Plan Review Details - Permit 22030290
Plan Review Stops For Permit 22030290
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-07-15 Cont ID  
Sent By cpuell Date 2022-07-15 Time 16:20 Rev Time 0.00
Received By cpuell Date 2022-07-15 Time 16:20 Sent To  
Notes
2022-07-15 16:21:37APPLICANT UPLOADED NEW PLANS AND APPLICATION FORM 1401
 ELIZABETH AVE

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-05-07 Cont ID  
Sent By cpuell Date 2022-05-07 Time 09:07 Rev Time 0.00
Received By cpuell Date 2022-05-07 Time 09:07 Sent To  
Notes
2022-05-07 09:16:48INCONSISTENCIES WITH THE APPLICATION FORM AND THE
 PLANS, PLANS LIST 1501 ELIZABETH ST APPLICATION FORM
 LIST 1503 ELIZABETH ST. PLEASE CONFIRM THE AREA WHERE
 THE WORK IS TO BE DONE. PLEASE RESPOND TO
 [email protected] OR CALL 561-805-6659.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-08-25 Cont ID  
Sent By rmcphers Date 2022-08-25 Time 09:11 Rev Time 0.00
Received By rmcphers Date 2022-08-25 Time 09:11 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-08-02 Cont ID  
Sent By rmcphers Date 2022-08-02 Time 10:59 Rev Time 0.00
Received By rmcphers Date 2022-08-02 Time 10:59 Sent To  
Notes
2022-08-02 11:00:23PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-05-05 Cont ID  
Sent By rmcphers Date 2022-05-05 Time 15:30 Rev Time 0.00
Received By rmcphers Date 2022-05-05 Time 15:30 Sent To  
Notes
2022-05-05 15:31:38PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-09-16 Cont ID  
Sent By rmcphers Date 2022-09-16 Time 09:59 Rev Time 0.00
Received By rmcphers Date 2022-09-16 Time 09:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-08-25 Cont ID  
Sent By rmcphers Date 2022-08-25 Time 09:52 Rev Time 0.00
Received By rmcphers Date 2022-08-25 Time 09:35 Sent To  
Notes
2022-08-25 09:41:05CREATING 2 UNITS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW STAIR HAND RAIL EXTENSION AT THE BOTTOM
 OF THE STAIRS TO SLOPE PER FBC 1014.6 HANDRAIL
 EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM)
 BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE
 DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER.
  
 2) ACCESSIBLE RESTROOM = PLEASE SHOW THE TOILET PAPER
 DISPENSER DIMENSIONS FROM THE FRONT OF THE TOILET TO
 THE CENTER OF THE TOILET PAPER DISPENSER - FBC A 604.7
 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 3) COMMENT RESPONSE SHOWS THE CORRECTION - PLEASE SHOW
 ON THE DRAWINGS - - PLEASE SHOW THE RAMP EDGE
 PROTECTION (SHOW THE GUARD RAIL BOTTOM RAIL WITHIN 4"
 OF THE RAMP) FBC A 405.9 EDGE PROTECTION.
 EDGE PROTECTION COMPLYING WITH 405.9.1 OR 405.9.2 SHALL
 BE PROVIDED ON EACH SIDE OF RAMP RUNS AND AT EACH SIDE
 OF RAMP LANDINGS. 405.9.2CURB OR BARRIER.
 A CURB OR BARRIER SHALL BE PROVIDED THAT PREVENTS THE
 PASSAGE OF A 4 INCH (100 MM) DIAMETER SPHERE, WHERE ANY
 PORTION OF THE SPHERE IS WITHIN 4 INCHES (100 MM) OF
 THE FINISH FLOOR OR GROUND SURFACE.
  
 4) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR STOREFRONT WINDOWS
 AND DOORS - ALL PRODUCT APPROVALS NEED TO BE REVIEWED
 AND MARKED APPROVED BY THE DESIGNER OF RECORD FBC WPB
 107.3.4
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-02 Cont ID  
Sent By rmcphers Date 2022-08-02 Time 10:59 Rev Time 0.00
Received By rmcphers Date 2022-08-02 Time 10:28 Sent To  
Notes
2022-08-02 10:59:10CREATING 2 UNITS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW STAIR HAND RAIL EXTENSION AT THE BOTTOM
 OF THE STAIRS TO SLOPE PER FBC 1014.6 HANDRAIL
 EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM)
 BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE
 DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER.
  
 2) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS
 "REFLECTIVE SURFACE" WHEN SHOWING THE DIMENSION FROM
 THE FLOOR TO THE BOTTOM OF THE MIRROR - FBC A 603.3
 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 3) ACCESSIBLE RESTROOM = PLEASE SHOW THE TOILET PAPER
 DISPENSER DIMENSIONS FROM THE FRONT OF THE TOILET AND
 HEIGHT FROM THE FLOOR - FBC A 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 4) PLEASE SHOW THE RAMP EDGE PROTECTION (SHOW THE GUARD
 RAIL BOTTOM RAIL WITHIN 4" OF THE RAMP) FBC A 405.9
 EDGE PROTECTION.
 EDGE PROTECTION COMPLYING WITH 405.9.1 OR 405.9.2 SHALL
 BE PROVIDED ON EACH SIDE OF RAMP RUNS AND AT EACH SIDE
 OF RAMP LANDINGS. 405.9.2CURB OR BARRIER.
 A CURB OR BARRIER SHALL BE PROVIDED THAT PREVENTS THE
 PASSAGE OF A 4 INCH (100 MM) DIAMETER SPHERE, WHERE ANY
 PORTION OF THE SPHERE IS WITHIN 4 INCHES (100 MM) OF
 THE FINISH FLOOR OR GROUND SURFACE.
  
 5) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR STOREFRONT WINDOWS
 AND DOORS - ALL PRODUCT APPROVALS NEED TO BE REVIEWED
 AND MARKED APPROVED BY THE DESIGNER OF RECORD FBC WPB
 107.3.4
  
 6) CANNOT REUSE STOREFRONT WINDOWS UNLESS YOU HAVE A
 CURRENT PRODUCT APPROVAL FOR THEM - FBC EXISTING 707.4
 REPLACEMENT OF WINDOWS AND DOORS.
 THE REPLACEMENT OF GARAGE DOORS, EXTERIOR DOORS,
 SKYLIGHTS, AND OPERATIVE AND INOPERATIVE WINDOWS SHALL
 BE DESIGNED AND CONSTRUCTED TO COMPLY WITH CHAPTER 16
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 7) ELEVATION CERTIFICATE PROVIDED IS INCORRECT - PALM
 BEACH COUNTY FLOOD MAP SHOWS BUILDING IN A FLOOD ZONE
 (AE 12.10) - NFIP - JOB IS A SUBSTANTIAL IMPROVEMENT
 JOB VALUE + 5 YEAR ACCUMULATION = 1,015,272.00 -
 BUILDING VALUE = 1,355,080.00 - THE BUILDING LOWEST
 FLOOR ELEVATION NEEDS TO BE AT 14.10 NAVD - PLEASE
 PROVIDE AN ELEVATION CERTIFICATE TO VERIFY THE LOWEST
 FLOOR ELEVATION - ORDINANCE NO. 4729-17 SEC. 18-35 (A)
 AND (B)

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-05 Cont ID  
Sent By rmcphers Date 2022-05-05 Time 15:31 Rev Time 0.00
Received By rmcphers Date 2022-05-05 Time 15:31 Sent To  
Notes
2022-05-05 15:41:39CREATING 2 UNITS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE MOP SINK WALLS TO COMPLY WITH FBC
 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR,
  
 2) PLEASE SHOW STAIR HAND RAIL HEIGHT PER FBC 1014.2
 HEIGHT.
 HANDRAIL HEIGHT, MEASURED ABOVE STAIR TREAD NOSINGS, OR
 FINISH SURFACE OF RAMP SLOPE, SHALL BE UNIFORM, NOT
 LESS THAN 34 INCHES (864 MM) AND NOT MORE THAN 38
 INCHES (965 MM).
  
 3) PLEASE SHOW STAIR HAND RAIL EXTENSION AT THE BOTTOM
 OF THE STAIRS TO SLOPE PER FBC 1014.6 HANDRAIL
 EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM)
 BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE
 DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER.
  
 4) PLEASE SHOW THE STAIR RISER HEIGHT AND TREAD DEPTHS
 TO COMPLY WITH FBC 1011.5.2 RISER HEIGHT AND TREAD
 DEPTH.
 STAIR RISER HEIGHTS SHALL BE 7 INCHES (178 MM) MAXIMUM
 AND 4 INCHES (102 MM) MINIMUM. THE RISER HEIGHT SHALL
 BE MEASURED VERTICALLY BETWEEN THE NOSINGS OF ADJACENT
 TREADS. RECTANGULAR TREAD DEPTHS SHALL BE 11 INCHES
 (279 MM) MINIMUM MEASURED HORIZONTALLY BETWEEN THE
 VERTICAL PLANES OF THE FOREMOST PROJECTION OF ADJACENT
 TREADS AND AT A RIGHT ANGLE TO THE TREAD?S NOSING.
  
 5) PLEASE SHOW THAT STAIR HAND RAILS ARE REQUIRED ON
 BOTH SIDES PER FBC 1011.11 HANDRAILS.
 FLIGHTS OF STAIRWAYS SHALL HAVE HANDRAILS ON EACH SIDE
 AND SHALL COMPLY WITH SECTION 1014.
  
 6) PLEASE SHOW THE STAIR LANDINGS SIZES PER FBC 1011.6
  
 7) PLEASE SHOW THE STAIR AND RAMP WIDTHS FBC 1005 - -
 FBC 1012.5.1
  
 8) PLEASE SHOW THAT HAND RAILS ARE REQUIRED ON BOTH
 SIDES OF THE RAMP - FBC 1012.8 HANDRAILS.
 RAMPS WITH A RISE GREATER THAN 6 INCHES (152 MM) SHALL
 HAVE HANDRAILS ON BOTH SIDES.
  
 9) PLEASE SHOW THE RAMP LANDING SIZES - FBC A
  
 10) PLEASE SHOW THE RAMP SLOPE - FBC A
  
 11) PLEASE SHOW THE RAMP HAND RAIL HEIGHT - FBC A
  
 12) PLEASE SHOW THE ACCESSIBLE DOOR WIDTHS - FBC A
  
 13) BUILDING ADDRESS APPEARS TO BE INCORRECT ON THE
 BUILDING PERMIT APPLICATION AND THE DRAWINGS - PLEASE
 CORRECT.
  
 14) PLEASE SHOW THE ACCESSIBLE RESTROOM DIMENSION
 DETAILS FOR THE GRAB BAR SIZES AND LOCATIONS, MIRROR,
 TOILET PAPER HOLDER, FIXTURE CLEAR FLOOR SPACE ETC PER
 FBC A CHAPTER 6
  
 15) PLEASE SHOW THE ACCESSIBLE ROUTE TO UNIT 100A - FBC
 A 206.4 ENTRANCES.
 ENTRANCES SHALL BE PROVIDED IN ACCORDANCE WITH 206.4.
 ENTRANCE DOORS, DOORWAYS, AND GATES SHALL COMPLY WITH
 404 AND SHALL BE ON AN ACCESSIBLE ROUTE COMPLYING WITH
 402.
  
 16) DRAWING S0.01 SHOWS WIND SPEED USED FOR WIND DESIGN
 AS 169MPH - WIND DESIGN SPEED SHOULD BE 170MPH PER FBC
 WPB SECTION 120
  
 17) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR STOREFRONT WINDOWS
 AND DOORS - ALL PRODUCT APPROVALS NEED TO BE REVIEWED
 AND MARKED APPROVED BY THE DESIGNER OF RECORD FBC WPB
 107.3.4
  
 18) CANNOT REUSE STOREFRONT WINDOWS UNLESS YOU HAVE A
 CURRENT PRODUCT APPROVAL FOR THEM - FBC EXISTING 707.4
 REPLACEMENT OF WINDOWS AND DOORS.
 THE REPLACEMENT OF GARAGE DOORS, EXTERIOR DOORS,
 SKYLIGHTS, AND OPERATIVE AND INOPERATIVE WINDOWS SHALL
 BE DESIGNED AND CONSTRUCTED TO COMPLY WITH CHAPTER 16
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 19) NFIP - JOB IS A SUBSTANTIAL IMPROVEMENT JOB VALUE +
 5 YEAR ACCUMULATION = 1,015,272.00 - BUILDING VALUE =
 1,355,080.00 - THE BUILDING LOWEST FLOOR ELEVATION
 NEEDS TO BE AT 14.10 NAVD - PLEASE PROVIDE AN ELEVATION
 CERTIFICATE TO VERIFY THE LOWEST FLOOR ELEVATION -
 ORDINANCE NO. 4729-17 SEC. 18-35 (A) AND (B)

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-07-27 Cont ID  
Sent By jleahy Date 2022-07-27 Time 13:40 Rev Time 0.00
Received By jleahy Date 2022-07-27 Time 11:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-05-06 Cont ID  
Sent By jleahy Date 2022-05-06 Time 14:36 Rev Time 0.00
Received By jleahy Date 2022-05-06 Time 12:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-09-07 Cont ID  
Sent By cwalker Date 2022-09-07 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-09-07 10:21:49FIRE PROVISO COMMENTS:
  
 ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE
 ALARM) SHALL REMAIN OPERATIONAL DURING ALL PHASES OF
 DEMOLITION AND CONSTRUCTION.
  
 ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE
 ALARM) SHALL BE PROTECTED FROM DAMAGE DURING ALL PHASES
 OF DEMOLITION AND CONSTRUCTION.
  
 ANY AND ALL WORK ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE PERFORMED UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-07-15 Cont ID  
Sent By cwalker Date 2022-07-15 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-07-15 11:00:59FIRE PROVISO COMMENTS:
 ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE
 ALARM) SHALL REMAIN OPERATIONAL DURING ALL PHASES OF
 DEMOLITION AND CONSTRUCTION.
 ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE
 ALARM) SHALL BE PROTECTED FROM DAMAGE DURING ALL PHASES
 OF DEMOLITION AND CONSTRUCTION.
 ANY AND ALL WORK ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE PERFORMED UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
 C. WALKER
 561-804-4762
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-03-28 Cont ID  
Sent By cwalker Date 2022-03-28 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-03-28 11:06:17FIRE COMMENTS:
 RETAIL SPACE 100B, MERCANTILE OCCUPANCY,
 THE LIFE SAFETY PLAN INDICATES A SINGLE EXIT WITH A
 DIRECT TRAVEL DISTANCE OF 74? 4?. THERE IS NO FURNITURE
 PLAN INCLUDED IN THE SUBMITTALS, WHICH CAN CHANGE THE
 DIRECTION OF TRAVEL THAT CAN EXCEED THE REQUIRED 75?
 TRAVEL DISTANCE AS REQUIRED IN NFPA 101 36.2.4.3
 BOTH RETAIL SPACES 100A AND 100B ARE REQUIRED TO HAVE
 PORTABLE FIRE EXTINGUISHERS PROVIDED. NFPA 101 36.3.5.3
 FIRE REVIEW CONDUCTED BY,
 C. R. WALKER, SENIOR FIRE INSPECTOR
 561-804-4762
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-09-16 Cont ID  
Sent By rmcphers Date 2022-09-16 Time 10:50 Rev Time 0.00
Received By rmcphers Date 2022-09-06 Time 07:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-29 Cont ID  
Sent By aoliver Date 2022-08-29 Time 07:16 Rev Time 0.00
Received By aoliver Date 2022-08-12 Time 09:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-02 Cont ID  
Sent By rmcphers Date 2022-08-02 Time 11:00 Rev Time 0.00
Received By rmcphers Date 2022-07-14 Time 13:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-07 Cont ID  
Sent By cpuell Date 2022-05-07 Time 09:16 Rev Time 0.00
Received By cpuell Date 2022-03-28 Time 05:34 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-10-11 Cont ID  
Sent By lmarchan Date 2022-10-11 Time 10:53 Rev Time 0.00
Received By lmarchan Date 2022-08-02 Time 11:38 Sent To  
Notes
2022-10-11 07:55:22RECEIPT MU-2022-045426 - $26,549.06 PAID
2022-08-02 11:38:338/2/22 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-05-05 Cont ID  
Sent By rmcphers Date 2022-05-05 Time 17:20 Rev Time 0.00
Received By rmcphers Date 2022-05-05 Time 17:19 Sent To  
Notes
2022-05-05 17:21:16PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-07-26 Cont ID  
Sent By medwards Date 2022-07-26 Time 13:52 Rev Time 0.00
Received By medwards Date 2022-07-26 Time 13:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-05-02 Cont ID  
Sent By medwards Date 2022-05-02 Time 17:45 Rev Time 0.00
Received By medwards Date 2022-05-02 Time 17:45 Sent To  
Notes
2022-05-02 17:45:191ST REVIEW FMC
 PERMIT: 22030290
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IS THIS A CHANGE OF USE?
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC 101.5.1.1.2
  
 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON
 FMC 403.3.1.1 3RD SENTENCE TELLS US TO USE TABLE
 403.3.1.1 TO FIND THE OCCUPANT COUNT. WE CANNOT USE THE
 EGRESS OCCUPANT COUNTY.
  
 4) PLEASE SHOW THE ROOF ACCESS. FMC 306.5
  
 5) WHY IS THE EXHAUST OF 2 SEPARATE TENANT SPACES BEING
 SHARED? FMC 501.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2022-08-25 Cont ID  
Sent By rmcphers Date 2022-08-25 Time 09:45 Rev Time 0.00
Received By rmcphers Date 2022-08-25 Time 09:45 Sent To  
Notes
2022-08-25 09:45:36JOB IS A SUBSTANTIAL IMPROVEMENT JOB VALUE + 5 YEAR
 ACCUMULATION = 1,015,272.00 - BUILDING VALUE =
 1,355,080.00 - THE BUILDING LOWEST FLOOR ELEVATION
 NEEDS TO BE AT 14.10 NAVD - PLEASE PROVIDE AN ELEVATION
 CERTIFICATE TO VERIFY THE LOWEST FLOOR ELEVATION -
 ORDINANCE NO. 4729-17 SEC. 18-35 (A) AND (B)
  
 AE 12.10
  
 ELEVATION CERTIFICATE SHOWS LOWEST FLOOR AT 16.30 NAVD

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-07-15 Cont ID  
Sent By rwbrown Date 2022-07-15 Time 13:17 Rev Time 0.00
Received By rwbrown Date 2022-07-15 Time 13:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-04-26 Cont ID  
Sent By rwbrown Date 2022-04-26 Time 10:45 Rev Time 0.00
Received By rwbrown Date 2022-04-26 Time 10:36 Sent To  
Notes
2022-04-26 10:44:571ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. PAGE P2.1 - V7 FPC 410.3 - A HIGH/LOW DRINKING
 FOUNTAIN IS REQUIRED.
  
 2. PAGE P0.1 - 2020 FPC - 607.1.1 TEMPERATURE LIMITING
 MEANS - THE THERMOSTAT CONTROL ON THE WATER HEATER
 CANNOT BE THE LIMITING DEVICE FOR HOT WATER DELIVERY.
 PLEASE PROVIDE A DETAIL FOR A LIMITING DEVICE FOR THE
 PURPOSE OF HOT WATER DELIVERY. THIS WOULD BE IN
 ADDITION TO THE REQUIREMENTS FOR TEMPERED WATER FOR
 PUBLIC HAND-WASHING 607.1.2/419.5.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-09-16 Cont ID  
Sent By rmcphers Date 2022-09-16 Time 09:59 Rev Time 0.00
Received By rmcphers Date 2022-09-16 Time 09:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-08-25 Cont ID  
Sent By rmcphers Date 2022-08-25 Time 09:56 Rev Time 0.00
Received By rmcphers Date 2022-08-25 Time 09:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-07-15 Cont ID  
Sent By rwbrown Date 2022-07-15 Time 13:18 Rev Time 0.00
Received By rwbrown Date 2022-07-15 Time 13:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-05-05 Cont ID  
Sent By rmcphers Date 2022-05-05 Time 17:25 Rev Time 0.00
Received By rmcphers Date 2022-05-05 Time 17:25 Sent To  
Notes
2022-05-02 17:50:51MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 3 Status P Date 2022-08-25 Cont ID  
Sent By vbroglia Date 2022-08-25 Time 16:05 Rev Time 0.00
Received By vbroglia Date 2022-08-25 Time 16:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-07-28 Cont ID  
Sent By vbroglia Date 2022-07-28 Time 16:44 Rev Time 0.00
Received By vbroglia Date 2022-07-28 Time 16:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-04-05 Cont ID  
Sent By vbroglia Date 2022-04-05 Time 16:42 Rev Time 0.00
Received By vbroglia Date 2022-04-05 Time 16:42 Sent To  
Notes
***NONE***