Plan Review Details - Permit 22011190
Plan Review Stops For Permit 22011190
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-03-11 Cont ID  
Sent By jgomez Date 2022-03-11 Time 14:40 Rev Time 0.00
Received By jgomez Date 2022-03-11 Time 14:31 Sent To  
Notes
2022-03-11 14:40:42APPROVED WITH PROVISO:
 1- THIS IS A TOWNHOUSE. ATTIC BREEZE TO BE INSTALLED IN
 THE ROOF SHEATHING NOT LESS THAN 4'-0" FROM THE
 TOWNHOUSE COMMON WALL.
 SEC. R302.2.2.2 FBC-RESIDENTIAL.
  
 2- SEE ENGINEERING FOR REQUIRED CURB FASTENING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-03 Cont ID  
Sent By jgomez Date 2022-03-03 Time 13:08 Rev Time 0.00
Received By jgomez Date 2022-03-03 Time 10:31 Sent To  
Notes
2022-03-03 13:09:15RESIDENTIAL (R3) REVISION SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 REVISION #22011190
  
 1- OK.
  
 ORIGINAL COMMENT:
 2- ATTIC BREEZE PRODUCT APPROVAL SUBMITTED STATES UNDER
 LIMITS OF USE ON PAGE 4 OF 6 THAT "DESIGN OF SUPPORT
 SYSTEM IS OUTSIDE THE SCOPE OF THIS REPORT". THIS
 PRODUCT APPROVAL IS FOR A FAN TO BE MOUNTED ON A WOOD
 OR STEEL & ALUMINUM CURB. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF THE CURB SHOWING
 COMPLIANCE WITH THE WIND DESIGN CRITERIA OF SEC.
 R301.2.1 FBC-RESIDENTIAL.
 NOTE: BUILDING SUBPERMIT MAY BE REQUIRED FOR FRAMING
 INSPECTION.
  
 RESPONSE:
 ROOF CURB INSTALLATION GUIDE SUBMITTED DOESN'T ADDRESS
 THE WIND DESIGN CRITERIA. THE WIND DESIGN CRITERIA IS
 REQUIRED. PROVIDE CURB ENGINEERING SHOWING COMPLIANCE
 WITH THE WIND DESIGN CRITERIA. SEC. 107.2.1.2 CITY
 AMENDMENTS.
 NOTE: ENGINEER OF RECORD FOR ATTIC BREEZE FAN DOESN'T
 INCLUDE THE CURB ASSEMBLY. SEE PRODUCT ASSEMBLY AS
 EVALUATED INFORMATION ON PAGE 2 OF 6 OF PRODUCT
 APPROVAL FL13339.4 R9 SUBMITTED.
  
 ORIGINAL COMMENT.
 3- THIS VENT IS ADDITIONAL WORK. PROVIDE THE VALUE FOR
 ALL ADDITIONAL WORK. SEC. 109.3 CITY AMENDMENTS.
  
 RESPONSE:
 NOT ADDRESSED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-02-08 Cont ID  
Sent By jgomez Date 2022-02-08 Time 17:38 Rev Time 0.00
Received By jgomez Date 2022-02-08 Time 14:51 Sent To  
Notes
2022-02-08 17:38:37RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 REVISION #22011190
  
 NOTE:
 LEVEL 2 ALTERATION. SEC. 603 FBC-EXISTING BUILDING.
 SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- THIS IS A TOWNHOUSE. ROOF DIAGRAM SUBMITTED SHOWS
 THE SOLAR ATTIC FAN TO BE LOCATED LESS THAN FOUR FEET
 OF THE FIRE RATED DEMISING WALL. NO OPENING ALLOWED IN
 THIS AREA. REVISE AS REQUIRED. CLEARLY SPECIFY DISTANCE
 FROM FIRE RATED DEMISING WALL. SEC. R302.2
 FBC-RESIDENTIAL.
  
 2- ATTIC BREEZE PRODUCT APPROVAL SUBMITTED STATES UNDER
 LIMITS OF USE ON PAGE 4 OF 6 THAT "DESIGN OF SUPPORT
 SYSTEM IS OUTSIDE THE SCOPE OF THIS REPORT". THIS
 PRODUCT APPROVAL IS FOR A FAN TO BE MOUNTED ON A WOOD
 OR STEEL & ALUMINUM CURB. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF THE CURB SHOWING
 COMPLIANCE WITH THE WIND DESIGN CRITERIA OF SEC.
 R301.2.1 FBC-RESIDENTIAL.
 NOTE: BUILDING SUBPERMIT MAY BE REQUIRED FOR FRAMING
 INSPECTION.
  
 3- THIS VENT IS ADDITIONAL WORK. PROVIDE THE VALUE FOR
 ALL ADDITIONAL WORK. SEC. 109.3 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-11 Cont ID  
Sent By jgomez Date 2022-03-11 Time 14:40 Rev Time 0.00
Received By jgomez Date 2022-03-09 Time 08:22 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-03 Cont ID  
Sent By jgomez Date 2022-03-03 Time 13:23 Rev Time 0.00
Received By jgomez Date 2022-03-02 Time 07:21 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-08 Cont ID  
Sent By jgomez Date 2022-02-08 Time 17:38 Rev Time 0.00
Received By jgomez Date 2022-01-31 Time 08:56 Sent To I
Notes
***NONE***