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2022-04-18 Cont ID  
Sent By rmcphers Date 2022-04-18 Time 11:53 Rev Time 0.00
Received By rmcphers Date 2022-04-18 Time 11:53 Sent To  
Notes
2022-04-18 11:54:08NO DEMO

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-04-18 Cont ID  
Sent By rmcphers Date 2022-04-18 Time 11:54 Rev Time 0.00
Received By rmcphers Date 2022-04-18 Time 11:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-04-09 Cont ID  
Sent By fgiaquin Date 2022-04-09 Time 23:24 Rev Time 0.00
Received By fgiaquin Date 2022-04-09 Time 22:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-03-21 Cont ID  
Sent By   Date 2022-03-21 Time   Rev Time 0.00
Received By bdolan Date 2022-03-21 Time 10:58 Sent To  
Notes
2022-03-21 11:05:28CONSTRUCTION OF DEMISING WALL MAY IMPACT EXISITING
 SPRINKLER COVERAGE. AN EVALUATION OF SPRINKLER COVERAGE
 MAY BE NECESSARY.
  
 ALL WORK ON THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE
 COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR AND
 SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS, ARE
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE
 FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE SYSTEM.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-26 Cont ID  
Sent By medwards Date 2022-05-26 Time 10:14 Rev Time 0.00
Received By medwards Date 2022-05-22 Time 12:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-18 Cont ID  
Sent By rmcphers Date 2022-04-18 Time 11:55 Rev Time 0.00
Received By rmcphers Date 2022-03-18 Time 05:39 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-04-18 Cont ID  
Sent By rmcphers Date 2022-04-18 Time 11:54 Rev Time 0.00
Received By rmcphers Date 2022-04-18 Time 11:54 Sent To  
Notes
2022-04-18 11:54:57NO CHANGE OF OCCUPANCY - NO ADDED SQUARE FOOTAGE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-05-26 Cont ID  
Sent By medwards Date 2022-05-26 Time 10:12 Rev Time 0.00
Received By medwards Date 2022-05-26 Time 10:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-04-04 Cont ID  
Sent By medwards Date 2022-04-04 Time 15:34 Rev Time 0.00
Received By medwards Date 2022-04-04 Time 14:37 Sent To  
Notes
2022-04-04 15:34:461ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22030923
  
 CODES IN EFFECT:
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL SYSTEMS MUST BE SEPARATED FOR EACH
 TENANT SPACE.
  
 2) PLEASE PROVIDE A MECHANICAL EQUIPMENT SIZING
 CALCULATION FOR THIS NEW SMALLER TENANT SPACE. FEC
 C403.2.1
  
 3) THE MECHANICAL SYSTEMS SERVING THE PET LIFE TENANT
 CANNOT PENETRATE THE NEWLY INSTALLED 1 HOUR RATED
 TENANT SEPARATION WALL WITHOUT INSTALLING DAMPERS.
 PLEASE PROVIDE AN UPDATED MECHANICAL DRAWING SHOWING
 THIS. FBC 107.2.1
  
 4) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS
 DOWNSIZED TENANT SPACE. FMC 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-03-29 Cont ID  
Sent By rwbrown Date 2022-03-29 Time 11:13 Rev Time 0.00
Received By rwbrown Date 2022-03-29 Time 11:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-26 Cont ID  
Sent By medwards Date 2022-05-26 Time 10:14 Rev Time 0.00
Received By medwards Date 2022-05-26 Time 10:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-04-18 Cont ID  
Sent By rmcphers Date 2022-04-18 Time 11:55 Rev Time 0.00
Received By rmcphers Date 2022-04-18 Time 11:55 Sent To  
Notes
2022-04-04 15:35:56MECHANICAL DIGITAL SIGNATURE APPROVED ME