Plan Review Details - Permit 22020076
Plan Review Stops For Permit 22020076
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2022-05-18 Cont ID  
Sent By scwelter Date 2022-05-18 Time 13:52 Rev Time 0.00
Received By scwelter Date 2022-05-18 Time 13:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-03 Cont ID  
Sent By rmcphers Date 2022-05-03 Time 13:47 Rev Time 0.00
Received By rmcphers Date 2022-05-03 Time 12:55 Sent To  
Notes
2022-05-03 13:47:20ROOFED PATIO ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING (A-1) SHOWS BUILDING CONSTRUCTION TYPE AS
 IIB - PLEASE SHOW PATIO ADDITION TO COMPLY WITH FBC
 602.2 TYPES I AND II.
 TYPES I AND II CONSTRUCTION ARE THOSE TYPES OF
 CONSTRUCTION IN WHICH THE BUILDING ELEMENTS LISTED IN
 TABLE 601 ARE OF NONCOMBUSTIBLE MATERIALS, EXCEPT AS
 PERMITTED IN SECTION 603 AND ELSEWHERE IN THIS CODE.
  
 2) PLEASE SHOW CEILING HEIGHT TO COMPLY WITH FBC 1208.2
 MINIMUM CEILING HEIGHTS.
 OCCUPIABLE SPACES, HABITABLE SPACES AND CORRIDORS SHALL
 HAVE A CEILING HEIGHT OF NOT LESS THAN 7 FEET 6 INCHES
 (2286 MM) ABOVE THE FINISHED FLOOR.
  
 3) PLEASE SHOW THE WIDTH BETWEEN RAILINGS TO ENTER THE
 STAIRWAY FROM THE DECK FBC 1005.1
  
 4) PLEASE SHOW THE VERTICAL ACCESSIBILITY PER FBC A
 201.1.1
  
 5) THE PATIO SHOWS A 4" STEP DOWN FROM THE EXISTING
 FLOOR ELEVATION THE DECK NEEDS TO BE ACCESSIBLE PER FBC
 206.2.5 RESTAURANTS AND CAFETERIAS.
 IN RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE
 SHALL BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED
 OR SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
 NOTWITHSTANDING THE REQUIREMENTS AND EXCEPTIONS OF THIS
 SECTION, SECTION 201.1.1 SHALL APPLY.
  
 6) PLEASE SHOW THE ACCESSIBLE BAR SEATING PER FBC A 226
 - SHOW KNEE AND TOE CLEARANCE PER FBC A CHAPTER 3 -
 SHOW DINING BAR TOP HEIGHT PER FBC A 902
  
 7) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR DOORS - ALL
 PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE DESIGNER OF RECORD FBC WPB 107.3.4 -
 DOOR PRODUCT APPROVALS CAN BE ADDED TO THE DEFERRED
 SUBMITTAL LIST ON DRAWING "COVER' PAGE.
  
 8) PLEASE SHOW THE STAIR LANDING WIDTH AND DEPTH AT THE
 TOP AND BOTTOM OF THE STAIR FBC 1011.6 STAIRWAY
 LANDINGS.
 THERE SHALL BE A FLOOR OR LANDING AT THE TOP AND BOTTOM
 OF EACH STAIRWAY. THE WIDTH OF LANDINGS SHALL BE NOT
 LESS THAN THE WIDTH OF STAIRWAYS SERVED. EVERY LANDING
 SHALL HAVE A MINIMUM WIDTH MEASURED PERPENDICULAR TO
 THE DIRECTION OF TRAVEL EQUAL TO THE WIDTH OF THE
 STAIRWAY. WHERE THE STAIRWAY HAS A STRAIGHT RUN THE
 DEPTH NEED NOT EXCEED 48 INCHES (1219 MM).
  
 9) PLEASE SHOW THE PATIO FLOOR DECKING ATTACHMENTS FBC
 WPB 107.2
  
 10) JOB VALUE SHOWN ON THE BUILDING PERMIT APPLICATION
 APPEARS TO BE LOW - PLEASE PROVIDE A COST BREAK DOWN
 (JOB VALUE IS MATERIAL AND LABOR) FBC 109.3 BUILDING
 PERMIT VALUATIONS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-05-18 Cont ID  
Sent By jleahy Date 2022-05-18 Time 11:52 Rev Time 0.00
Received By jleahy Date 2022-05-18 Time 11:44 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2022-04-25 Cont ID  
Sent By rrossano Date 2022-04-25 Time   Rev Time  
Received By rrossano Date 2022-04-25 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-04-20 Cont ID  
Sent By pleduc Date 2022-04-20 Time   Rev Time 0.00
Received By pleduc Date 2022-04-20 Time 12:17 Sent To  
Notes
2022-04-20 12:24:24THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF EXTERIOR EXIT STAIRS, BUT
 NO DESIGN CALL OUT OF MATERIAL, TREAD & RISERS
 DIMENSIONS, TREAD DESIGN TO AVOID WATER BUILDUP,
 RAILING DESIGN, ETC. THAT MEET THE REQUIREMENTS OF NFPA
 101, CH 7 MEANS OF EGRESS.
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE.
  
  
 2) THERE ARE EXISTING WINDOWS AND A DOOR UNDER THE
 PROPOSED TERRACE AND WITHIN 10' OF THE EXIT STAIRS.
  
 THOSE OPENINGS ARE REQUIRED TO BE RATED PER NFPA 101 CH
 7, MEANS OF EGRESS.
  
 7.2.2.6.3 SEPARATION AND PROTECTION OF OUTSIDE STAIRS.
 7.2.2.6.3.1* OUTSIDE STAIRS SHALL BE SEPARATED FROM THE
 INTERIOR OF THE
 BUILDING BY CONSTRUCTION WITH THE FIRE RESISTANCE
 RATING REQUIRED FOR
 ENCLOSED STAIRS WITH FIXED OR SELF-CLOSING OPENING
 PROTECTIVES, EXCEPT AS
 FOLLOWS:
 (1) OUTSIDE STAIRS SERVING AN EXTERIOR EXIT ACCESS
 BALCONY THAT HAS TWO
 REMTE OUTSIDE STAIRWAYS OR RAMPS SHALL BE PERMITTED TO
 BE
 UNPROTECTED.
 (2) OUTSIDE STAIRS SERVING TWO OR FEWER ADJACENT
 STORIES, INCLUDING THE
 STORY WHERE THE EXIT DISCHARGES, SHALL BE PERMITTED TO
 BE UNPROTECTED
 WHERE THERE IS A REMOTELY LOCATED SECOND EXIT.
 (3) IN EXISTING BUILDINGS, EXISTING OUTSIDE STAIRS
 SERVING THREE OR FEWER
 ADJACENT STORIES, INCLUDING THE STORY WHERE THE EXIT
 DISCHARGES, SHALL
 BE PERMITTED TO BE UNPROTECTED WHERE THERE IS A
 REMOTELY LOCATED
 SECOND EXIT.
 (4) THE FIRE RESISTANCE RATING OF A SEPARATION
 EXTENDING 10 FT (3050 MM)
 FROM THE STAIRS SHALL NOT BE REQUIRED TO EXCEED 1 HOUR
 WHERE OPEN INGS HAVE A MINIMUM 3
 ?4-HOUR FIRE PROTECTION RATING.
 (5) OUTSIDE STAIRS IN EXISTING BUILDINGS PROTECTED
 THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE
 WITH SECTION 9.7 SHALL BE PERMITTED TO BE UNPROTECTED
  
 PLEASE REVIEW AND CORRECT.
  
  
 3) THERE IS AN INDICATION OF CHANGING THE SINGLE
 EXTERIOR DOOR TO A DOUBLE DOOR, BUT THERE IS NO
 INDICATION OF DOOR HARDWARE,
  
 PLEASE PROVIDE.
  
  
 3A) IS THE EXISTING DOOR AN EXIT SPACE FROM THE 2ND
 FLOOR SPACE AND IS THERE AN EXSITING EXIT SIGN OVER
 THIS PROPOSED DOUBLE DOOR.
  
 PLEASE PROVIDE DETAILS, INCLUDING DOOR HARDWARE
 COMPLIANT WITH EXIT DOOR HARDWARE PER NFPA 101, CH 7
 MEANS OF EGRESS.
  
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE
  
  
 3B) THERE IS NO INDICATION OF THE INTERIOR EXISITNG
 SPACE OCCUPANCY CLASSIFICATION.
  
 PLEASE PROVIDE THE EXISTING SPACE OCCUPANCY
 CLASSIFICATION.
  
  
  
 4) THERE ARE INDICATIONS THAT STRUCTURAL SUPPORT
 COLUMNS ARE IN CLOSE PROXIMITY TO VEHICLE PARKING
 SPACES.
  
 WHAT ARE THE PROPOSED SAFETY FEATURES TO HELP ELIMINATE
 VEHICLE CONTACT WITH THESE SUPPORT COLUMNS.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-01 Cont ID  
Sent By aoliver Date 2022-06-01 Time 08:40 Rev Time 0.00
Received By aoliver Date 2022-04-18 Time 08:25 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-05-03 Cont ID  
Sent By rmcphers Date 2022-05-03 Time 14:16 Rev Time 0.00
Received By rmcphers Date 2022-05-03 Time 14:16 Sent To  
Notes
2022-05-03 14:17:16OPEN PATIO ADDITION

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2022-05-05 Cont ID  
Sent By medwards Date 2022-05-05 Time 06:45 Rev Time 0.00
Received By medwards Date 2022-05-05 Time 06:45 Sent To  
Notes
2022-05-05 06:46:34IMPROVEMENTS TO EXTERIOR, NO MECHANICAL WORK SHOWN IN
 THIS SUBMITTAL.ME

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-04-28 Cont ID  
Sent By ccole Date 2022-04-28 Time 11:57 Rev Time 0.00
Received By ccole Date 2022-04-28 Time 10:54 Sent To  
Notes
2022-04-28 12:03:481ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22020076
 4/28/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE $7200.00 JOB VALUE APPEARS VERY LOW FOR THE
 TOTAL SCOPE OF THE PROPOSED NEW TERRACE AND BAR. PLEASE
 PROVIDE AN ITEMIZED COST BREAKDOWN FOR THE ENTIRE
 PROJECT THAT INCLUDES LABOR, MATERIALS, EQUIPMENT,
 FIXTURES, APPLIANCES, SITE WORK, AND DESIGN WORK- SEC.
 109.3 WPB.
  
 2) SHEET A-1: REFER TO SECS. 1107.1, 810.1, & 810.2 FBC
 EX AND PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE
 THAT INCLUDES THE REQUIRED AND PROVIDED NUMBER OF
 FIXTURES FOR THE OCCUPANCY BASED ON THE OCCUPANCY
 CLASSIFICATION AND THE INCREASED TOTAL OCCUPANT LOAD.
 PLEASE SHOW THE LOCATIONS OF ALL REQUIRED FIXTURES TO
 VERIFY COMPLIANCE.
  
 3) P-1: PLEASE PROVIDE SIZING CALCULATIONS FOR THE
 GREASE INTERCEPTOR PER SEC. 1003.3.5- 1003.3.7 FBC P.
 PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR
 INSTALLATION OF THE GREASE INTERCEPTOR- SEC. 105.1 &
 107.1 WPB.
  
 4) P-1: WHAT IS THE TEMPERATURE LIMITING MEANS FOR THE
 HOT WATER DELIVERIES AT THE SINKS? PLEASE NOTE THAT THE
 THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE THE
 LIMITING DEVICE AND A SEPARATE MASTER THERMOSTATIC
 MIXING VALVE OR POINT OF USE MIXING VALVES SHALL BE
 INSTALLED- SEC. 607.1.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2022-05-03 Cont ID  
Sent By rmcphers Date 2022-05-03 Time 14:18 Rev Time 0.00
Received By rmcphers Date 2022-05-03 Time 14:18 Sent To  
Notes
2022-05-03 14:18:23ROOFING TO BE DEFERRED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-05-03 Cont ID  
Sent By rmcphers Date 2022-05-03 Time 14:24 Rev Time 0.00
Received By rmcphers Date 2022-05-03 Time 14:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-05-31 Cont ID  
Sent By ckimmerl Date 2022-05-31 Time 09:37 Rev Time 0.00
Received By ckimmerl Date 2022-05-31 Time 10:08 Sent To  
Notes
2022-05-31 09:37:041. PLEASE PROVIDE A SURVEY
 2. RESTRIPE/PAVING/MILLING SEPARATE PERMIT.
 3. RE-STRIPING OF THE PARKING LOT NEEDS TO MEET CITY
 PARKING STALL DIMENSIONS AND STRIPING DETAILS OF SEC.
 94-485. - GENERAL PROVISIONS.
 5. PLEASE SUBMITT LANSCAPE PLAN/PERMIT TO ADDRESS
 NONCONFORMITIES ON SITE'S LANDSCAPING.
  
 CHRIS KIMMERLY
 [email protected] 822-1426
  