Plan Review Details - Permit 22020523
Plan Review Stops For Permit 22020523
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-04-08 Cont ID  
Sent By rmcdouga Date 2022-04-08 Time 08:29 Rev Time 0.00
Received By rmcdouga Date 2022-04-07 Time 17:28 Sent To  
Notes
2022-04-08 08:32:02A SIGNED AND SEALED COPY OF THE TEST PILE REPORT THAT
 HAS BEEN REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD FOR THE PROJECT IS REQUIRED TO BE SUBMITTED WITH
 THE FOUNDATION PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-16 Cont ID  
Sent By rmcdouga Date 2022-03-16 Time 11:28 Rev Time 0.00
Received By rmcdouga Date 2022-03-16 Time 10:19 Sent To  
Notes
2022-03-16 10:50:37PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) DURING THE DEMOLITION PROCESS TRUCKS WILL BE
 ENTERING AND LEAVING THE SITE. BANYAN AND OLIVE IS A
 HIGH TRAFFIC AREA. YOU WILL NEED TO SUBMIT A MOT PLAN
 FOR REVIEW AND APPROVAL.FBC 3306
  
 2) A SEPARATE PERMIT WILL BE REQUIRED TO INSTALL THE
 REQUIRED TEMPORARY CONSTRUCTION FENCE. FBC 3306

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-03-17 Cont ID  
Sent By fgiaquin Date 2022-03-17 Time 23:42 Rev Time 0.00
Received By fgiaquin Date 2022-03-17 Time 23:42 Sent To  
Notes
2022-03-17 23:43:06ELEC DEMO APPLICATION RECEIVED AND UPLOADED TO PROJECT
 DOCS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-03-09 Cont ID  
Sent By fgiaquin Date 2022-03-09 Time 20:22 Rev Time 0.00
Received By fgiaquin Date 2022-03-09 Time 19:01 Sent To  
Notes
2022-03-09 20:22:06ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AN APPLICATION FOR ELECTRICAL DEMO IS REQUIRED BY
 LICENSED ELECTRICIAN. YOU CAN EMAIL APPLICATION TO
 [email protected] OR [email protected]. WHEN ELECTRICAL
 APPLICATION IS ON FILE FAILED PLAN REVIEW WILL BE
 CHANGED TO A PASS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 1 Status P Date 2022-03-09 Cont ID  
Sent By rrossano Date 2022-03-09 Time   Rev Time 0.00
Received By rrossano Date 2022-03-09 Time   Sent To  
Notes
2022-03-09 18:26:34PASSED WITH PROVISO:
  
 CALL FOR LOCATES, DIAL 811 BEFORE YOU DIG. FOR MORE
 INFO ON "CALL BEFORE YOU DIG", GO TO
 HTTP://WWW.SUNSHINE811.COM (REF: UNDERGROUND FACILITY
 DAMAGE PREVENTION AND SAFETY ACT, FLORIDA STATUTE,
 CHAPTER 556.)
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORDINATOR,
 CITY OF WPB ENGINEERING SERVICES DEPARTMENT
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING/ENGINEERING-
 STANDARDS-DETAILS
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-04-04 Cont ID  
Sent By pleduc Date 2022-04-04 Time   Rev Time 0.00
Received By pleduc Date 2022-04-04 Time 10:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-02-18 Cont ID  
Sent By pleduc Date 2022-02-18 Time   Rev Time 0.00
Received By pleduc Date 2022-02-18 Time 10:42 Sent To  
Notes
2022-02-18 10:46:31THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE INSTALL OF PERIMETER
 FENCING AND SIGNAGE.
  
 THERE IS LIMITED DETAIL OF THE FENCING TYPE AND
 LOCATION AND NO INDICATION OF THE ENTRY/EXIT GATES
 INCLUDING OPENING WIDTH.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE MORE DETAIL OF
 THE FENCE LOCATION, IF ANY FIRE HYDRANTS ARE BEING
 BLOCKED, GATE LOCATION AND GATE WIDTHS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-11 Cont ID  
Sent By aoliver Date 2022-04-11 Time 06:49 Rev Time 0.00
Received By aoliver Date 2022-04-01 Time 09:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-16 Cont ID  
Sent By rmcdouga Date 2022-03-16 Time 11:28 Rev Time 0.00
Received By rmcdouga Date 2022-02-15 Time 05:54 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-10-11 Cont ID  
Sent By shill Date 2022-10-11 Time 11:22 Rev Time 0.00
Received By shill Date 2022-10-11 Time 11:22 Sent To  
Notes
2022-10-11 11:22:39MASTER
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-04-08 Cont ID  
Sent By rmcdouga Date 2022-04-08 Time 08:49 Rev Time 0.00
Received By rmcdouga Date 2022-04-08 Time 08:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-03-16 Cont ID  
Sent By rmcdouga Date 2022-03-16 Time 11:28 Rev Time 0.00
Received By rmcdouga Date 2022-03-16 Time 10:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-04-08 Cont ID  
Sent By ckimmerl Date 2022-04-08 Time 11:44 Rev Time 0.00
Received By ckimmerl Date 2022-04-08 Time 11:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-03-11 Cont ID  
Sent By aaponte Date 2022-03-11 Time 09:24 Rev Time 0.00
Received By aaponte Date 2022-03-11 Time 09:24 Sent To  
Notes
***NONE***