Plan Review Details - Permit 22020571
Plan Review Stops For Permit 22020571
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-02-14 Cont ID  
Sent By cpuell Date 2022-02-14 Time 12:10 Rev Time 0.00
Received By cpuell Date 2022-02-14 Time 12:09 Sent To  
Notes
2022-02-14 12:10:37ADDRESS APPROPRIATE FOR PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-06-07 Cont ID  
Sent By shill Date 2022-06-07 Time 09:58 Rev Time 0.00
Received By shill Date 2022-06-07 Time 09:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-05-27 Cont ID  
Sent By jgomez Date 2022-05-27 Time 14:53 Rev Time 0.00
Received By jgomez Date 2022-05-27 Time 14:23 Sent To  
Notes
2022-05-27 14:57:49BUILDING REVIEW APPROVED WITH PROVISO (NOTE: PROVIDE
 INFORMATION PRIOR TO INSTALLATION/INSPECTION TO AVOID
 CONFLICTS/DELAYS):
 1- SHEETS S-102 AND S-201: ARCHITECT TO REVISE TOP
 CHORD DEAD LOAD FOR ROOF TRUSSES. 5 P.S.F. IS TOO LOW
 FOR CONCRETE ROOF TILE.
 2- SHEET A-201: ARCHITECT TO REVISE THE WALL PRESSURES
 TABLE. ULTIMATE WIND SPEED DESIGN PRESSURES ARE TOO
 LOW. REVISE ULTIMATE AND NOMINAL DESIGN PRESSURES.
 3- STAIRWAY CONSTRUCTION: PLANS DON'T PROVIDE STAIRWAY
 DIMENSIONS. NEED ALL THE STAIRWAY DIMENSIONS: WIDTH,
 LANDINGS, ETC.
 NOTE: ALSO, NOTE # 3 ON SHEET A-401 IS NO LONGER A CODE
 REQUIREMENT. THE SPECIFIED RISER AND TREAD DIMENSIONS
 DON'T COMPLY WITH THIS STATEMENT EITHER. REVISE AS
 REQUIRED.
 4- STAIR SECTION 1 ON SHEET A-401. REVISE FIREBLOCKING
 AT TOP OF STAIRS. 2X FIREBLOCKING AS SHOWN ON THIS
 SECTION DOESN'T PROVIDE FIREBLOCKING TO THE SECOND
 FLOOR AT THE TRIANGLE AREA.
 5- REVISED STRUCTURAL BUCK DETAILS ON SHEET A-202.
 2"X4" P.T. PLUS BLOCKING DOESN'T PROVIDE FULL SUPPORT
 TO THE DOOR FRAME.
 6- PROVIDE PRODUCT APPROVALS APPROVED BY ARCHITECT FOR:
 A)GARAGE EXTERIOR SWING DOOR. B)MASTER BEDROOM EXTERIOR
 SWING DOOR. C)ROOF TILE ADHESIVE LISTED IN ROOF TILE
 PRODUCT APPROVAL. D)ROOF TILE HIP & RIDGE METAL SUPPORT
 TO BE USED.
 7- PROVIDE DRAINAGE CERTIFICATE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-05-27 Cont ID  
Sent By jgomez Date 2022-05-27 Time 11:19 Rev Time 0.00
Received By jgomez Date 2022-05-26 Time 18:42 Sent To  
Notes
2022-05-27 11:21:01NEW SINGLE FAMILY RESIDENCE(R3) SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22020571
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 ***IMPORTANT***
 ENERGY CALCULATIONS NEED TO BE CERTIFIED BY THE OWNER
 OR AUTHORIZED AGENT BEFORE ISSUING THE PERMIT.
  
  
 1- ENERGY CALCULATIONS SUBMITTED:
 ORIGINAL COMMENT:
 A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING STREET ADDRESS OF JOB, OWNER'S NAME,
 BUILDER'S NAME AND JURISDICTION NUMBER (THIS
 JURISDICTION IS 604700). SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 ONLY THE STREET ADDRESS WAS PROVIDED.
  
 C)OK.
 D)OK.
  
 ORIGINAL COMMENT:
 E)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 2- DESIGNER OF RECORD TO SPECIFY ALL LIVE AND DEAD
 LOADS FOR SECOND FLOOR AND ROOF. CLEARLY SPECIFY SECOND
 FLOOR LIVE AND DEAD LOADS (TOP AND BOTTOM CHORDS) AND
 ROOF LIVE AND DEAD LOADS (TOP AND BOTTOM CHORDS),
 INCLUDING THE ATTIC LIVE LOAD AS REQUIRED BY TABLE
 R301.5 FBC-RESIDENTIAL. NOTE: SEE FOOTNOTES "B" AND
 "G".
  
 RESPONSE:
 ROOF TRUSSES INFORMATION ON SHEETS S-102 AND S-201
 SPECIFY 5 P.S.F. TOP CHORD DEAD LOAD FOR ROOF TRUSSES.
 THIS DESIGN LOAD IS TO LOW IF THE ROOF IS GOING TO
 RECEIVE CONCRETE TILE. REVISE AS REQUIRED. SEC. R301.4
 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 3-SHEET A-201: REVISE THE WINDOW DESIGN PRESSURES TO
 MATCH DESIGN PRESSURES SHOWN ON THE WALL PRESSURES
 (COMPONENT & CLADDING) TABLE ON SAME SHEET.
 NOTE: REVISE BASED ON WINDOW SIZE AND ZONE. SEC.
 R301.2.1 FBC-RESIDENTIAL.
 SEE FOOTNOTE "B" ON TABLE R301.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 WALL PRESSURES TABLE WERE REVISED AND ARE INCORRECT.
 THE ULTIMATE WIND SPEED DESIGN PRESSURES ARE TOO LOW.
 THEREFORE, THE NOMINAL WIND SPEED PRESSURES ARE
 INCORRECT ALSO. REVISE AS REQUIRED.
  
 4- OK.
  
 5- PROVIDE COMPLETE INFORMATION FOR STAIRWAY
 CONSTRUCTION:
 ORIGINAL COMMENT:
 A)PLANS DON'T PROVIDE STAIRWAY DIMENSIONS. SEC.
 R311.7.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. ONLY THE STAIR FLIGHT DIMENSIONS WERE
 GIVEN. NEED ALL THE STAIRWAY DIMENSIONS: WIDTH,
 LANDINGS, ETC.
  
 B) OK.
 C) OK.
  
 ORIGINAL COMMENT:
 D)SHEET A-401 NEED TO REFERENCE CORRECT CODE SECTIONS
 ON THE TYPICAL STAIR NOTES AND TYPICAL RAILING NOTES.
 SEE SEC. R311.7 FBC-RESIDENTIAL.
  
 RESPONSE:
 NOTE # 3 IS NO LONGER A CODE REQUIREMENT. ALSO, THE
 SPECIFIED RISER AND TREAD DIMENSIONS DON'T COMPLY WITH
 THIS STATEMENT EITHER. REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 E)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 FIREBLOCKING IN ALL THE AREAS REQUIRED BY SEC. R302.11
 FBC-RESIDENTIAL. NEED FIREBLOCKING AT TOP AND BOTTOM OF
 THE RUN.
 NOTE: FIREBLOCKING AND DRAFSTOPPING ARE TWO DIFFERENT
 THINGS. SEE SEC. R302.11 FBC-RESIDENTIAL AND SEC.
 R302.12 FBC-RESIDENTIAL.
  
 RESPONSE:
 STAIR SECTION 1 ON SHEET A-401. REVISE FIREBLOCKING AT
 TOP OF STAIRS. 2X FIREBLOCKING AS SHOWN ON THIS SECTION
 DOESN'T PROVIDE FULL FIREBLOCKING TO THE SECOND FLOOR
 AT THE TRIANGLE AREA. REVISE AS REQUIRED.
  
 6- OK.
 7- OK.
 8- OK.
  
 ORIGINAL COMMENT:
 9- REVISE DETAIL C ON SHEET A-202. STRUCTURAL BUCK
 NEEDS TO PROVIDE FULL SUPPORT TO THE DOOR FRAME AS
 REQUIRED BY SEC. R609.7.2.1 FBC-RESIDENTIAL. 2"X4" P.T.
 BUCK DOESN'T PROVIDE FULL SUPPORT TO THE DOOR FRAME.
 REVISE AS REQUIRED.
  
 RESPONSE:
 REVISED DETAIL STILL SHOWS 2X4 BUCK WITH PERPENDICULAR
 BLOCKING. THIS BLOCKING IS NOT ENOUGH TO PROVIDE FULL
 SUPPORT TO THE DOOR FRAME. SEE WALL SECTIONS AND
 TYPICAL BUCK DETAILS FOR SIZE OF BLOCKING OR FURRING
 STRIPS. REVISE AS REQUIRED.
  
 10- OK.
 11- OK.
 12- OK.
 13- OK.
  
 14-PROVIDE PRODUCT APPROVALS (FAC 61G20-3.001): NOTE:
 COORDINATE WITH REVISION REQUIRED ON ITEM #3 ABOVE THEN
 CHECK PRODUCT APPROVALS DESIGN PRESSURES AND RESUBMIT
 AS REQUIRED.
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)OK.
 B)GARAGE EXTERIOR SWING DOOR.
 C)MASTER BEDROOM EXTERIOR SWING DOOR.
 D)OK.
 E)OK.
 F)OK.
 G)OK.
 H)ROOF TILE ADHESIVE LISTED IN ROOF TILE PRODUCT
 APPROVAL.
 I)OK.
 J)OK.
 K)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED.
  
 NOTE: FLORIDA PRODUCT APPROVALS: NEED TO PROVIDE
 COMPLETE PRODUCT APPROVAL INCLUDING THE FLORIDA PRODUCT
 APPROVAL COVER PAGE.
 THIS PAGE IS REQUIRED BECAUSE IT SHOWS THE CURRENT CODE
 VERSION AND THE PRODUCT APPROVAL STATUS. CHAPTER 553
 F.S. AND FAC 61G20-3.001
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: COORDINATE PRODUCT APPROVAL SUBMITTAL AFFIDAVIT
 ON SHEET A-202 WITH ALL PRODUCT APPROVALS SUBMITTED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-05 Cont ID  
Sent By jgomez Date 2022-04-05 Time 14:32 Rev Time 0.00
Received By jgomez Date 2022-04-05 Time 10:34 Sent To  
Notes
2022-04-05 14:39:22NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22020571
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING STREET ADDRESS OF JOB, OWNER'S NAME,
 BUILDER'S NAME AND JURISDICTION NUMBER (THIS
 JURISDICTION IS 604700). SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 C)PROVIDE THE NAME OF THE PERSON DOING THE CALCULATIONS
 AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY CONSERVATION.
  
 D)ROOF MATERIAL SPECIFIED ON PAGE 2 IS INCORRECT. SEE
 PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 2- DESIGNER OF RECORD TO SPECIFY ALL LIVE AND DEAD
 LOADS FOR SECOND FLOOR AND ROOF. CLEARLY SPECIFY SECOND
 FLOOR LIVE AND DEAD LOADS (TOP AND BOTTOM CHORDS) AND
 ROOF LIVE AND DEAD LOADS (TOP AND BOTTOM CHORDS),
 INCLUDING THE ATTIC LIVE LOAD AS REQUIRED BY TABLE
 R301.5 FBC-RESIDENTIAL. NOTE: SEE FOOTNOTES "B" AND
 "G".
  
 3-SHEET A-201: REVISE THE WINDOW DESIGN PRESSURES TO
 MATCH DESIGN PRESSURES SHOWN ON THE WALL PRESSURES
 (COMPONENT & CLADDING) TABLE ON SAME SHEET.
 NOTE: REVISE BASED ON WINDOW SIZE AND ZONE. SEC.
 R301.2.1 FBC-RESIDENTIAL.
 SEE FOOTNOTE "B" ON TABLE R301.2.1 FBC-RESIDENTIAL
  
 4- SHEET A-202: PROVIDE DETAILS/SPECIFICATIONS FOR
 BALCONY FRAMED KNEE WALL. SPECIFY ALL FRAMING MEMBERS
 AND CONNECTORS. SPECIFY ALL WALL COMPONENTS/FINISHES.
 FASTENING. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 5- PROVIDE COMPLETE INFORMATION FOR STAIRWAY
 CONSTRUCTION:
 A)PLANS DON'T PROVIDE STAIRWAY DIMENSIONS. SEC.
 R311.7.1 FBC-RESIDENTIAL.
  
 B)CLEARLY SPECIFY TREAD DIMENSION. SEE SEC. R311.7.5.2
 FBC-RESIDENTIAL FOR PROPER WAY OF MEASURING TREAD.
  
 C)PROVIDE NOSING INFORMATION. SEC. R311.7.5.3
 FBC-RESIDENTIAL.
  
 D)SHEET A-401 NEED TO REFERENCE CORRECT CODE SECTIONS
 ON THE TYPICAL STAIR NOTES AND TYPICAL RAILING NOTES.
 SEE SEC. R311.7 FBC-RESIDENTIAL.
  
 E)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 FIREBLOCKING IN ALL THE AREAS REQUIRED BY SEC. R302.11
 FBC-RESIDENTIAL. NEED FIREBLOCKING AT TOP AND BOTTOM OF
 THE RUN.
 NOTE: FIREBLOCKING AND DRAFSTOPPING ARE TWO DIFFERENT
 THINGS. SEE SEC. R302.11 FBC-RESIDENTIAL AND SEC.
 R302.12 FBC-RESIDENTIAL.
  
 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF ALL NEW HANDRAILS AND GUARDRAILS,
 INCLUDING BALCONY GUARDRAIL SHOWING COMPLIANCE WITH
 TABLE R301.5, SEC. R311.7.8 AND SEC. R312.1
 FBC-RESIDENTIAL.
 NOTE: IF THIS IS A DEFERRED SUBMITTAL, THEN SPECIFY THE
 DESIGN GUIDELINES REQUIRED BY TABLE R301.5, SEC.
 R311.7.8 AND SEC. R312.1 AND CLEARLY SPECIFY ON PLANS
 THAT SHOP DRAWINGS NEED TO BE SUBMITTED FOR REVIEW
 PRIOR TO CONSTRUCTION. ALL SHOP DRAWINGS TO BE REVIEWED
 BY THE DESIGN PROFESSIONAL OF RECORD PRIOR TO SUBMITTAL
 TO THIS OFFICE.
  
 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 DRAFSTOPPING IN SECOND FLOOR AREAS AS REQUIRED BY SEC.
 R302.12 FBC-RESIDENTIAL.
  
 8- SHEET S-101: FOOTING SCHEDULE DOESN'T PROVIDE
 SPECIFICATIONS FOR FOOTING MF3 SHOWN ON THE FOUNDATION
 PLAN. PROVIDE INFORMATION. SEC. R301.1 FBC-RESIDENTIAL.
  
 9- REVISE DETAIL C ON SHEET A-202. STRUCTURAL BUCK
 NEEDS TO PROVIDE FULL SUPPORT TO THE DOOR FRAME AS
 REQUIRED BY SEC. R609.7.2.1 FBC-RESIDENTIAL. 2"X4" P.T.
 BUCK DOESN'T PROVIDE FULL SUPPORT TO THE DOOR FRAME.
 REVISE AS REQUIRED.
  
 10-REVISE ROOF SHEATHING NAILING TYPE, SIZE AND
 SPACING. NEED TO USE RING SHANK NAILS AND ROOF
 SHEATHING NEEDS TO BE NAILED WITH AT 4 INCHES O.C. IN
 THE FIELD AND EDGES AS REQUIRED BY SEC. R803.2.3.1 AND
 TABLE R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: ROOF SHEATHING SPECIFICATIONS ON DETAIL 2/S-301
 AND SPECIFICATIONS SHOWN ON THE DIAPHRAGM SCHEDULE ON
 SAME SHEET DON'T MATCH. REVISE AS REQUIRED AND REVISE
 ROOF SHEATHING SPECIFICATION SHOWN ON OTHER WALLS
 SECTIONS ON DIFFERENT SHEETS TO AVOID CONFLICT/DELAYS.
  
 11-SHOW ON PLANS CARBON MONOXIDE ALARMS BY ALL THE
 BEDROOMS AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 12- WIND RESISTANCE OF EXTERIOR SOFFITS: DESIGNER OF
 RECORD TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 FOR THE SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH
 SEC. R704 FBC-RESIDENTIAL.
  
 13- WINDOW FALL PROTECTION SHALL BE PROVIDED ON SECOND
 FLOOR WINDOWS WHERE THE TOP OF THE WINDOW SILL OF AN
 OPERABLE WINDOW IS LOCATED LESS THAN 24" ABOVE THE
 FINISHED FLOOR . SEC. R312.2 FBC RESIDENTIAL.
 NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT OF SECOND
 FLOOR WINDOWS AND SPECIFY TYPE OF WINDOW FALL
 PROTECTION IF REQUIRED.
 NOTE: WINDOWS LOCATED ON THE STAIRWAY NEED TO COMPLY
 WITH THE WINDOW FALL PROTECTION SEC. R312.2
 FBC-RESIDENTIAL. PROVIDE COMPLETE DETAIL AND
 SPECIFICATIONS SHOWING COMPLIANCE.
  
 14-PROVIDE PRODUCT APPROVALS (FAC 61G20-3.001): NOTE:
 COORDINATE WITH REVISION REQUIRED ON ITEM #3 ABOVE THEN
 CHECK PRODUCT APPROVALS DESIGN PRESSURES AND RESUBMIT
 AS REQUIRED.
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ENTRY DOOR WITH SIDELITES AS SHOWN ABOVE.
 B)GARAGE EXTERIOR SWING DOOR.
 C)MASTER BEDROOM EXTERIOR SWING DOOR.
 D)SINGLE HUNG WINDOWS.
 E)FIXED WINDOWS.
 F)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO AVOID DELAYS/CONFLICTS).
 G)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
 H)ROOF TILE ADHESIVE LISTED IN ROOF TILE PRODUCT
 APPROVAL.
 I)ROOF TILE UNDERLAYMENT.
 J)OVERHEAD GARAGE DOOR THAT MEETS THE SPECIFIED DESIGN
 PRESSURES.
 K)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED.
 L)BALCONY UNDERLAYMENT SPECIFIED ON PLANS TO RECEIVE
 TILE.
  
 NOTE: FLORIDA PRODUCT APPROVALS: NEED TO PROVIDE
 COMPLETE PRODUCT APPROVAL INCLUDING THE FLORIDA PRODUCT
 APPROVAL COVER PAGE.
 THIS PAGE IS REQUIRED BECAUSE IT SHOWS THE CURRENT CODE
 VERSION AND THE PRODUCT APPROVAL STATUS. CHAPTER 553
 F.S. AND FAC 61G20-3.001
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: COORDINATE PRODUCT APPROVAL SUBMITTAL AFFIDAVIT
 ON SHEET A-202 WITH ALL PRODUCT APPROVALS SUBMITTED.
  
 16- VALUATION WAS UPDATED TO $695,451.00 AS REQUIRED BY
 SEC. 109.3 CITY AMENDMENTS. VALUATION TO INCLUDE ALL
 LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND
 DESIGN PROFESSIONAL FEES. THE PERMIT FEE BALANCE IS
 $11,184.88
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-05-09 Cont ID  
Sent By fgiaquin Date 2022-05-09 Time 23:34 Rev Time 0.00
Received By fgiaquin Date 2022-05-09 Time 23:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-03-03 Cont ID  
Sent By fgiaquin Date 2022-03-03 Time 22:26 Rev Time 0.00
Received By fgiaquin Date 2022-03-03 Time 19:48 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2022-04-05 Cont ID  
Sent By lcrespo Date 2022-04-05 Time 14:47 Rev Time 0.00
Received By lcrespo Date 2022-04-05 Time 14:47 Sent To  
Notes
2022-02-15 09:58:15GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE, AND A GAS PLAN REVIEW HAS NOT
 BEEN PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND
 PLANS WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENT TO THE FBC
 SEC. 105.1.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-06-07 Cont ID  
Sent By shill Date 2022-06-07 Time 09:58 Rev Time 0.00
Received By shill Date 2022-05-31 Time 10:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-05-27 Cont ID  
Sent By jgomez Date 2022-05-27 Time 14:58 Rev Time 0.00
Received By jgomez Date 2022-05-27 Time 14:23 Sent To I
Notes
2022-05-27 14:23:50JUILO,
 SEE ATTACHED ENERGY CALCS FOR 245 ALHAMBRA PL.
 PLEASE PROCEED WITH THE PERMIT WITH THE PROVISIONS.
 --
 THANK YOU
 TERRIE SEPTOR
  
 SHAFFICK ALI ROUGH & FINISH CARPENTRY, INC.
 16756 62ND ROAD NORTH
 LOXAHATCHEE, FL 33470
  
 EMAIL: [email protected]
 OFFICE: 561-792-9284
 OFFICE FAX: 561-422-1891
 SHAFFICK CELL-561-722-7590
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-27 Cont ID  
Sent By jgomez Date 2022-05-27 Time 14:16 Rev Time 0.00
Received By jgomez Date 2022-04-21 Time 15:52 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-05 Cont ID  
Sent By jgomez Date 2022-04-05 Time 14:48 Rev Time 0.00
Received By jgomez Date 2022-02-14 Time 08:58 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-06-08 Cont ID  
Sent By lmarchan Date 2022-06-08 Time 16:26 Rev Time 0.00
Received By lmarchan Date 2022-06-07 Time 09:13 Sent To  
Notes
2022-06-08 15:37:24RECEIPT MU-2022-026079 -$2404.37 PAID
  
2022-06-07 09:14:036/7/22 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-04-05 Cont ID  
Sent By jgomez Date 2022-04-05 Time 14:48 Rev Time 0.00
Received By jgomez Date 2022-04-05 Time 14:48 Sent To  
Notes
2022-04-05 14:48:53IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-05-04 Cont ID  
Sent By medwards Date 2022-05-04 Time 10:55 Rev Time 0.00
Received By medwards Date 2022-05-04 Time 10:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-02-28 Cont ID  
Sent By medwards Date 2022-02-28 Time 06:49 Rev Time 0.00
Received By medwards Date 2022-02-28 Time 06:03 Sent To  
Notes
2022-02-28 06:49:461ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22020571
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROJECT NAME LISTED ON THE ENERGY CALCULATIONS IS
 ALL RESIDENCE. PLEASE BE SPECIFIC TO THE ACTUAL PROJECT
 AND ADDRESS OF THE PROJECT. FBC 107.2.1
  
 2) PROJECT NAME LISTED ON THE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS IS ALL RESIDENCE. PLEASE BE
 SPECIFIC TO THE ACTUAL PROJECT AND ADDRESS OF THE
 PROJECT. FBC 107.2.1
  
 3) THE DUCTWORK SERVING THE MASTER SUITE AREA IS
 MISSING A MAIN TRUNK LINE. PLEASE SHOW THE TRUNK LINE
 ALONG WITH THE SIZE OF THIS TRUNK LINE. FBC 107.2.1
  
 4) PROVIDE THE CFM?S OF THE KITCHEN HOOD EXHAUST. FBC
 RES M1503.4
  
 5) PLEASE SHOW THE DRYER EXHAUST DUCT AND TERMINATION
 LOCATION FOR THE LAUNDRY ROOM ON THE 2ND FLOOR. FBC RES
 M1502 AND 1503
  
 6) PLEASE SHOW THE CONDENSATE DRAIN AND TERMINATION
 LOCATIONS FOR BOTH MECHANICAL SYSTEMS. FBC RES M1411.3
  
 7) THE DESIGNER OF THE MECHANICAL DRAWING MUST WRITE
 AND SIGN THEIR NAME ON THE DRAWING.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-04-27 Cont ID  
Sent By lcrespo Date 2022-04-27 Time 10:38 Rev Time 0.00
Received By lcrespo Date 2022-04-27 Time 10:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-02-15 Cont ID  
Sent By lcrespo Date 2022-02-15 Time 09:51 Rev Time 0.00
Received By lcrespo Date 2022-02-15 Time 09:51 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2022-05-27 Cont ID  
Sent By jgomez Date 2022-05-27 Time 14:02 Rev Time 0.00
Received By jgomez Date 2022-05-27 Time 11:23 Sent To  
Notes
2022-05-27 14:04:55PROVISO:
 1-PROVIDE PRODUCT APPROVALS FOR:
 A) ROOF TILE ADHESIVE LISTED IN ROOF TILE PRODUCT
 APPROVAL.
 B) ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS.
  
 APPROVED:
 A) ROOF TILE NOA 21-0420.04
 B) ROOF TILE UNDERLAYMENT NOA 18-0502.03.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-04-05 Cont ID  
Sent By jgomez Date 2022-04-05 Time 14:44 Rev Time 0.00
Received By jgomez Date 2022-04-05 Time 14:43 Sent To  
Notes
2022-04-05 14:46:27ROOFING REVIEW
  
 1-PROVIDE PRODUCT APPROVALS (FAC 61G20-3.001): NOTE:
 COORDINATE WITH REVISION REQUIRED ON ITEM #3 ABOVE THEN
 CHECK PRODUCT APPROVALS DESIGN PRESSURES AND RESUBMIT
 AS REQUIRED.
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
 B)ROOF TILE ADHESIVE LISTED IN ROOF TILE PRODUCT
 APPROVAL.
 C)ROOF TILE UNDERLAYMENT.
 D) ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED.
 E)BALCONY UNDERLAYMENT SPECIFIED ON PLANS TO RECEIVE
 TILE.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: COORDINATE PRODUCT APPROVAL SUBMITTAL AFFIDAVIT
 ON SHEET A-202 WITH ALL PRODUCT APPROVALS SUBMITTED.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-06-07 Cont ID  
Sent By shill Date 2022-06-07 Time 09:55 Rev Time 0.00
Received By shill Date 2022-06-07 Time 09:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-05-27 Cont ID  
Sent By jgomez Date 2022-05-27 Time 14:16 Rev Time 0.00
Received By jgomez Date 2022-05-27 Time 14:11 Sent To  
Notes
2022-05-27 14:16:36SIGNATURE REVIEW:
  
 1- SURVEY SUBMITTED NEEDS SURVEYOR'S ORIGINAL
 SEAL/SIGNATURE AS REQUIRED BY CHAPTER 472 F.S. WHEN
 SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
  
 NOTE: SUBMIT SURVEY ELECTRONICALLY WITH SURVEYOR'S
 DIGITAL SIGNATURE OR PROVIDE HARD COPY WITH SURVEYOR'S'
 ORIGINAL SEAL AND SIGNATURE.
  
  
2022-05-04 10:56:11MECHANICAL DIGITAL SIGNATURE NOT REQUIRED. ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-04-04 Cont ID  
Sent By jgomez Date 2022-04-04 Time 14:59 Rev Time 0.00
Received By jgomez Date 2022-04-04 Time 14:59 Sent To  
Notes
2022-04-04 15:00:32SIGNATURE REVIEW:
  
 1- SURVEY SUBMITTED NEEDS SURVEYOR'S ORIGINAL
 SEAL/SIGNATURE AS REQUIRED BY CHAPTER 472 F.S. WHEN
 SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
 NOTE: SUBMIT SURVEY ELECTRONICALLY WITH SURVEYOR'S
 DIGITAL SIGNATURE OR PROVIDE HARD COPY WITH SURVEYOR'S'
 ORIGINAL SEAL AND SIGNATURE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2022-06-06 Cont ID  
Sent By kdefranc Date 2022-06-06 Time 16:32 Rev Time 0.00
Received By kdefranc Date 2022-06-06 Time 16:29 Sent To  
Notes
2022-06-06 16:30:476/6/22 ? PASSED
  
 REVIEW COMMENTS TO BE ADDRESSED:
 1. PLEASE IDENTIFY/INDICATE/DEMONSTRATE CONSISTENT
 SETBACKS FOR THE PROPOSED PRINCIPAL BUILDING (?HOUSE?)
 ON THE SURVEY AND SITE PLAN. [SATISFIED]
 A. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE SETBACKS
 FOR THE PROPOSED MECHANICAL EQUIPMENT (SUCH AS THE
 ?POOL PUMP & FILTER, GAS POOL HEATER, AND A/C?S #1 AND
 2?). [SATISFIED]
 2. PLEASE IDENTIFY/INDICATE/DEMONSTRATE A CONSISTENT
 HEIGHT OF THE PROPOSED PRINCIPAL BUILDING (?HOUSE?) ON
 THE SITE PLAN AND ELEVATIONS. [SATISFIED]
  
 ADDITIONAL REVIEW COMMENTS (THAT REQUIRE A SEPARATE
 PERMIT) TO BE ADDRESSED:
 1. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE WIDTH OF
 THE PROPOSED DRIVEWAY ON THE SITE PLAN. [SATISFIED]
 2. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE PROPOSED
 FENCE OR SIMILAR STRUCTURE THAT WILL ENCLOSE THE POOL
 ON THE SITE PLAN. IDENTIFY/INDICATE THE HEIGHT OF THE
 PROPOSED FENCE OR SIMILAR STRUCTURE THAT WILL ENCLOSE
 THE POOL ON THE SITE PLAN. [SATISFIED]
 3. PLEASE SUBMIT A LANDSCAPE PERMIT APPLICATION OR A
 LANDSCAPE CONDITIONAL APPROVAL PERMIT FORM. [SATISFIED]
  
  
 KEVIE DEFRANC
 PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1200
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-04-28 Cont ID  
Sent By kdefranc Date 2022-04-28 Time 16:23 Rev Time 0.00
Received By kdefranc Date 2022-04-28 Time 16:22 Sent To  
Notes
2022-04-28 16:22:484/28/22 ? FAILED
  
 REVIEW COMMENTS TO BE ADDRESSED:
 1. PLEASE IDENTIFY/INDICATE/DEMONSTRATE CONSISTENT
 SETBACKS FOR THE PROPOSED PRINCIPAL BUILDING (?HOUSE?)
 ON THE SURVEY AND SITE PLAN. [NOT SATISFIED]
 A. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE SETBACKS
 FOR THE PROPOSED MECHANICAL EQUIPMENT (SUCH AS THE
 ?POOL PUMP & FILTER, GAS POOL HEATER, AND A/C?S #1 AND
 2?). [NOT SATISFIED]
 2. PLEASE IDENTIFY/INDICATE/DEMONSTRATE A CONSISTENT
 HEIGHT OF THE PROPOSED PRINCIPAL BUILDING (?HOUSE?) ON
 THE SITE PLAN AND ELEVATIONS. [NOT SATISFIED]
  
 ADDITIONAL REVIEW COMMENTS (THAT REQUIRE A SEPARATE
 PERMIT) TO BE ADDRESSED:
 1. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE WIDTH OF
 THE PROPOSED DRIVEWAY ON THE SITE PLAN. [NOT SATISFIED]
 2. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE PROPOSED
 FENCE OR SIMILAR STRUCTURE THAT WILL ENCLOSE THE POOL
 ON THE SITE PLAN. IDENTIFY/INDICATE THE HEIGHT OF THE
 PROPOSED FENCE OR SIMILAR STRUCTURE THAT WILL ENCLOSE
 THE POOL ON THE SITE PLAN. [NOT SATISFIED]
 3. PLEASE SUBMIT A LANDSCAPE PERMIT APPLICATION OR A
 LANDSCAPE CONDITIONAL APPROVAL PERMIT FORM. [SATISFIED]
  
  
 KEVIE DEFRANC
 PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1200
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-02-18 Cont ID  
Sent By kdefranc Date 2022-02-18 Time 15:54 Rev Time 0.00
Received By kdefranc Date 2022-02-18 Time 15:53 Sent To  
Notes
2022-02-18 15:54:472/18/22 ? FAILED
  
 REVIEW COMMENTS TO BE ADDRESSED:
 1. PLEASE IDENTIFY/INDICATE/DEMONSTRATE CONSISTENT
 SETBACKS FOR THE PROPOSED PRINCIPAL BUILDING (?HOUSE?)
 ON THE SURVEY AND SITE PLAN.
 A. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE SETBACKS
 FOR THE PROPOSED MECHANICAL EQUIPMENT (SUCH AS THE
 ?POOL PUMP & FILTER, GAS POOL HEATER, AND A/C?S #1 AND
 2?).
 2. PLEASE IDENTIFY/INDICATE/DEMONSTRATE A CONSISTENT
 HEIGHT OF THE PROPOSED PRINCIPAL BUILDING (?HOUSE?) ON
 THE SITE PLAN AND ELEVATIONS.
  
 ADDITIONAL REVIEW COMMENTS (THAT REQUIRE A SEPARATE
 PERMIT) TO BE ADDRESSED:
 1. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE WIDTH OF
 THE PROPOSED DRIVEWAY ON THE SITE PLAN.
 2. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE PROPOSED
 FENCE OR SIMILAR STRUCTURE THAT WILL ENCLOSE THE POOL
 ON THE SITE PLAN. IDENTIFY/INDICATE THE HEIGHT OF THE
 PROPOSED FENCE OR SIMILAR STRUCTURE THAT WILL ENCLOSE
 THE POOL ON THE SITE PLAN.
 3. PLEASE SUBMIT A LANDSCAPE PERMIT APPLICATION OR A
 LANDSCAPE CONDITIONAL APPROVAL PERMIT FORM.
  
  
 KEVIE DEFRANC
 PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1200
  