Plan Review Details - Permit 22021016
Plan Review Stops For Permit 22021016
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-03-11 Cont ID  
Sent By lcrespo Date 2022-03-11 Time 06:58 Rev Time 0.00
Received By lcrespo Date 2022-03-11 Time 06:58 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-02-23 Cont ID  
Sent By lcrespo Date 2022-02-23 Time 11:08 Rev Time 0.00
Received By lcrespo Date 2022-02-23 Time 11:08 Sent To  
Notes
2022-02-23 11:09:1001/18/22 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE PROVIDE MANUFACTURES SPECIFICATIONS
 FOR GAS TANKLESS, POOL HEATER, GENERATOR, AND COOK TOP
 EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC RES. SEC.
 G2408.1. GAS APPLIANCES SHALL BE LISTED AND LABELED.
 THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION PER THE 2020 FBC RES. SEC. G2413.2 AND
 G2404.3.
  
 2. A REGULATOR IS REQUIRED TO BRING THE SYSTEM DOWN TO
 10.5 WC ON THE TANKLESS HEATER, BUT THE FPU REGULATOR
 MAY STEP DOWN FOR THIS SYSTEM.
  
 3. THE SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT
 MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202)
 GD, ACCESS.
  
 4. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE
 403.5.3. WOULD YOU PLEASE NOTE ON PLANS. IF APPLICABLE.
  
 5. CONDENSATE FOR TANKLESS NEEDS TO BE 1' AWAY FROM THE
 STRUCTURE PER THE 2020 FBC SEC. R318.5. IF APPLICABLE.
 WOULD YOU PLEASE NOTE ON PLANS. IF APPLICABLE.
  
 6. WOULD YOU PLEASE SHOW AND LABEL ALL UNIONS IN FRONT
 OF REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES.
 SEC G2421.2.
  
 7. WOULD YOU PLEASE LABEL AND SHOW DRIP LEG ON
 EQUIPMENT INSTALLED, EXCEPT FOR APPLIANCES, RANGE,
 DRYERS & OD GRILLS PER THE 2020 FBC RES. SEC. G2419.2.
  
 8. WOULD YOU PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON
 GAS ISOMERIC PER THE 2020 FBC RES. SEC. G2420.5.
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-11 Cont ID  
Sent By lcrespo Date 2022-03-11 Time 06:58 Rev Time 0.00
Received By lcrespo Date 2022-03-10 Time 08:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-23 Cont ID  
Sent By lcrespo Date 2022-02-23 Time 11:22 Rev Time 0.00
Received By lcrespo Date 2022-02-22 Time 06:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-03-11 Cont ID  
Sent By lcrespo Date 2022-03-11 Time 06:58 Rev Time 0.00
Received By lcrespo Date 2022-03-11 Time 06:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-02-23 Cont ID  
Sent By lcrespo Date 2022-02-23 Time 11:06 Rev Time 0.00
Received By lcrespo Date 2022-02-23 Time 11:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-02-23 Cont ID  
Sent By lcrespo Date 2022-02-23 Time 11:06 Rev Time 0.00
Received By lcrespo Date 2022-02-23 Time 11:06 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved