Plan Review Details - Permit 22021171
Plan Review Stops For Permit 22021171
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-05-05 Cont ID  
Sent By rmcdouga Date 2022-05-05 Time 15:56 Rev Time 0.00
Received By rmcdouga Date 2022-05-05 Time 15:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-06 Cont ID  
Sent By rmcdouga Date 2022-04-06 Time 08:10 Rev Time 0.00
Received By rmcdouga Date 2022-04-06 Time 08:10 Sent To  
Notes
2022-04-06 08:13:47PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT GENERATOR PAD DRAWINGS WITH GENERATOR TO PAD
 ANCHORING DETAILS. IF A PREFABRICATED GENERATOR PAD
 WILL BE USED, SUBMIT SIGNED AND SEALED SITE SPECIFIC
 ENGINEERING FOR IT. FBC AMENDMENTS 107.2.1
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-03-21 Cont ID  
Sent By fgiaquin Date 2022-03-21 Time 21:05 Rev Time 0.00
Received By fgiaquin Date 2022-03-21 Time 20:28 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2022-05-11 Cont ID  
Sent By ccole Date 2022-05-11 Time 10:57 Rev Time 0.00
Received By ccole Date 2022-05-11 Time 10:29 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-05-05 Cont ID  
Sent By ccole Date 2022-05-05 Time 07:11 Rev Time 0.00
Received By ccole Date 2022-05-05 Time 07:01 Sent To  
Notes
2022-05-05 07:12:231ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22021171
 5/5/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. THE PERMIT APPLICATION
 CALLS FOR A SEPARATE PERMIT FOR GAS HOWEVER A
 SUB-PERMIT APPPICATION HAS NOW BEEN SUBMITTED. PLEASE
 COMPLY WITH THE COMMENTS BELOW.
  
 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES
 ALL NEW AND EXISTING GAS PIPING AND APPLIANCES AT THE
 RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES. REFER TO
 FBC RES. CHAPTER 24 FUEL GAS- THE RISER SHALL INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) SUBMIT CUT SHEETS FOR ALL EQUIPMENT RELATING TO THE
 GAS INSTALLATION SUCH AS REGULATORS, AND THE GENERATOR
 FLEX CONNECTOR- SECTIONS G2421.2 & G2422.1.2 FBC RES.
 PLEAE NOTE THE SUBMITTALS MAY BE DEFERRED AND BE ONSITE
 FOR INSPECTION- SEC. 107.3.4.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2022-04-08 Cont ID  
Sent By ccole Date 2022-04-08 Time 09:10 Rev Time 0.00
Received By ccole Date 2022-04-08 Time 09:07 Sent To  
Notes
2022-04-08 09:12:07CONTRACTOR REQUESTS GAS FOR THE GENERATOR TO BE UNDER A
 SEPARATE PERMIT.

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2022-03-10 Cont ID  
Sent By amhamilt Date 2022-03-10 Time 10:32 Rev Time 0.00
Received By amhamilt Date 2022-03-10 Time 10:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2022-05-11 Time   Rev Time 0.00
Received By aoliver Date 2022-05-07 Time 11:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-05 Cont ID  
Sent By rmcdouga Date 2022-05-05 Time 15:57 Rev Time 0.00
Received By rmcdouga Date 2022-04-10 Time 08:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-04-08 Time   Rev Time 0.00
Received By cdecoeur Date 2022-02-28 Time 06:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2022-05-11 Cont ID  
Sent By ccole Date 2022-05-11 Time 10:29 Rev Time 0.00
Received By ccole Date 2022-05-11 Time 10:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2022-05-05 Cont ID  
Sent By ccole Date 2022-05-05 Time 07:14 Rev Time 0.00
Received By ccole Date 2022-05-05 Time 07:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-04-08 Cont ID  
Sent By ccole Date 2022-04-08 Time 09:10 Rev Time 0.00
Received By ccole Date 2022-04-08 Time 09:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-05-11 Cont ID  
Sent By ccole Date 2022-05-11 Time 10:35 Rev Time 0.00
Received By ccole Date 2022-05-11 Time 10:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-05 Cont ID  
Sent By rmcdouga Date 2022-05-05 Time 15:57 Rev Time 0.00
Received By rmcdouga Date 2022-05-05 Time 15:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-04-06 Cont ID  
Sent By rmcdouga Date 2022-04-06 Time 08:08 Rev Time 0.00
Received By rmcdouga Date 2022-04-06 Time 08:08 Sent To  
Notes
2022-04-06 08:10:01THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 PREFABRICATED GENERATOR PADS. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT OR
 ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE
 OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF
 DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN
 APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15

Review Stop Z ZONING
Rev No 1 Status P Date 2022-03-07 Cont ID  
Sent By vbroglia Date 2022-03-07 Time 13:44 Rev Time 0.00
Received By vbroglia Date 2022-03-07 Time 13:44 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved