Plan Review Details - Permit 22020144
Plan Review Stops For Permit 22020144
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-03-01 Cont ID  
Sent By jwitmer Date 2022-03-01 Time 16:19 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-02-23 Cont ID  
Sent By jwitmer Date 2022-02-23 Time 09:00 Rev Time 0.00
Received By jwitmer Date 2022-02-23 Time 08:11 Sent To  
Notes
2022-02-23 09:00:07COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-03-16 Cont ID  
Sent By jwitmer Date 2022-03-16 Time 08:44 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-03-16 08:44:00PASSED BUT STAMP WILL NOT BE PLACED ON THE PLANS UNTIL
 CONTRACTOR SIGNATURE, PRINTED NAME AND LICENSE NUMBER
 ON PLANS.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 REQUIRES THE CONTRACTOR FOR THAT TRADE THAT WILL BE
 LICENSED IN THAT TRADE, WILL ALSO BE THE CONTRACTOR
 THAT DESIGNS THE SYSTEM UNDER THAT TRADE. THE
 CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF
 PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF
 THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-03-01 Cont ID  
Sent By jwitmer Date 2022-03-01 Time 16:18 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-02-23 Cont ID  
Sent By jwitmer Date 2022-02-23 Time 08:59 Rev Time 0.00
Received By jwitmer Date 2022-02-23 Time 08:11 Sent To  
Notes
2022-02-23 08:59:10WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22020144
 ADD: 300 CLEMATIS ST. # 2
 CONT: BUILTMORE CONTRACTING
 TEL: 561-331-1476
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 23RD/ 2022
 ACTION: DENIED
  
 1) FLOOR PLAN
 1A) 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE
 THE EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 REQUIRES THE CONTRACTOR FOR THAT TRADE THAT WILL BE
 LICENSED IN THAT TRADE, WILL ALSO BE THE CONTRACTOR
 THAT DESIGNS THE SYSTEM UNDER THAT TRADE. THE
 CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF
 PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF
 THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 1B) THE FLOOR PLAN DOES NOT PROVIDE AN ADDRESS WHERE
 WORK IS TO OCCUR.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED.
  
 2020 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 1C) ADDITIONAL INFORMATION IS REQUIRED. THE PERMIT
 APPLICATION INDICATES OFFICE ALTERATION AND A VALUE OF
 $4,000.00 DOLLARS. THE SUBMITTED FLOOR PLAN HAS VARIOUS
 LOCATIONS WITH REVISION 1 HIGHLIGHTED, PLEASE PROVIDE A
 SCOPE OF WORK/ NARRATIVE WHAT IS COVERED UNDER THIS
 PERMIT.
  
 1D) THERE ARE DETAIL MARKERS ON THIS PLAN A/ A3.01, B/
 A3.01 THESE PAGES ARE NOT INCLUDED IN THE SUBMITTED
 FLOOR PLAN.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 1E) WHAT APPEARS AS NEW WORK JUST TO THE LEFT OF OFFICE
 229 THERE ARE DASHED LINE BUT THERE IS WORDING OPEN
 WORK STATION. DOES THIS MEAN THE WALLS ARE BEING
 REMOVED AND A NEW WORK STATION IS BEING CREATED?
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1F) WHAT APPEARS AS NEW WORK JUST TO THE LEFT OF OFFICE
 229 THERE ARE DASHED LINE WITH A INTERIOR SWING DOOR.
 JUST TO THE RIGHT OF THE DOOR JAMB ON THE INTERIOR SIDE
 THERE IS A RED BOX WITH A ?S? DOES THIS STAND FOR
 EITHER A LIGHT SWITCH OR ELECTRICAL OUTLET THAT IS
 SWITCHED.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
2022-02-23 08:12:17IN REVIEW. JW

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-03-31 Cont ID  
Sent By fgiaquin Date 2022-03-31 Time 20:41 Rev Time 0.00
Received By fgiaquin Date 2022-03-31 Time 19:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-03-11 Cont ID  
Sent By fgiaquin Date 2022-03-11 Time 23:49 Rev Time 0.00
Received By fgiaquin Date 2022-03-11 Time 23:42 Sent To  
Notes
2022-03-11 23:49:51PLAN NOT SIGNED AS PER LAST PLAN REVIEW COMMENTS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-02-22 Cont ID  
Sent By fgiaquin Date 2022-02-22 Time 23:44 Rev Time 0.00
Received By fgiaquin Date 2022-02-22 Time 21:15 Sent To  
Notes
2022-02-22 23:44:22ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-03-16 Cont ID  
Sent By pleduc Date 2022-03-16 Time   Rev Time 0.00
Received By pleduc Date 2022-03-16 Time 13:00 Sent To  
Notes
2022-03-16 13:01:44FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-02-28 Cont ID  
Sent By pleduc Date 2022-02-28 Time   Rev Time 0.00
Received By pleduc Date 2022-02-28 Time 11:48 Sent To  
Notes
2022-02-28 11:49:07FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-02-07 Cont ID  
Sent By pleduc Date 2022-02-07 Time   Rev Time 0.00
Received By pleduc Date 2022-02-07 Time 12:48 Sent To  
Notes
2022-02-07 12:58:48THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION ON THE APPLICATION OF "OFFICE
 ALTERATIONS", HOWEVER, IT IS UNCLEAR OF THE PROPOSED
 WORK LOOKING AT THE FLOOR PLAN.
  
 THE FLOOR PLAN DOES NOT PROVIDE AN ACCURATE LEGEND FOR
 THE VARIOUS CALL-OUTS, THERE ARE MULTIPLE CLOUDED
 AREAS( ARE THEY ALL INCLUDED )
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK AND A FLOOR
 PLAN THAT CLEARLY DETAILS THE PROPOSED WORK.
  
  
  
 2) SHOULD THE SCOPE OF WORK INVLOVE DEMO OF WALLS, FIRE
 SPRINKLER PROTECTION MAY REQUIRE MODIFICATIONS.
  
 REMOVAL OF WALLS REQUIRES A CODE COMPLIANT SPRINKLER
 HEAD COVERAGE REVIEW BY A FIRE SPRINKLER CONTRACTOR.
  
 ALL FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE A NOTE OF
 ACKNOWLEDGEMENT ON THE FLOOR PLAN.
  
  
  
 3) THE FLOOR PLAN DOES NOT HAVE THE ADDRESS/SUITE ON
 IT.
  
 PLEASE PROVIDE THE PROPER ADDDRESS ON THE FLOOR PLAN
 SHEET.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-04-05 Cont ID  
Sent By lcrespo Date 2022-04-05 Time 14:36 Rev Time 0.00
Received By lcrespo Date 2022-04-04 Time 10:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-31 Cont ID  
Sent By fgiaquin Date 2022-03-31 Time 20:41 Rev Time 0.00
Received By fgiaquin Date 2022-03-15 Time 06:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-11 Cont ID  
Sent By fgiaquin Date 2022-03-11 Time 23:50 Rev Time 0.00
Received By fgiaquin Date 2022-02-25 Time 07:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-02-23 Time   Rev Time 0.00
Received By cdecoeur Date 2022-02-04 Time 07:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-03-23 Cont ID  
Sent By medwards Date 2022-03-23 Time 14:44 Rev Time 0.00
Received By medwards Date 2022-03-23 Time 14:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-03-07 Cont ID  
Sent By medwards Date 2022-03-07 Time 06:39 Rev Time 0.00
Received By medwards Date 2022-03-07 Time 06:39 Sent To  
Notes
2022-03-07 06:41:14PLEASE PROVIDE A MECHANICAL DRAWING THAT SHOWS THE
 SUPPLY AND RETURN DUCTS AND GRILLES FOR THIS NEWLY
 ENCLOSED ROOM. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-02-16 Cont ID  
Sent By medwards Date 2022-02-16 Time 15:20 Rev Time 0.00
Received By medwards Date 2022-02-16 Time 15:20 Sent To  
Notes
2022-02-16 15:21:45PLEASE PROVIDE A SCOPE OF WORK FOR THE MECHANICAL WORK
 BEING COMPLETED UNDER THIS PROJECT. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2022-02-28 Cont ID  
Sent By rwbrown Date 2022-02-28 Time 14:07 Rev Time 0.00
Received By rwbrown Date 2022-02-28 Time 14:07 Sent To  
Notes
2022-02-28 14:08:24NO PLUMBING INDICATED ON PLANS
  
 RYAN W BROWN

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-02-10 Cont ID  
Sent By rwbrown Date 2022-02-10 Time 14:06 Rev Time 0.00
Received By rwbrown Date 2022-02-10 Time 14:06 Sent To  
Notes
2022-02-10 14:24:511ST PLUMBING REVIEW
  
 PLAN REVIEW RESULTS: DENIED
 1. PLEASE SUBMIT THE MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS WITH RESPECT TO PLUMBING PER THE 2017 WPB
 CHPT 1 AMENDS - 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FACILITIES - INCLUDE THE OCCUPANT
 LOAD
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. WATER HEATERS
 6. VENTS
 13. PLUMBING RISER
  
 2. PER 2017 WPB CHPT 1 AMENDS - 107.2.1 - PLEASE
 CLARIFY THE FULL SCOPE OF THE JOB. SHOWING AN EXISTING
 AND PROPOSED TO HELP INDICATE THE WORK BEING PERFORMED
 AND THE CHANGES TO THE OCCUPANT LOAD FOR VERIFICATION
 OF THE MINIMUM FACILITIES REQUIRED.
  
 3. A COMPREHENSIVE REVIEW COULD NOT BE PERFORMED. NEWLY
 SUBMITTED INFORMATION COULD GENERATE NEW COMMENTS.
 PLEASE SUBMIT THE CORRECTS FOR FURTHER REVIEW.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-04-05 Cont ID  
Sent By lcrespo Date 2022-04-05 Time 14:35 Rev Time 0.00
Received By lcrespo Date 2022-04-05 Time 14:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-03-16 Cont ID  
Sent By jwitmer Date 2022-03-16 Time 08:41 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-03-16 08:40:35107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 REQUIRES THE CONTRACTOR FOR THAT TRADE THAT WILL BE
 LICENSED IN THAT TRADE, WILL ALSO BE THE CONTRACTOR
 THAT DESIGNS THE SYSTEM UNDER THAT TRADE. THE
 CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF
 PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF
 THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-03-01 Cont ID  
Sent By jwitmer Date 2022-03-01 Time 16:18 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-02-23 Cont ID  
Sent By jwitmer Date 2022-02-23 Time 09:01 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-02-23 09:01:25107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 REQUIRES THE CONTRACTOR FOR THAT TRADE THAT WILL BE
 LICENSED IN THAT TRADE, WILL ALSO BE THE CONTRACTOR
 THAT DESIGNS THE SYSTEM UNDER THAT TRADE. THE
 CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF
 PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF
 THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  