Plan Review Details - Permit 22030111
Plan Review Stops For Permit 22030111
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-03-22 Cont ID  
Sent By jwitmer Date 2022-03-22 Time 10:34 Rev Time 0.00
Received By jwitmer Date 2022-03-22 Time 10:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-04-12 Cont ID  
Sent By jwitmer Date 2022-04-12 Time 16:34 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-22 Cont ID  
Sent By jwitmer Date 2022-03-22 Time 10:48 Rev Time 0.00
Received By jwitmer Date 2022-03-22 Time 10:14 Sent To  
Notes
2022-03-22 10:48:36WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22030111
 ADD: 801 S OLIVE AVE# 1001
 CONT: THE LEVI GROUP LLC
 TEL: 561-714-8000
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 22ND/2022
 ACTION: DENIED
  
 1) NEITHER THE PERMIT APPLICATION NOR FLOOR PLAN STATE
 WHAT THE FLOOR FINISH WILL BE IN THE 2 BATHROOMS NOR
 THE FLOOR NOTES ON SHEET A-2/ 12.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES.
  
 2) THE DEMO FLOOR PLAN IN THE MASTER BATH STATES TO
 REMOVE SECTION OF CURVED SOFFIT ABOVE, THE FLOOR PLAN
 IS SILENT AS TO HOW TO REFRAME THE DROPPED CEILING OR
 DOES THE CEILING GO ALL THE WAY TO THE CONCRETE FLOOR
 DECK ABOVE. IF NEW FRAMING IS INVOLVED, PROVIDE THE
 SIZE AND SPACING OF THE CEILING FRAMING MEMBERS, SPAN,
 IF BRACED, OR STIFF BACK AT MID-SPAN AND TYPE OF
 CEILING FINISH MATERIAL AND THICKNESS. 2020 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES.
  
 3) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-04-13 Cont ID  
Sent By mpeterso Date 2022-04-13 Time 13:32 Rev Time 0.00
Received By mpeterso Date 2022-04-13 Time 13:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-03-29 Cont ID  
Sent By mpeterso Date 2022-03-29 Time 15:19 Rev Time 0.00
Received By mpeterso Date 2022-03-29 Time 15:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-04-06 Cont ID  
Sent By pleduc Date 2022-04-06 Time   Rev Time 0.00
Received By pleduc Date 2022-04-06 Time 13:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-03-09 Cont ID  
Sent By pleduc Date 2022-03-09 Time   Rev Time 0.00
Received By jwitmer Date 2022-03-22 Time 10:21 Sent To  
Notes
2022-03-09 11:16:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION ON THE DEMO PLAN: "REMOVE
 EXISTING FLOORING AND BASEBOARDS THROUGHOUT", HOWEVER,
 THERE IS NO INDICATION OF THE REPLACEMENT FLOOR
 PRODUCT/MATERIAL.
  
 THERE IS ALSO A SPEC SHEET FOR THE FLOOR UNDERLAYMENT,
 BUT NO SPEC SHEET NOR A PRODUCT NAME FOR THE ACTUAL
 PROPOSED REPLACEMENT FLOORING.
  
 VINYL FLOORING IS MANUFACTURED AROUND THE WORLD AND NOT
 ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING
 PRODUCT NAME AND THE PRODUCT SPEC SHEETS OF THE
 PROPOSED FINISHED
 FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
 2) THE ARE INDICATIONS OF DEMO WORK.
  
 FIRE SPRINKLERS AND FIRE ALARM EQUIPMENT SHALL BE
 PROTECTED FROM PAINTING OR DAMAGE.
  
 THE FIRE SPRINKLER/FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO AND RECONSTRUCTION.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND ENSURE
 COMPLIANCE.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-13 Cont ID  
Sent By mpeterso Date 2022-04-13 Time 13:32 Rev Time 0.00
Received By mpeterso Date 2022-04-05 Time 06:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-29 Cont ID  
Sent By mpeterso Date 2022-03-29 Time 15:19 Rev Time 0.00
Received By mpeterso Date 2022-03-08 Time 09:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-04-06 Cont ID  
Sent By rwbrown Date 2022-04-06 Time 06:37 Rev Time 0.00
Received By rwbrown Date 2022-04-06 Time 06:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-03-09 Cont ID  
Sent By rwbrown Date 2022-03-09 Time 11:01 Rev Time 0.00
Received By rwbrown Date 2022-03-09 Time 11:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-04-12 Cont ID  
Sent By jwitmer Date 2022-04-12 Time 16:34 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-03-22 Cont ID  
Sent By jwitmer Date 2022-03-22 Time 10:49 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***