Plan Review Details - Permit 22021307
Plan Review Stops For Permit 22021307
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2022-11-30 Cont ID  
Sent By eroseber Date 2022-11-30 Time 21:03 Rev Time 0.00
Received By eroseber Date 2022-11-30 Time 21:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2022-11-07 Cont ID  
Sent By eroseber Date 2022-11-07 Time 20:28 Rev Time 0.00
Received By eroseber Date 2022-11-07 Time 20:28 Sent To  
Notes
2022-11-07 20:30:221. CONTRACTOR INFORMATION FOR MRH SUPPLIED TO ENGINEER
 FOR REQUIRED DESIGN PRESSURE CALCULATIONS APPEARS TO
 HAVE INADVERTENTLY BEEN SUBMITTED AS 48FT. PLEASE
 RESUBMIT CORRECT MRH TO ENGINEER FOR DESIGN PRESSURE
 CALCULATION BASED ON CORRECT DATA. FBC 107.2
 2. PLEASE PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO
 THE PLAN, DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR
 FBC B 1405.4.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-10-24 Cont ID  
Sent By pvalenti Date 2022-10-24 Time 06:44 Rev Time 0.00
Received By pvalenti Date 2022-10-24 Time 06:30 Sent To  
Notes
2022-10-24 07:03:29PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1/FBC B 1609.1.1, THE SIGNED/SEALED
 SUBMITTALS FROM PROFESSIONAL ENGINEER, FRANK BENNARDO,
 INDICATE A MEAN ROOF HEIGHT OF 48' UNDER THE
 CONTRACTOR-PROVIDED INPUT SECTION OF ENGINEERING
 EXPRESS DOCUMENTS. THIS DOES NOT APPEAR TO BE ACCURATE.
 PLEASE RE-EVALUATE AND RESUBMIT OR PROVIDE
 CLARIFICATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-09-19 Cont ID  
Sent By shill Date 2022-09-19 Time 13:04 Rev Time 0.00
Received By shill Date 2022-09-19 Time 13:04 Sent To  
Notes
2022-09-19 13:04:46[email protected]
 [email protected]
  
 1.THIS PROJECT MRH EXCEEDS 60', THEREFORE REQUIRING
 SIGNED AND SEALED SITE SPECIFIC ENGINEERING. FBC 107.2.
 2. PLEASE CLARIFY WITH PROJECT SPECIFIC DOCUMENTS,
 HIGHLIGHTED DESIGN PRESSURE COMPLIANCE, AND NO
 DUPLICATED DOCUMENTS. 3 SETS OF DESIGN PRESSURE
 REQUIREMENTS SUBMITTED FROM ENGINEERING EXPRESS. NONE
 ARE HIGHLIGHTED AND SIGNATURES ARE INVALID. FBC 107.2
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-05-16 Cont ID  
Sent By jbrooks Date 2022-05-16 Time 08:04 Rev Time 0.00
Received By jbrooks Date 2022-05-16 Time 08:03 Sent To  
Notes
2022-05-16 08:04:521ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. MEAN ROOF HEIGHT NOT PROVIDED. APARTMENT HEIGHT
 NOTATED AT 25FT, THIS UNIT APPEARS TO BE ON THE 7TH
 FLOOR. HEIGHT MAYBE APPROX. 70? FT.
 2. ENGINEER?S CALCULATIONS SHOULD REFERENCE HEIGHT
 PRESSURES OVER 60? IN HEIGHT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-07 Cont ID  
Sent By pvalenti Date 2022-04-07 Time 07:50 Rev Time 0.00
Received By pvalenti Date 2022-04-07 Time 07:39 Sent To  
Notes
2022-04-07 07:54:17PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, INDICATE WITHIN THE MULLION PRODUCT
 APPROVAL, BY CIRCLING/MARKING, THE SELECTED OPTIONS FOR
 MULLION TYPE/SIZE & THICKNESS THAT WILL BE USED
 CONSIDERING THE WIND LOAD PRESSURES.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status P Date 2022-11-30 Cont ID  
Sent By eroseber Date 2022-11-30 Time 21:04 Rev Time 0.00
Received By eroseber Date 2022-11-15 Time 08:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status F Date 2022-11-07 Cont ID  
Sent By eroseber Date 2022-11-07 Time 20:31 Rev Time 0.00
Received By eroseber Date 2022-10-26 Time 15:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-10-24 Cont ID  
Sent By pvalenti Date 2022-10-24 Time 07:11 Rev Time 0.00
Received By pvalenti Date 2022-10-05 Time 06:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-09-19 Cont ID  
Sent By shill Date 2022-09-19 Time 13:05 Rev Time 0.00
Received By shill Date 2022-09-02 Time 07:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-16 Cont ID  
Sent By jbrooks Date 2022-05-16 Time 08:05 Rev Time 0.00
Received By jbrooks Date 2022-04-20 Time 16:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-07 Cont ID  
Sent By pvalenti Date 2022-04-07 Time 08:06 Rev Time 0.00
Received By pvalenti Date 2022-03-21 Time 10:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-11-30 Cont ID  
Sent By eroseber Date 2022-11-30 Time 21:04 Rev Time 0.00
Received By eroseber Date 2022-11-30 Time 21:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-10-24 Cont ID  
Sent By pvalenti Date 2022-10-24 Time 07:03 Rev Time 0.00
Received By pvalenti Date 2022-10-24 Time 06:30 Sent To  
Notes
2022-10-24 07:11:01PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW APPROVED.
  
 NOTE: ANY FUTURE DOCUMENTS SIGNED/SEALED BY DESIGN
 PROFESSIONAL WILL BE REVIEWED FOR 3RD PARTY VERIFIABLE
 DIGITAL SIGNATURES.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-09-19 Cont ID  
Sent By shill Date 2022-09-19 Time 13:04 Rev Time 0.00
Received By shill Date 2022-09-19 Time 13:04 Sent To  
Notes
2022-09-19 13:05:09SEE BUILDING REVIEW
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-05-16 Cont ID  
Sent By jbrooks Date 2022-05-16 Time 08:05 Rev Time 0.00
Received By jbrooks Date 2022-05-16 Time 08:04 Sent To  
Notes
2022-05-16 08:05:361ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
  
 1. ENGINEERS CALCULATIONS SHALL BE ORIGINAL DIGITALLY
 SIGNED. A COPY PROVIDED. 62G15-23
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
 EITHER UPLOAD A VALID ELECTRONICALLY SIGNED PLAN TO ME,
 OR YOU CAN MAIL OR DROP OFF ONE ORIGINAL SIGNED AND
 SEALED PAPER ORIGINAL WITH A WET SIGNATURE TO:
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6656.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-04-07 Cont ID  
Sent By pvalenti Date 2022-04-07 Time 07:54 Rev Time 0.00
Received By pvalenti Date 2022-04-07 Time 07:39 Sent To  
Notes
2022-04-07 08:06:25PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW DENIED:
  
 PROVIDE AN ENGINEER SIGNED/SEALED WIND LOAD DESIGN
 PRESSURES SHEET.
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN OR YOU CAN DELIVER AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  