Plan Review Details - Permit 22021179
Plan Review Stops For Permit 22021179
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-02-24 Cont ID  
Sent By cthroop Date 2022-02-24 Time 10:35 Rev Time 0.00
Received By cthroop Date 2022-02-24 Time 09:09 Sent To  
Notes
2022-02-24 10:40:05BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A
 SPAN OF 40 FEET OR GREATER IN ANY DIRECTION:
  
 A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE
 BASEPLATE/TIEDOWN DETAILS.
 B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE PER ASCE
 7-16.
  
 THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY
 A DESIGN PROFESSIONAL. (SEE SIGNATURE REVIEW COMMENTS)
  
 NO EXCEPTIONS BY ORDER OF THE BUILDING OFFICIAL
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. STATE ON SITE PLAN IF THE SIDES OF THE 20X40 TENT
 WILL BE OPEN. IF CLOSED, PROVIDE A LIFE SAFETY PLAN.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2022-02-24 Cont ID  
Sent By pleduc Date 2022-02-24 Time   Rev Time 0.00
Received By pleduc Date 2022-02-24 Time 14:52 Sent To  
Notes
2022-02-24 14:54:26THE TENTS ARE LESS THAN 900SQ FT, LIFE SAFETY REVIEW
 NOT REQUIRED BY FIRE,
  
 FS 633.202 - FLORIDA FIRE PREVENTION CODE. (17) A TENT
 UP TO 900 SQUARE FEET IS EXEMPT FROM THE FLORIDA FIRE
 PREVENTION CODE, INCLUDING THE NATIONAL CODES
 INCORPORATED BY REFERENCE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-23 Cont ID  
Sent By amcgrego Date 2022-02-23 Time 17:28 Rev Time  
Received By amcgrego Date 2022-02-23 Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-02-24 Cont ID  
Sent By cthroop Date 2022-02-24 Time 10:41 Rev Time 0.00
Received By cthroop Date 2022-02-24 Time 10:35 Sent To  
Notes
2022-02-24 10:42:47SIGNATURE REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 CFM
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 1ST REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: ENGINEERING WIND LOAD CALSC'S AND TIE DOWN DETAILS.
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  