Plan Review Details - Permit 22030401
Plan Review Stops For Permit 22030401
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-25 Cont ID  
Sent By pleduc Date 2022-05-25 Time   Rev Time 0.00
Received By pleduc Date 2022-05-25 Time 12:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-04-07 Cont ID  
Sent By pleduc Date 2022-04-07 Time   Rev Time 0.00
Received By pleduc Date 2022-04-06 Time 13:10 Sent To  
Notes
2022-04-07 11:41:14THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET FP 24 ROOF B - THERE IS AN INDICATION OF A
 HOSE VALVE CONNECTION THAT APPEARS TO BE OBSTRUCTED BY
 A BOXED WALL AREA.
  
 PER NFPA 14
  
 7.3 LOCATIONS OF HOSE CONNECTIONS.
 7.3.1* GENERAL.
 7.3.1.1 HOSE CONNECTIONS AND HOSE STATIONS SHALL BE
 UNOBSTRUCTED AND SHALL BE LOCATED NOT LESS THAN 3 FT
 (0.9 M) OR MORE
 THAN 5 FT (1.5 M) ABOVE THE FLOOR
  
 THE HVC NEEDS TO BE RELOCATED AT LEAST TO THE OTHER
 CORNER OF THE BOXED AREA OR OUT IN FRONT OF THE BOXED
 WALL AREA SO THAT IT IS MORE VISIBLE AND ACCESSIBLE TO
 FD OPERATIONS.
  
 ADDITIONALLY, A FD HOSE CONNECTION SIGN WILL BE
 REQUIRED SO THAT IT CAN BE SEEN FROM ABOVE THE AREA A/C
 EQUIPMENT.
  
 PLEASE CORRECT AND PROVIDE A NOTE FOR THE SIGN ON THE
 PLAN SHEET.
  
  
 2) ANY FIRE LINE UNDERGROUND RELATED TO THIS PERMIT'S
 PROPOSED WORK SHALL BE DONE UNDER SEPARATE PERMIT AND
 SHOP DRAWINGS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A NOTE
 OF ACKNOWLDGMENT ON SHEET FP 3.
  
  
  
  
 3) SHEET FP 1 - WITHIN THE FIRE SPRINKLER HEAD LEGEND
 THERE ARE NO INDICATIONS OF THE TOTAL NUMBER OF EACH
 HEAD TYPE.
  
 THE TOTAL OF THOSE HEADS SHOULD MATCH THE TOTAL FOR THE
 JOB.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 4) SHEET FP 4 L01A - PLEASE REVIEW THE TOTALS FOR THE
 TOTAL THIS SHEET FOR HEADS TY-FRB HSW (5) , TY-FRB HSW
 (3) AS THESE NUMBERS CANNOT BE VERIFIED WITHIN THE
 FLOOR PLAN.
  
 ADDITIONALLY, PLEASE REVIEW THE SIMILAR LEGENDS ON
 OTHER SHEETS FOR THESE HEADS AS THEY ALSO CANNOT BE
 VERIFIED.
  
  
  
 5) SHEET FP 25 - IT COULD NOT BE EASILY IDENTIFIED DUE
 TO THE PLAN SHEET WITH COLORS COMES OUT VERY BLURRY,
 BUT ARE THERE INDICATION OF PRV'S WHERE REQUIRED ON THE
 APPLICABLE FLOORS AND FD HOSE CONNECTIONS?
  
 PLEASE REVIEW AND PROVIDE A NOTE ON THE PLAN SHEET
 EITHER IT WILL BE PROVIDED OR THAT IT WILL NOT WITH
 DETAILS.
  
  
 5A) SHEET FP 25 - THERE IS NO INDICATION OF THE ROOF
 FDHC THAT IS INDICATED ON SHEET FP 24 ROOF B.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE A NOTE OF
 EXPLANATION/CLARIFICATION.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-26 Cont ID  
Sent By lmarchan Date 2022-05-26 Time 09:03 Rev Time 0.00
Received By lmarchan Date 2022-05-22 Time 12:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-08 Cont ID  
Sent By lcrespo Date 2022-04-08 Time 13:38 Rev Time 0.00
Received By lcrespo Date 2022-03-30 Time 13:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-04-08 Cont ID  
Sent By lcrespo Date 2022-04-08 Time 13:36 Rev Time 0.00
Received By lcrespo Date 2022-04-08 Time 13:36 Sent To  
Notes
***NONE***