Plan Review Details - Permit 22021396
Plan Review Stops For Permit 22021396
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-05-23 Cont ID  
Sent By jbrooks Date 2022-05-23 Time 08:28 Rev Time 0.00
Received By jbrooks Date 2022-05-23 Time 07:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-05-09 Cont ID  
Sent By jbrooks Date 2022-05-09 Time 12:45 Rev Time 0.00
Received By jbrooks Date 2022-05-09 Time 10:08 Sent To  
Notes
2022-05-09 12:45:42JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL2533-R27 SYSTEM NO. W-82 DOES NOT MEET THE
 MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17
 FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT
 MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR
 EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED
 ENGINEERED NAILING CALCULATIONS WITH AN APPROVED
 SYSTEM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-07 Cont ID  
Sent By jbrooks Date 2022-04-07 Time 11:18 Rev Time 0.00
Received By jbrooks Date 2022-04-07 Time 08:00 Sent To  
Notes
2022-04-07 11:19:12JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. SUBMITTED PRODUCT APPROVAL FL2533-R25 HAS BEEN
 REVISED TO FL2533-R26. PLEASE PROVIDE A COMPLETE SET.
 INCLUDE COVER PAGE, EVALUATION REPORTS AND INSTALLATION
 INSTRUCTIONS FOR SYSTEM USED. FLORIDA DBPR PRODUCT
 APPROVAL FL2533-R25 SYSTEM NO. W-84 DO NOT MEET THE
 MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17
 FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT
 MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR
 EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED
 ENGINEERED NAILING CALCULATIONS WITH AN APPROVED
 SYSTEM. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE
 CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN
 PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 AS PER RULE 61G20-3.
 2. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S). FLAT/LOW
 SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE.
 3. FBC B 107.2.1 PROVIDE A ROOF DRAINAGE PLAN THAT
 COMPLIES WITH SECTION 903.4 OF THE 2020 FBC-RESIDENTIAL
 AND CHAPTER 11 OF THE 2020 FBC-PLUMBING.
 4. FBC EB 706.6 PROVIDE A FLASHING DETAIL DRAWING FOR
 THE EXISTING PARAPET WALLS TO INCLUDE PARAPET WALL
 HEIGHT(S).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2022-04-07 Cont ID  
Sent By jbrooks Date 2022-04-07 Time 11:19 Rev Time  
Received By jbrooks Date   Time   Sent To  
Notes
2022-04-07 11:19:52*FLAT ROOF ONLY*

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-05-23 Cont ID  
Sent By jbrooks Date 2022-05-23 Time 08:28 Rev Time 0.00
Received By jbrooks Date 2022-05-12 Time 13:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-09 Cont ID  
Sent By jbrooks Date 2022-05-09 Time 12:45 Rev Time 0.00
Received By jbrooks Date 2022-04-28 Time 06:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-07 Cont ID  
Sent By jbrooks Date 2022-04-07 Time 11:19 Rev Time 0.00
Received By jbrooks Date 2022-04-06 Time 10:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-05-23 Cont ID  
Sent By jbrooks Date 2022-05-23 Time 08:28 Rev Time 0.00
Received By jbrooks Date 2022-05-23 Time 08:27 Sent To  
Notes
***NONE***