Plan Review Details - Permit 22030012
Plan Review Stops For Permit 22030012
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-07-05 Cont ID  
Sent By jwitmer Date 2022-07-05 Time 13:59 Rev Time 0.00
Received By jwitmer Date 2022-07-05 Time 13:54 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-03-22 Cont ID  
Sent By jwitmer Date 2022-03-22 Time 07:52 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-03-22 07:52:45COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-09-06 Cont ID  
Sent By jwitmer Date 2022-09-06 Time 10:44 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-07-05 Cont ID  
Sent By jwitmer Date 2022-07-05 Time 14:27 Rev Time 0.00
Received By jwitmer Date 2022-07-05 Time 13:54 Sent To  
Notes
2022-07-05 14:27:06WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22030012
 ADD: 819 8TH STREET
 CONT: NEWBOLD CONSTRUCTION
 TEL: 561-644-5764
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES.JULY05TH/2022
 ACTION: DENIED
  
 1) BUILDING PROVISO: SEE ZONING COMMENTS 1, 2,& 3
 SEPARATE PERMIT ARE REQUIRED FOR FENCE PERMIT,
 LANDSCAPING PERMIT , IRRIGATION PERMIT & RESTRIPING OF
 PARKING LOT.
  
 2) COMPLIED.
  
 3) 2ND REQUEST. NEITHER THE CONTRACTOR OR ENGINEER OF
 RECORD HAS COMPLIED WITH: BOTH THE NOA 20-0428.01
 4200/6200 ALUM. FIXED FRAME L. M. I. AND NOA 20-0814.10
 CLIPPED EXTRUDED ALUM. TUBE MULLION W/ AND W/O STEEL
 REINFORCEMENT ARE MISSING COMPLIANCE WITH IDENTIFY
 GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH
 IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 4) 2ND REQUEST SEMI-COMPLIED. 61G15-23.002(2)(B) FL.
 ADMIN. CODE. A COVER SHEET WITH LISTED PAGES OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE
 COVERED UNDER THE COVER SHEET OR INDEX SHEET.
 1ST ROUND COMMENTS. PLEASE NOTE THE ENGINEERING
 CALCULATIONS WERE SEALED WITH AN ENGINEERS SEAL FROM
 SOUTH CAROLINA. FLORIDA STATUTE 471.003?QUALIFICATIONS
 FOR PRACTICE; EXEMPTIONS. ?
 (1)?NO PERSON OTHER THAN A DULY LICENSED ENGINEER SHALL
 PRACTICE ENGINEERING OR USE THE NAME OR TITLE OF
 ?LICENSED ENGINEER,? ?PROFESSIONAL ENGINEER,? OR ANY
 OTHER TITLE, DESIGNATION, WORDS, LETTERS,
 ABBREVIATIONS, OR DEVICE TENDING TO INDICATE THAT SUCH
 PERSON HOLDS AN ACTIVE LICENSE AS AN ENGINEER IN THIS
 STATE.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-22 Cont ID  
Sent By jwitmer Date 2022-03-22 Time 09:24 Rev Time 0.00
Received By jwitmer Date 2022-03-22 Time 07:52 Sent To  
Notes
2022-03-22 09:24:25WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22030012
 ADD: 819 8TH STREET
 CONT: NEWBOLD CONSTRUCTION
 TEL: 561-644-5764
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 22ND/2022
 ACTION: DENIED
  
 1) SEE ZONING COMMENTS 1, 2,& 3 SEPARATE PERMIT ARE
 REQUIRED FOR FENCE PERMIT, LANDSCAPING PERMIT ,
 IRRIGATION PERMIT & RESTRIPING OF PARKING LOT.
  
 2) SHEET D1 FOR ALL WINDOWS 1-18 (SINGLE SECTION) THE
 STATEMENT EXISTING WINDOWS ARE NON-IMPACT WINDOWS TO BE
 REMOVED AND WALL TRIMMED BELOW FOR NEW SILL HEIGHT OF
 36 INCHES. ARE THESE WINDOWS TO BE RE-USED? IF SO HOW
 WILL THEY MEET THE REQUIREMENT IN THE 2020 FBC-BUILDING
 CODE 1609.1.2.2 LARGE MISSILE IMPACT OR 1609.1.2.4.
  
 3) BOTH THE NOA 20-0428.01 4200/6200 ALUM. FIXED FRAME
 L. M. I. AND NOA 20-0814.10 CLIPPED EXTRUDED ALUM. TUBE
 MULLION W/ AND W/O STEEL REINFORCEMENT ARE MISSING
 COMPLIANCE WITH IDENTIFY GLAZING/ MULLIONS. PLEASE
 IDENTIFY IN THE PRODUCT APPROVAL BEFORE SUBMITTING TO
 DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 4) PLEASE NOTE THE ENGINEERING CALCULATIONS WERE SEALED
 WITH AN ENGINEERS SEAL FROM SOUTH CAROLINA. FLORIDA
 STATUTE 471.003?QUALIFICATIONS FOR PRACTICE;
 EXEMPTIONS. ?
 (1)?NO PERSON OTHER THAN A DULY LICENSED ENGINEER SHALL
 PRACTICE ENGINEERING OR USE THE NAME OR TITLE OF
 ?LICENSED ENGINEER,? ?PROFESSIONAL ENGINEER,? OR ANY
 OTHER TITLE, DESIGNATION, WORDS, LETTERS,
 ABBREVIATIONS, OR DEVICE TENDING TO INDICATE THAT SUCH
 PERSON HOLDS AN ACTIVE LICENSE AS AN ENGINEER IN THIS
 STATE.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-08-24 Cont ID  
Sent By pleduc Date 2022-08-24 Time   Rev Time 0.00
Received By pleduc Date 2022-08-24 Time 11:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-06-27 Cont ID  
Sent By pleduc Date 2022-06-27 Time   Rev Time 0.00
Received By pleduc Date 2022-06-27 Time 10:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-03-03 Cont ID  
Sent By pleduc Date 2022-03-03 Time   Rev Time 0.00
Received By pleduc Date 2022-03-03 Time 14:20 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-06-27 Cont ID  
Sent By fmittner Date 2022-06-27 Time 16:26 Rev Time 0.00
Received By fmittner Date 2022-06-27 Time 16:26 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2022-06-15 Cont ID  
Sent By fmittner Date 2022-06-15 Time 13:43 Rev Time 0.00
Received By fmittner Date 2022-06-15 Time 13:43 Sent To  
Notes
2022-06-15 13:43:49WINDOWS NEED TO MATCH ORIGINAL OPENING SIZE, RETAIN
 SILL AND HAVE GRIDS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2022-09-06 Time   Rev Time 0.00
Received By lmarchan Date 2022-08-23 Time 16:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-21 Cont ID  
Sent By aoliver Date 2022-07-21 Time 08:49 Rev Time 0.00
Received By aoliver Date 2022-06-24 Time 07:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-16 Cont ID  
Sent By aoliver Date 2022-06-16 Time 09:09 Rev Time 0.00
Received By aoliver Date 2022-03-02 Time 12:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-09-06 Cont ID  
Sent By jwitmer Date 2022-09-06 Time 10:37 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-07-05 Cont ID  
Sent By jwitmer Date 2022-07-05 Time 14:28 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-07-05 14:28:251) 2ND REQUEST SEMI-COMPLIED. 61G15-23.002(2)(B) FL.
 ADMIN. CODE. A COVER SHEET WITH LISTED PAGES OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE
 COVERED UNDER THE COVER SHEET OR INDEX SHEET

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-03-22 Cont ID  
Sent By rmcdouga Date 2022-03-02 Time 17:02 Rev Time 0.00
Received By jwitmer Date 2022-03-02 Time 17:02 Sent To  
Notes
2022-03-22 09:25:38PLEASE NOTE THE ENGINEERING CALCULATIONS WERE SEALED
 WITH AN ENGINEERS SEAL FROM SOUTH CAROLINA. FLORIDA
 STATUTE 471.003?QUALIFICATIONS FOR PRACTICE;
 EXEMPTIONS. ?
 (1)?NO PERSON OTHER THAN A DULY LICENSED ENGINEER SHALL
 PRACTICE ENGINEERING OR USE THE NAME OR TITLE OF
 ?LICENSED ENGINEER,? ?PROFESSIONAL ENGINEER,? OR ANY
 OTHER TITLE, DESIGNATION, WORDS, LETTERS,
 ABBREVIATIONS, OR DEVICE TENDING TO INDICATE THAT SUCH
 PERSON HOLDS AN ACTIVE LICENSE AS AN ENGINEER IN THIS
 STATE.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
2022-03-02 17:08:05SIGNED AND SEALED PAPER PLANS AND STEEPLE CALCULATIONS
 SENT TO STORAGE.

Review Stop Z ZONING
Rev No 3 Status P Date 2022-08-29 Cont ID  
Sent By ckimmerl Date 2022-08-25 Time 12:32 Rev Time 0.00
Received By ckimmerl Date 2022-08-25 Time 12:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-07-20 Cont ID  
Sent By ckimmerl Date 2022-07-20 Time 10:46 Rev Time 0.00
Received By ckimmerl Date 2022-07-20 Time 09:55 Sent To  
Notes
2022-07-20 10:46:01REPEAT COMMENTS
  
 1. PROPOSED FENCE REQUIRES A SEPARATE PERMIT.
 - PLEASE SUBMIT FOR A FENCE PERMIT.
 - PROPOSED FENCE HEIGHT FOR FRONT, SIDE, AND REAR MEETS
 CODE.
  
 2. FOR THE SURFACE PARKING LOT. SHADE TREES SHALL BE
 PLANTED AT 30-FOOT INTERVALS ALONG BOTH THE FRONT AND
 SIDE.
 - PLEASE PROVIDE TREE DETAILS AND LOCATIONS IN SITE
 PLAN OR SEPARATE SHEET.
  
 3. LANDSCAPE AREAS ALONG THE BASE OF THE BUILDING NEED
 TO BE PROTECTED FROM DRIVEWAY VIA CURBING.
 - PLEASE PROVIDE CURB DETAILS IN SITE PLAN OR SEPARATE
 SHEET.
  
 4. THE SOUTHERN ROW OF PARKING SPACES ALONG THE STREET
 FRONTAGE REQUIRES A TERMINAL LANDSCAPE ISLAND OF A
 MINIMUM OF 8FT. IN WIDTH AND NO SHORTER THAN THE LENGTH
 OF THE ADJACENT SPACE. ISLAND SHALL ALSO BE PROTECTED
 WITH A CURB AND INCLUDE LANDSCAPING.
  
 5. PARKING STALL DIMENSIONS. PARKING STALL DIMENSIONS
 SHALL COMPLY WITH THE GENERAL PARKING STANDARDS
 ACCORDING TO FIGURE XV-2 IN SECTION 94-485.
 - PLEASE PROVIDE PARKING STALL STRIPING DETAIL WITHIN
 SITE PLAN OR ON SEPARATE SHEET.
  
  
 WINDOW REPLACEMENT, PAVERS, STEEPLE RENOVATION, FENCE,
 AND AC SCREENING ALL MEET CODE REQUIREMENTS.
  
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 [email protected]
 822-1426

Review Stop Z ZONING
Rev No 1 Status F Date 2022-03-16 Cont ID  
Sent By vbroglia Date 2022-03-16 Time 15:52 Rev Time 0.00
Received By ckimmerl Date 2022-03-16 Time 12:00 Sent To  
Notes
2022-03-16 15:52:141. PROPOSED FENCE REQUIRES A SEPARATE PERMIT. WHEN
 SUBMITTING SEPARATE FENCE PERMITS PLEASE NOTE: MAX
 HEIGHT ALONG FRONT SHALL BE 4?, MAX HEIGHT FOR SIDE AND
 REAR FENCES IS 6?.
  
 2. PROPOSED LANDSCAPE WILL REQUIRE A SEPARATE PERMIT.
  
 3. SEPARATE PERMITS FOR IRRIGATION, ETC. AS IS
 APPLICABLE.
  
 4. REQUIRED 5' LANDSCAPE BUFFER ON THE STREET FRONTAGE,
 NEEDS TO BE INCREASED. CANNOT COUNT THE PORTION OF
 RIGHT-OF-WAY AS PART OF LANDSCAPE BUFFER. REQUIRE 5'
 ADDITIONAL, MAY REQUIRE REDUCTION IN ASPHALT PARKING TO
 BE PUSHED IN/BACK.
 - PARKING SPACES ARE LARGER THAN IS REQUIRED FOR
 STANDARD SPACE. CITY STANDARD IS 18'X8'6" FOR REGULAR
 SPACE, ADA SPACES SHALL BE 18'X12' WITH ADJACENT 5'
 AISLE. PARKING STALL DIMENSIONS CAN BE REDUCED TO
 CITY-STANDARD IN ORDER TO PROVIDE ADDITIONAL LANDSCAPE
 BUFFER SPACE.
 - PLEASE PROVIDE PARKING LOT DRIVE AISLE DIMENSION,
 APPEARS LARGER THAN REQUIRED. CITY STANDARD IS 24' OF
 SPACE TO ALLOW FOR VEHICULAR MOBILITY, EXISTING ASPHALT
 LOT APPEARS GREATER THAN 24', CAN BE REDUCED TO CITY
 STANDARD IN ORDER TO PROVIDE ADDITIONAL LANDSCAPE
 BUFFER SPACE.
  
 5. REQUIRED 5' LANDSCAPE BUFFER ON EAST SIDE OF
 PROPERTY NEEDS TO BE INCLUDED, SITE PLAN SHOWS PROPOSED
 COCOPLUM/HEDGES OUTSIDE OF PROPERTY?
  
 6. FOR THE SURFACE PARKING LOT. SHADE TREES SHALL BE
 PLANTED AT 30-FOOT INTERVALS ALONG BOTH THE FRONT AND
 SIDE.
  
 7. PAVER WALKWAY SHALL BE ALTERED FROM PROPOSED PLANS.
 - PLEASE REMOVE PAVERS FROM DRIVEWAY APRON AND THE
 SECTION WITHIN RIGHT-OF-WAY/SIDEWALK.
 - PLEASE WIDEN THE PAVER PORTION TO ENCOMPASS THE FULL
 WIDTH OF THE DRIVEWAY.
 - REQUIRED DEPTH OF PAVER SECTION NEEDS ONLY TO INCLUDE
 UP UNTIL THE DEPTH OF THE FIRST PARKING SPACE. TOTAL
 DEPTH OF PAVERS IS APPROXIMATELY 23? (5? BUFFER + 18?
 PARKING DEPTH)
 DO NOT NEED TO DO ENTIRE LENGTH OF ASPHALT UNLESS
 DESIRED.
  
 8. PLEASE CLEARLY INDICATE THE PROPERTY LINE WITHIN THE
 SITE PLAN.
  
 9. SURVEY IS NOT CORRECT, PLEASE PROVIDE UPDATED SURVEY
 WITH RECENTLY UNIFIED PARCELS, SHOW FULL SCOPE OF
 PROPERTY AND PROJECT AREA.
  
 10. LANDSCAPE AREAS ALONG THE BASE OF THE BUILDING
 NEEDS TO BE PROTECTED FROM DRIVEWAY VIA CURBING.
  
 11. PARKING LOT/SPACES NEED TO FOLLOW CITY STANDARDS IN
 PARKING STRIPING SEE SEC. 94-485. - GENERAL PROVISIONS.
 (4?6?6?4?)
  
 12. LANDSCAPE SCREENING FOR MECHANICAL EQUIPMENT ON
 FRONT CORNER IS ONLY POSSIBLE IF ASPHALT IS REMOVED,
 PLEASE CLARIFY.
  
 13. THE ROW OF PARKING SPACES ALONG THE STREET REQUIRES
 A TERMINAL LANDSCAPE ISLAND OF A MINIMUM OF 8? IN WIDTH
 AND NO SHORTER THAN THE LENGTH OF THE ADJACENT SPACE.
 ISLAND SHALL ALSO BE PROTECTED WITH A CURB.
  
 CHRIS KIMMERLY
 [email protected]
 822-1426