|
 |
 |
 |
 |
 |
Plan Review Details - Permit 22030621
Plan Review Stops For Permit 22030621 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2022-08-04 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-08-04 |
Time |
14:32 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-08-04 |
Time |
14:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-07-01 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-07-01 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-07-01 |
Time |
13:57 |
Sent To |
|
|
Notes |
2022-07-01 14:05:45 | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | FBC B 107.2.1, PLEASE ADJUST THE LAYOUT SHEET TO | | INDICATE SPECIFICALLY THE LOCATION OF THE PROPOSED | | SHUTTERED OPENING. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-08-04 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-08-04 |
Time |
14:36 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-07-13 |
Time |
06:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-07-01 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-07-01 |
Time |
14:26 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-05-04 |
Time |
07:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2022-08-04 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-08-04 |
Time |
14:32 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-08-04 |
Time |
14:25 |
Sent To |
|
|
Notes |
2022-08-04 14:34:34 | SIGNATURE REVIEW DENIED: | | | | THE CALCULATIONS SHEET THAT WAS SUBMITTED DOES NOT | | INDICATE THAT THE DESIGN PROFESSIONAL'S SIGNATURE/SEAL | | HAS BEEN THIRD PARTY VERIFIED. | | | | FS 471/FS 481 DOCUMENTS PREPARED BY AN | | ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE | | TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A | | SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL. | | UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY | | VERIFIED) PLAN: | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | BUILDING DIVISION | | CITY OF WEST PALM BEACH | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | FEEL FREE TO CONTACT ME AT 561 805 6673. | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2022-07-01 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-07-01 |
Time |
14:26 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-07-01 |
Time |
14:03 |
Sent To |
|
|
Notes |
2022-07-01 14:15:10 | | | SIGNATURE REVIEW DENIED: | | | | THE CALCULATIONS SHEET THAT WAS SUBMITTED DOES NOT | | INDICATE THAT THE DESIGN PROFESSIONAL'S SIGNATURE/SEAL | | HAS BEEN THIRD PARTY VERIFIED. | | | | FS 471/FS 481 DOCUMENTS PREPARED BY AN | | ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE | | TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A | | SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL. | | UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY | | VERIFIED) PLAN: | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | BUILDING DIVISION | | CITY OF WEST PALM BEACH | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | FEEL FREE TO CONTACT ME AT 561 805 6673. | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |