Plan Review Details - Permit 22020687
Plan Review Stops For Permit 22020687
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-02-15 Cont ID  
Sent By pvalenti Date 2022-02-15 Time 11:26 Rev Time 0.00
Received By pvalenti Date 2022-02-15 Time 11:26 Sent To  
Notes
2022-02-15 11:30:00PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 FOR OPENINGS 3 & 4, IN ADDITION TO THE TOP
 TRUSSCONNECTIONSAT 24"O.C., CONNECTIONS TO 1/4" FLAT
 BAR ARE AT 6" O.C. AS PER PRODUCT APPROVAL FL 17080-R3
 SHEET 12 OF 13.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-02-12 Cont ID  
Sent By pvalenti Date 2022-02-12 Time 08:02 Rev Time 0.00
Received By pvalenti Date 2022-02-12 Time 07:42 Sent To  
Notes
2022-02-12 08:09:11PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, THE SUBMITTED SCHEDULE APPEARS TO BE
 INCOMPLETE. FOR OPENINGS 3 AND 4 AN ADDITIONAL NOTE
 SHOULD BE ADDED. THIS NOTE NEEDS TO CLARIFY THAT IN
 ADDITION TO THE TOP TRUSS CONNECTIONS AT 24" O.C.,
 CONNECTIONS TO 1/4" FLAT BAR ARE AT 6" O.C.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-12 Cont ID  
Sent By pvalenti Date 2022-02-12 Time 08:09 Rev Time 0.00
Received By pvalenti Date 2022-02-11 Time 16:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-02-12 Cont ID  
Sent By pvalenti Date 2022-02-12 Time 07:56 Rev Time 0.00
Received By pvalenti Date 2022-02-12 Time 07:42 Sent To  
Notes
2022-02-12 07:58:22PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW APPROVED BY SUBMITTED HAND
 SIGNED/SEALED PAPER WINDLOAD DOCUMENT.