Plan Review Details - Permit 22020251
Plan Review Stops For Permit 22020251
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2023-07-14 Cont ID  
Sent By jgomez Date 2023-07-14 Time 14:24 Rev Time 0.00
Received By jgomez Date 2023-07-14 Time 14:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2023-07-07 Cont ID  
Sent By jgomez Date 2023-07-07 Time 18:18 Rev Time 0.00
Received By jgomez Date 2023-07-07 Time 15:50 Sent To  
Notes
2023-07-07 18:19:12ROOFING BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22020251
 201 DYER RD (TERRACE)
  
 PREVIOUS COMMENT FROM PREVIOUS PLAN REVIEWER:
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R10 SELECTED OPTION FOR SYSTEM NO W-4;
 EXPOSURE (C); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15);
 ULTIMATE WIND SPEED (170), IS NOT CORRECT. THE CORRECT
 EXPOSURE FOR THE LISTED ADDRESS IS EXPOSURE D. PLEASE
 SELECT THE CORRECT OPTIONS. PRODUCT APPROVAL
 FL16709-R10 WILL NOT SATISFY EXPOSURE CATEGORY D
 ENCLOSED AREAS WITHOUT USING INSULATION.
  
 RESPONSE:
 ENGINEERING CALCULATIONS SUBMITTED:
 A)ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL, THIS
 BUILDING IS LOCATED IN EXPOSURE "D" NOT "C". ENGINEER
 TO REVISE CALCULATIONS AS REQUIRED. (REPEAT COMMENT
 FROM PREVIOUS PLAN REVIEWER).
  
 B)PROVIDE ROOF SKETCH SHOWING THE DIMENSIONS FOR EACH
 NEW ROOF ZONE.
 FIGURE R301.2(7)FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 C)ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 2-DESIGNER OF RECORD FOR MASTER PERMIT NEEDS TO REVIEW
 AND APPROVE IN WRITING (NOT SIGNING AND SEALING) ALL
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2022-09-15 Cont ID  
Sent By jbrooks Date 2022-09-15 Time 14:36 Rev Time 0.00
Received By jbrooks Date 2022-09-15 Time 14:24 Sent To  
Notes
2022-09-15 14:37:05JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R10 SELECTED OPTION FOR SYSTEM NO W-4;
 EXPOSURE (C); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15);
 ULTIMATE WIND SPEED (170), IS NOT CORRECT. THE CORRECT
 EXPOSURE FOR THE LISTED ADDRESS IS EXPOSURE D. PLEASE
 SELECT THE CORRECT OPTIONS. PRODUCT APPROVAL
 FL16709-R10 WILL NOT SATISFY EXPOSURE CATEGORY D
 ENCLOSED AREAS WITHOUT USING INSULATION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2022-08-24 Cont ID  
Sent By jbrooks Date 2022-08-24 Time 09:46 Rev Time 0.00
Received By jbrooks Date 2022-08-24 Time 07:39 Sent To  
Notes
2022-08-24 09:46:32JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R10 SELECTED OPTION FOR SYSTEM NO W-5
 EXPOSURE (D); ENCLOSURE (ENCLOSED); ROOF HEIGHT (15 H <
 20); ULTIMATE WIND SPEED (180). ZONE 3 IS MARKED ?N/A?
 WHICH INDICATES SYSTEM IS ?NOT APPLICABLE? TO ZONE1
 PRIME DESIGN PRESSURE REQUIREMENTS AND CANNOT BE USED.
 PLEASE PROVIDE 2020 CODE VERSION PRODUCT APPROVAL/NOA
 THAT MEETS OR EXCEEDS DESIGN PRESSURE REQUIREMENTS FOR
 EXPOSURE D AREAS. SIGNED AND SEALED NAILING
 CALCULATIONS MAY BE REQUIRED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2022-08-01 Cont ID  
Sent By jbrooks Date 2022-08-01 Time 13:28 Rev Time 0.00
Received By jbrooks Date 2022-08-01 Time 07:56 Sent To  
Notes
2022-08-01 13:28:32JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.3.4.1. SUBMITTED MIAMI-DADE COUNTY NOA
 NO.: 18-0502.03, MIAMI-DADE COUNTY NOA NO.: 19-0814.02,
 MIAMI-DADE COUNTY NOA NO.: 20-0714.01, MIAMI-DADE
 COUNTY NOA NO.: 22-0411.02 & PRODUCT APPROVAL FL5374-R6
 SHALL BE SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A
 NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. ALL SUBMITTED PRODUCT
 APPROVALS/NOA?S MUST BE SIGNED BY THE
 ARCHITECT/ENGINEER AND THEN UPLOADED INTO YOUR FILE
 BEFORE PERMIT APPLICATION CAN BE APPROVED. FIFTH
 REQUEST.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-07-26 Cont ID  
Sent By jbrooks Date 2022-07-26 Time 11:55 Rev Time 0.00
Received By jbrooks Date 2022-07-26 Time 08:09 Sent To  
Notes
2022-07-26 11:55:37JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL5374-R6 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT).
 2. FBC B 107.3.4.1. SUBMITTED MIAMI-DADE COUNTY NOA
 NO.: 18-0502.03, MIAMI-DADE COUNTY NOA NO.: 19-0814.02,
 MIAMI-DADE COUNTY NOA NO.: 20-0714.01, MIAMI-DADE
 COUNTY NOA NO.: 22-0411.02 & PRODUCT APPROVAL FL5374-R6
 SHALL BE SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A
 NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-03-22 Cont ID  
Sent By jbrooks Date 2022-03-22 Time 14:04 Rev Time 0.00
Received By jbrooks Date 2022-03-22 Time 08:43 Sent To  
Notes
2022-03-22 14:05:00JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC B 107.2.1. PLEASE PROVIDE ENGINEER'S SIGNED AND
 SEALED FASTENER SPACING DETAIL WITH CALCULATIONS FOR
 PERIMETERS AND CORNERS AS PER PRODUCT APPROVAL
 LIMITATIONS #7. PLEASE NOTE THIS PROJECT IS LOCATED IN
 AN EXPOSURE D CATEGORY AREA. SECOND REQUEST.
 2. FBC B 107.3.4.1. SUBMITTED MIAMI-DADE COUNTY NOA
 NO.:19-0311.04 SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. THIRD REQUEST.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-02-24 Cont ID  
Sent By jbrooks Date 2022-02-24 Time 11:11 Rev Time 0.00
Received By jbrooks Date 2022-02-24 Time 07:46 Sent To  
Notes
2022-02-24 11:12:24JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC B 107.2.1. PLEASE PROVIDE ENGINEER'S SIGNED AND
 SEALED FASTENER SPACING DETAIL WITH CALCULATIONS FOR
 PERIMETERS AND CORNERS AS PER PRODUCT APPROVAL
 LIMITATIONS #7. PLEASE NOTE THIS PROJECT IS LOCATED IN
 AN EXPOSURE D CATEGORY AREA.
 2. FBC B 107.3.4.1. SUBMITTED MIAMI-DADE COUNTY NOA
 NO.:19-0311.04 SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-02-08 Cont ID  
Sent By jbrooks Date 2022-02-08 Time 08:31 Rev Time 0.00
Received By jbrooks Date 2022-02-08 Time 07:23 Sent To  
Notes
2022-02-08 08:32:04JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED FLAT ROOF SYSTEM TO BE
 USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 2. FBC B 107.3.4.1. SUBMIT MISSING PRODUCT APPROVAL/NOA
 FOR THE PROPOSED FLAT ROOF SYSTEM TO BE USED SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST
 BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2023-07-14 Cont ID  
Sent By jgomez Date 2023-07-14 Time 14:26 Rev Time 0.00
Received By jgomez Date 2023-07-14 Time 14:10 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2023-07-07 Cont ID  
Sent By jgomez Date 2023-07-07 Time 18:21 Rev Time 0.00
Received By jgomez Date 2023-07-07 Time 15:50 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2022-09-16 Cont ID  
Sent By lmarchan Date 2022-09-16 Time 09:34 Rev Time 0.00
Received By lmarchan Date 2022-09-15 Time 07:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2022-08-24 Cont ID  
Sent By jbrooks Date 2022-08-24 Time 09:47 Rev Time 0.00
Received By jbrooks Date 2022-08-15 Time 15:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-08-01 Cont ID  
Sent By jbrooks Date 2022-08-01 Time 13:28 Rev Time 0.00
Received By jbrooks Date 2022-07-26 Time 16:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-07-26 Cont ID  
Sent By jbrooks Date 2022-07-26 Time 11:55 Rev Time 0.00
Received By jbrooks Date 2022-07-19 Time 08:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-22 Cont ID  
Sent By jbrooks Date 2022-03-22 Time 14:05 Rev Time 0.00
Received By jbrooks Date 2022-03-20 Time 09:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-24 Cont ID  
Sent By jbrooks Date 2022-02-24 Time 11:12 Rev Time 0.00
Received By jbrooks Date 2022-02-14 Time 06:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-08 Cont ID  
Sent By jbrooks Date 2022-02-08 Time 08:32 Rev Time 0.00
Received By jbrooks Date 2022-02-07 Time 06:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-07-14 Cont ID  
Sent By jgomez Date 2023-07-14 Time 14:25 Rev Time 0.00
Received By jgomez Date 2023-07-14 Time 14:10 Sent To  
Notes
2023-07-14 14:25:59ENGINEER CALCULATIONS WITH ENGINEER'S WET SIGNATURE.
 JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-07-07 Cont ID  
Sent By jgomez Date 2023-07-07 Time 18:20 Rev Time 0.00
Received By jgomez Date 2023-07-07 Time 18:19 Sent To  
Notes
2023-07-07 18:21:53SIGNATURE REVIEW COMMENTS:
  
 ENGINEERING CALCULATIONS SUBMITTED:
  
 1-ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  