Plan Review Details - Permit 22011290
Plan Review Stops For Permit 22011290
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-04-12 Cont ID  
Sent By jwitmer Date 2022-04-12 Time 11:09 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-03-15 Cont ID  
Sent By jwitmer Date 2022-03-15 Time 13:01 Rev Time 0.00
Received By jwitmer Date 2022-03-15 Time 11:30 Sent To  
Notes
2022-03-15 13:01:15WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22011290
 ADD: 5600 N FLAGLER DR. # 2806
 CONT: LOWES HOME CENTER
 TEL: 561-7710047
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. MARCH 15TH/2022
 ACTION: DENIED
  
 1) 3RD REVIEW. PLEASENOTE IN ALL 3 FLOOR PLANS IT IS
 NOTED THE FINISH MATERIAL TYPE (H) IS FOR HARDWOOD/
 LAMINATE FLOORING. TO DATE NO PRODUCT TESTING REPORTS
 WERE SUBMITTED FOR HARDWOOD/ LAMINATE FLOORING ON A 6
 INCH CONRETE SLAB,NO DRPPED CEILING!!!!.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR
 LAMINATE FLOORING AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) 3RD REVIEW. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) 3RD REVIEW. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) 3RD REVIEW. FLAME SPREAD- FBC-B 2020 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-01 Cont ID  
Sent By jwitmer Date 2022-03-01 Time 14:18 Rev Time 0.00
Received By jwitmer Date 2022-03-01 Time 14:09 Sent To  
Notes
2022-03-01 14:18:11WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22011290
 ADD: 5600 N FLAGLER DR. # 2806
 CONT: LOWES HOME CENTER
 TEL: 561-7710047
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. MARCH 01/2022
 ACTION: DENIED
  
 1) 2ND REQUEST. PLEASE NOTE THERE ARE NO TESTING
 REPORTS FOR MSC-90 THAT HAVE PASSED THE IIC/STC TESTING
 ON A 6 INCH SLAB. TEST REPORTS ARE TO INCLUDE THE FLOOR
 FINISH MATERIAL THIS APPEARS TO BE A 8 INCH CONCRETE
 SLAB NOT 6 INCH. THE 2ND ISSUE IS THE FLAME SPREAD TEST
 REPORT IS FOR PROFLEX SUPER SIM 90. PLEASE NOTE THE
 CITY IS IN RECEIPT OF ALL TEST REPORTS FOR PROFLEX
 SUPER SIM 90 FOR TILE AND OR MARBLE.
 PROFLEX SUPER SIM 90 /TILE OR MARBLE
 IIC = 50 DB / 6 INCH SLAB P. T. / NO DROPPED CEILING /
 ASTM E-492
 STC = 52 DB / 6 INCH SLAB P. T./ NO DROPPED / CEILING
 ASTM E-90
 FLAME= 0 ASTM-E84
 SMOKE= 0 ASTM E-84
  
  
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-02-22 Cont ID  
Sent By jwitmer Date 2022-02-22 Time 11:44 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-02-22 11:44:33WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22011290
 ADD: 5600 N FLAGLER DR. # 2806
 CONT: LOWES HOME CENTER
 TEL: 561-7710047
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 22/2022
 ACTION: DENIED
  
 1) PLEASE NOTE THERE ARE NO TESTING REPORTS FOR MSC-90
 THAT HAVE PASSED THE IIC/STC TESTING ON A 6 INCH SLAB.
 TEST REPORTS ARE TO INCLUDE THE FLOOR FINISH MATERIAL
 THIS APPEARS TO BE HARDWOOD / LAMINATED FLOORING.
  
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2022-04-12 Time   Rev Time 0.00
Received By   Date 2022-04-12 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2022-03-11 Cont ID  
Sent By clfranci Date 2022-03-11 Time   Rev Time 0.00
Received By clfranci Date 2022-03-11 Time   Sent To  
Notes
2022-03-11 15:08:22THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L.
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
  
 1) THE APPLICATION INDICATES THERE WILL BE THE
 REPLACEMENT OF FLOORING WITH THE DOCUMENTS IDENTIFYING
 MATERIALS BEING USED, BUT YOU HAVE ONLY PROVIDE THE
 RADIENT FLUX FOR THE UNDERLAYMENT PLEASE PROVIDE THE
 PRODUCT SPECS FOR THE ALLEN + ROTH WATER RESISTANT
 SCARLET OAK LAMINATE FLOORING THAT INCLUDE THE FIRE
 RATING.
  
 PER NFPA 101 CHAPTER 10, 10.2.7.2
  
 SHALL MEET THE MINIMUM CRITICAL RADIENT FLUX.
  
 CAITLIN L. FRANCIS
 FIRE INVESTIGATOR
 561-804-4728
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-02-28 Cont ID  
Sent By clfranci Date 2022-02-28 Time   Rev Time 0.00
Received By clfranci Date 2022-02-28 Time   Sent To  
Notes
2022-02-28 08:44:41THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L.
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
  
 1) THE APPLICATION INDICATES THERE WILL BE THE
 REPLACEMENT OF FLOORING WITH THE DOCUMENTS IDENTIFYING
 MATERIALS BEING USED, BUT YOU HAVE ONLY PROVIDE THE
 RADIENT FLUX FOR THE UNDERLAYMENT PLEASE PROVIDE THE
 PRODUCT SPECS FOR THE LAMINATE FLOORING THAT INCLUDE
 THE FIRE RATING.
  
 PER NFPA 101 CHAPTER 10, 10.2.7.2
  
 SHALL MEET THE MINIMUM CRITICAL RADIENT FLUX.
  
 CAITLIN L. FRANCIS
 FIRE INVESTIGATOR
 561-804-4728
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-02-03 Cont ID  
Sent By clfranci Date 2022-02-03 Time   Rev Time 0.00
Received By clfranci Date 2022-02-03 Time   Sent To  
Notes
2022-02-03 10:38:02THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L.
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
  
 1) THE APPLICATION INDICATES THERE WILL BE THE
 REPLACEMENT OF FLOORING WITH THE DOCUMENTS IDENTIFYING
 MATERIALS BEING USED, BUT PLEASE PROVIDE THE PRODUCT
 SPECS FOR THE LAMINATE FLOORING THAT INCLUDE THE FIRE
 RATING.
  
 PER NFPA 101 CHAPTER 10, 10.2.7.2
  
 SHALL MEET THE MINIMUM CRITICAL RADIENT FLUX.
  
 CAITLIN L. FRANCIS
 FIRE INVESTIGATOR
 561-804-4728
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-04-14 Cont ID  
Sent By aoliver Date 2022-04-14 Time 10:04 Rev Time 0.00
Received By aoliver Date 2022-04-10 Time 08:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-16 Cont ID  
Sent By aoliver Date 2022-03-16 Time 12:32 Rev Time 0.00
Received By aoliver Date 2022-03-09 Time 08:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-01 Cont ID  
Sent By jwitmer Date 2022-03-01 Time 14:18 Rev Time 0.00
Received By jwitmer Date 2022-02-23 Time 08:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-22 Cont ID  
Sent By jwitmer Date 2022-02-22 Time 11:45 Rev Time 0.00
Received By jwitmer Date 2022-02-01 Time 07:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-02-22 Cont ID  
Sent By jwitmer Date 2022-02-22 Time 11:44 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***