Plan Review Details - Permit 22020011
Plan Review Stops For Permit 22020011 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2022-09-06 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-09-06 |
Time |
09:39 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-09-06 |
Time |
09:39 |
Sent To |
|
|
Notes |
2022-09-06 10:09:59 | NEED FIRE PLAN REVIEW APPROVAL |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-03-23 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-03-23 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-03-23 |
Time |
14:14 |
Sent To |
|
|
Notes |
2022-03-23 14:44:03 | ADD WALLS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE SHOW THE DOOR OR OPENING WIDTHS TO COMPLY | | WITH FBC ACCESSIBILITY 404.2.3 CLEAR WIDTH. | | DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES | | (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH | | SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF | | THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2022-09-15 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-09-15 |
Time |
13:27 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-09-15 |
Time |
13:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2022-03-18 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-03-18 |
Time |
11:01 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-03-18 |
Time |
11:01 |
Sent To |
|
|
Notes |
2022-03-18 11:02:48 | ELECTRIC REVIEW FAILED | | 1) NO ELECTRIC PLAN. PLEASE PROVIDE AN ELECTRICAL PLAN | | FOR REVIEW. FBC 107.2 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2022-08-22 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-08-22 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-08-22 |
Time |
12:31 |
Sent To |
|
|
Notes |
2022-08-22 12:38:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | SOME OF THE PREVIOUS FIRE COMMENTS WERE NOT ADDRESSED. | | | | PLEASE NOTE BELOW AND RESPOND TO EACH INDIVIDUAL | | COMMENT SPECIFICALLY. | | | | | | 1) FOR CLARIFICATION AND COMFIRMATION, PLEASE PROVIDE | | THE APPROVED OCCUPANCY OF THIS BUILDING, IT IS AN | | EDUCATIONAL OR DAYCARE OCCUPANCY. | | | | PLEASE PROVIDE DETAILS. | | | | *************** COMMENT NOT ADDRESSED************** | | | | PLEASE PROVIDE DETAILS. | | | | | | | | 1A) THERE IS AN INDICATION OF NEW CLASSROOMS WITH | | OPENINGS TO A COMMON INTERIOR AREA. | | | | THERE ARE NO DIMENSIONS INDICATED FOR THE OPENINGS. | | | | ***********COMPLIED******************** | | | | | | | | ARE DOORS PROPOSED FOR THESE OPENINGS? | | | | *************** COMMENT NOT ADDRESSED************** | | | | NEW DRAWING 003 DIVIDING ROOM INDICATES "36" TYPICAL | | DOOR", BUT THERE IS NO DOOR SCHEDULE NOR DOOR HARDWARE. | | | | ARE THESE JUST OPENINGS OR WILL DOORS BE INSTALLED. | | | | PLEASE PROVIDE DETAILS. | | | | | | 2) THERE ARE NO INDICATIONS OF SMOKE ALARMS OR FIRE | | ALARM DEVICES WITHIN THE NEW CLASSROOMS. | | | | THIS OCCUPANCY WAS INSTALLED WITH A FIRE ALARM | | PREVIOUSLY. | | | | *************** COMMENT NOT ADDRESSED************** | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT THAT FIRE | | ALARM/SA DEVICES WILL BE INSTALLED UNDER SEPARATE | | PERMIT AND SHOP DRAWINGS. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2022-02-17 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-02-17 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-02-17 |
Time |
10:59 |
Sent To |
|
|
Notes |
2022-02-17 11:39:34 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) FOR CLARIFICATION AND COMFIRMATION, PLEASE PROVIDE | | THE APPROVED OCCUPANCY OF THIS BUILDING, IT IS AN | | EDUCATIONAL OR DAYCARE OCCUPANCY. | | | | PLEASE PROVIDE DETAILS. | | | | | | | | 1A) THERE IS AN INDICATION OF NEW CLASSROOMS WITH | | OPENINGS TO A COMMON INTERIOR AREA. | | | | THERE ARE NO DIMENSIONS INDICATED FOR THE OPENINGS. | | | | ARE DOORS PROPOSED FOR THESE OPENINGS? | | | | PLEASE PROVIDE DTAILS AND THE DIMENSIONS AND ENSURE | | THEY COMPLY WITH THE MINIMUM WIDTHS OF THE OCCUPANCY. | | | | | | 2) THERE ARE NO INDICATIONS OF SMOKE ALARMS OR FIRE | | ALARM DEVICES WITHIN THE NEW CLASSROOMS. | | | | THIS OCCUPANCY WAS INSTALLED WITH A FIRE ALARM | | PREVIOUSLY. | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT THAT FIRE | | ALARM/SA DEVICES WILL BE INSTALLED UNDER SEPARATE | | PERMIT AND SHOP DRAWINGS. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-09-15 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-09-15 |
Time |
13:38 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-08-18 |
Time |
06:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-03-23 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-03-23 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-02-11 |
Time |
07:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
N |
Date |
2022-03-23 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-03-23 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-03-23 |
Time |
14:44 |
Sent To |
|
|
Notes |
|
|
|