Plan Review Details - Permit 22011186
Plan Review Stops For Permit 22011186
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-09-26 Cont ID  
Sent By cpuell Date 2022-09-26 Time 17:02 Rev Time 0.00
Received By cpuell Date 2022-09-26 Time 17:02 Sent To  
Notes
2022-09-26 17:03:22NORTH UNIT IN DUPLEX GIVEN THE ADDRESS OF 910 4TH ST
 AND SOUTH UNIT OF DUPLEX GIVEN THE ADDRESS OF 912 4TH
 ST UPDATED PERMIT. DUPLEX ALLOWED ON SITE PER
 AMHAMILTON

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-08-18 Cont ID  
Sent By cpuell Date 2022-08-18 Time 14:11 Rev Time 0.00
Received By cpuell Date 2022-08-18 Time 14:11 Sent To  
Notes
2022-08-18 14:17:11PLEASE CONTACT [email protected] OR CALL
 561-805-6659 ONCE ZONING HAS APPROVED THE DUPLEX TO BE
 ASSIGNED ADDRESSES FOR THE UNITS IN THE DUPLEX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2023-03-07 Cont ID  
Sent By jgomez Date 2023-03-07 Time 10:15 Rev Time 0.00
Received By jgomez Date 2023-03-07 Time 10:06 Sent To  
Notes
2023-03-07 10:16:13BUILDING REVIEW APPROVED WITH PROVISO:
 1- DEFERRED SUBMITTAL:
 A)ENTRY WOOD DOOR AS SPECIFIED ON PLANS.
 B)WOOD FRENCH DOOR AS SPECIFIED ON PLANS.
 C)SINGLE HUNG WINDOWS.
 D)WINDOW MULLIONS (NOTE: SPECIFY MULLION SIZE TO VERIFY
 PRESSURES).
 E)HURRICANE SHUTTERS IF REQUIRED. PROVIDE COMPLETE
 INSTALLATION SCHEDULE.
 E)SHINGLES.
 2- DESIGNER OF RECORD TO REVIEW ALL PRODUCT APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2023-03-07 Cont ID  
Sent By jgomez Date 2023-03-07 Time 09:36 Rev Time 0.00
Received By jgomez Date 2023-03-07 Time 09:17 Sent To  
Notes
2023-03-07 09:38:4503/07/23 RECEIVED REVISED ENERGY CALCULATIONS FROM
 ALEXA PAREDES.
  
 NEW DUPLEX (R3) EIGHT BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22011186
 910 4TH ST
  
 18- REVISED ENERGY CALCULATIONS:
  
 RESPONSE:
 SIGNED AND SEALED ENERGY CALCULATIONS SUBMITTED NOW
 DON'T HAVE ITEMS #2 (MULTIPLE FAMILY) AND ITEM #3
 (NUMBER OF UNITS) REVISED. WE WENT BACK TO BUILDING
 REVIEW #6 WHEN THESE ITEMS WERE REQUESTED TO BE
 REVISED.
  
 16-DEFERRED SUBMITTAL: PRODUCT APPROVALS WILL BE
 SUBMITTED AFTER THE PERMIT IS ISSUED:
 A)ENTRY WOOD DOOR AS SPECIFIED ON PLANS.
 B)WOOD FRENCH DOOR AS SPECIFIED ON PLANS.
 C)SINGLE HUNG WINDOWS.
 D)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
 E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 E)SHINGLES.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2023-03-06 Cont ID  
Sent By jgomez Date 2023-03-06 Time 17:30 Rev Time 0.00
Received By jgomez Date 2023-03-06 Time 16:52 Sent To  
Notes
2023-03-06 16:57:1103/06/23 RECEIVED REVISED ENERGY CALCULATIONS FROM
 ALEXA PAREDES.
  
 NEW DUPLEX (R3) SEVEN BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22011186
 910 4TH ST
  
 18- REVISE ENERGY CALCULATIONS:
  
 RESPONSE:
 PREVIOUS COMMENTS WERE ADDRESSED. REVISED ENERGY
 CALCULATIONS HAVE A COPY OF THE ENGINEERS SEAL. IT
 DOESN'T HAVE THE SIGNATURE OF THE ENGINEER OF RECORD.
 NEED TO HAVE THE ORIGINAL SEAL/SIGNATURE OF THE
 ENGINEER OF RECORD AS REQUIRED BY SEC. 61G15-23.001 FAC
 AND CHAPTER 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS
 FOR PUBLIC RECORDS. THIS IS AN ELECTRONIC SUBMITTAL.
 SUBMIT PLANS/DOCUMENTS WITH ENGINEER'S VERIFIABLE
 DIGITAL SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 16-DEFERRED SUBMITTAL: PRODUCT APPROVALS WILL BE
 SUBMITTED AFTER THE PERMIT IS ISSUED:
 A)ENTRY WOOD DOOR AS SPECIFIED ON PLANS.
 B)WOOD FRENCH DOOR AS SPECIFIED ON PLANS.
 C)SINGLE HUNG WINDOWS.
 D)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
 E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 E)SHINGLES.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2023-03-06 Cont ID  
Sent By jgomez Date 2023-03-06 Time 10:51 Rev Time 0.00
Received By jgomez Date 2023-03-06 Time 10:43 Sent To  
Notes
2023-03-06 10:52:07NEW DUPLEX (R3) SIXTH BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22011186
 910 4TH ST
  
 PROVISO NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY (EXCEPT FOR
 PRODUCT APPROVALS DEFERRED SUBMITTAL).
  
 ***IMPORTANT
 ****CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED
 AT THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION
 BEFORE PERMIT ISSUANCE.
  
  
 18- REVISE ENERGY CALCULATIONS:
 PREVIOUS COMMENT:
 H)ITEM #2 WAS CORRECT BUT IT WAS REVISED AND NOW IS
 INCORRECT. IT IS MULTIPLE FAMILY. REVISE AGAIN AS
 REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I)ITEM #3 WAS CORRECT BUT IT WAS REVISED AND NOW IS
 INCORRECT. IT IS 2 UNITS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 16-DEFERRED SUBMITTAL: PRODUCT APPROVALS WILL BE
 SUBMITTED AFTER THE PERMIT IS ISSUED:
 A)ENTRY WOOD DOOR AS SPECIFIED ON PLANS.
 B)WOOD FRENCH DOOR AS SPECIFIED ON PLANS.
 C)SINGLE HUNG WINDOWS.
 D)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
 E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 E)SHINGLES.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-03-02 Cont ID  
Sent By jgomez Date 2023-03-02 Time 16:23 Rev Time 0.00
Received By jgomez Date 2023-03-02 Time 15:00 Sent To  
Notes
2023-03-02 16:23:20NEW DUPLEX (R3) FIFTH BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22011186
 910 4TH ST
  
 PROVISO NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY (EXCEPT FOR
 PRODUCT APPROVALS DEFERRED SUBMITTAL).
  
 ***IMPORTANT
 ****CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED
 AT THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION
 BEFORE PERMIT ISSUANCE.
  
  
 18- REVISE ENERGY CALCULATIONS:
 PREVIOUS COMMENT:
 G)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 NEW COMMENTS BASED ON REVISED CALCULATIONS
 H)ITEM #2 WAS CORRECT BUT IT WAS REVISED AND NOW IS
 INCORRECT. IT IS MULTIPLE FAMILY. REVISE AGAIN AS
 REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I)ITEM #3 WAS CORRECT BUT IT WAS REVISED AND NOW IS
 INCORRECT. IT IS 2 UNITS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 16-DEFERRED SUBMITTAL: PRODUCT APPROVALS WILL BE
 SUBMITTED AFTER THE PERMIT IS ISSUED:
 A)ENTRY WOOD DOOR AS SPECIFIED ON PLANS.
 B)WOOD FRENCH DOOR AS SPECIFIED ON PLANS.
 C)SINGLE HUNG WINDOWS.
 D)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
 E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 E)SHINGLES.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-03-01 Cont ID  
Sent By jgomez Date 2023-03-01 Time 11:03 Rev Time 0.00
Received By jgomez Date 2023-02-28 Time 18:21 Sent To  
Notes
2023-03-01 11:03:49NEW DUPLEX (R3) FOURTH BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22011186
 910 4TH ST
  
 PREVIOUS COMMENT:
 2-EGRESS WINDOW DISCUSSED WITH ROBERT BROWN, BUILDING
 OFFICIAL. SINCE THIS IS NEW CONSTRUCTION AND THE
 SPECIFIED WINDOW SIZE IS SMALLER THAN TYPICAL EGRESS
 SIZE AND THE ARCHITECT'S SPECIFIED WINDOW IS BASED ON
 SPECIFIC MANUFACTURER AND SPECIFIC SIZE WITH AN
 ADDITIONAL CONDITION TO MEET THE EGRESS REQUIREMENTS,
 THEN BUILDING OFFICIAL REQUIRES ARCHITECT OF RECORD TO
 SPECIFY ON PLANS HOW THE SPECIFIED WINDOW MEETS THE
 EGRESS REQUIREMENT. THIS IS REQUIRED IN ORDER FOR
 INSPECTOR TO VERIFY THIS CONDITION IN THE FIELD.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. ARCHITECT DOESN'T
 SPECIFY ON PLANS ON PLANS THE SPECIAL CONDITION
 REQUIRED FOR THE EGRESS WINDOW TO COMPLY WITH THE
 EGRESS REQUIREMENTS. THIS ADDITIONAL INFORMATION WAS
 REQUESTED BY BUILDING OFFICIAL FOR INSPECTION PURPOSES.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 16-DEFERRED SUBMITTAL: PRODUCT APPROVALS WILL BE
 SUBMITTED AFTER THE PERMIT IS ISSUED:
 A)ENTRY WOOD DOOR AS SPECIFIED ON PLANS.
 B)WOOD FRENCH DOOR AS SPECIFIED ON PLANS.
 C)SINGLE HUNG WINDOWS.
 D)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
 E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 E)SHINGLES.
  
 18- REVISE ENERGY CALCULATIONS:
 PREVIOUS COMMENT:
 G)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 NEW COMMENTS BASED ON REVISED CALCULATIONS
 H)ITEM #2 WAS CORRECT BUT IT WAS REVISED AND NOW IS
 INCORRECT. IT IS MULTIPLE FAMILY. REVISE AGAIN AS
 REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I)ITEM #3 WAS CORRECT BUT IT WAS REVISED AND NOW IS
 INCORRECT. IT IS 2 UNITS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-01-23 Cont ID  
Sent By jgomez Date 2023-01-23 Time 17:58 Rev Time 0.00
Received By jgomez Date 2023-01-23 Time 17:50 Sent To  
Notes
2023-01-23 17:59:11NEW DUPLEX (R3) THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22011186
 910 4TH ST
  
 1- OK.
  
 PREVIOUS COMMENT:
 2-PARTIALLY ADDRESSED. (DISCUSSED WITH ROBERT BROWN,
 BUILDING OFFICIAL). SINCE THIS IS NEW CONSTRUCTION AND
 THE SPECIFIED WINDOW SIZE IS SMALLER THAN TYPICAL
 EGRESS SIZE AND THE ARCHITECT'S SPECIFIED WINDOW IS
 BASED ON SPECIFIC MANUFACTURER AND SPECIFIC SIZE WITH
 AN ADDITIONAL CONDITION TO MEET THE EGRESS
 REQUIREMENTS, THEN BUILDING OFFICIAL REQUIRES ARCHITECT
 OF RECORD TO SPECIFY ON PLANS HOW THE SPECIFIED WINDOW
 MEETS THE EGRESS REQUIREMENT. THIS IS REQUIRED IN ORDER
 FOR INSPECTOR TO VERIFY THIS CONDITION IN THE FIELD.
  
 RESPONSE:
 NOT ADDRESSED. ARCHITECT DOESN'T SPECIFY ON PLANS ON
 PLANS THE SPECIAL CONDITION REQUIRED FOR THE EGRESS
 WINDOW TO COMPLY WITH THE EGRESS REQUIREMENTS. THIS
 ADDITIONAL INFORMATION WAS REQUESTED BY BUILDING
 OFFICIAL FOR INSPECTION PURPOSES.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 5- WALL SEPARATING THE TWO UNITS.
 PREVIOUS COMMENT:
 A)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR TYPE
 OF "MUD" TO BE USED TO SEAL ALL OPENINGS AND
 PENETRATIONS AS SPECIFIED ON DETAIL 2 ON SHEET A.4.
 (SEC. 107.2.1 CITY AMENDMENTS. SEC. 703.3
 FBC-BUILDING).
  
 ALSO, DETAIL 2 ON SHEET A.4 STATES THAT MASONRY WALL
 BETWEEN UNIT 1 AND UNIT 2 IS A 2 HR WALL. NEED TO
 SPECIFY THE SPECIFIC TYPE OF CONCRETE BLOCK TO BE
 CONSIDERED 2 HOUR. SEE UL ASSEMBLY U905 FOR SPECIFIC
 TYPE AND REVISE AS REQUIRED. PROVIDE COMPLETE DETAIL
 ASSEMBLY.
  
 RESPONSE:
 NOT ADDRESSED. REVISED SHEET A4 STATED ON ARCHITECT'S
 RESPONSE LETTER WAS NOT SUBMITTED.
  
 16-PRODUCT APPROVALS WILL BE SUBMITTED AFTER THE PERMIT
 IS ISSUED:
 A)ENTRY WOOD DOOR AS SPECIFIED ON PLANS.
 B)WOOD FRENCH DOOR AS SPECIFIED ON PLANS.
 C)SINGLE HUNG WINDOWS.
 D)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
 E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 E)SHINGLES.
 F)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
  
 18- REVISE ENERGY CALCULATIONS:
 PREVIOUS COMMENT:
 A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER NAME, BUILDER NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 BUILDER NAME IS INCORRECT.
  
 PREVIOUS COMMENT:
 F) ROOF TYPE AND MATERIAL SPECIFIED ON SECOND PAGE IS
 INCORRECT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 ROOF TYPE IS INCORRECT.
  
 PREVIOUS COMMENT:
 G)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 RESPONSE:
 NOT ADDRESSED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-02 Cont ID  
Sent By jgomez Date 2022-12-02 Time 19:09 Rev Time 0.00
Received By jgomez Date 2022-12-02 Time 17:18 Sent To  
Notes
2022-12-02 19:09:20NEW DUPLEX (R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22011186
 910 4TH ST
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY.
  
 ***IMPORTANT****CONTRACTOR TO ADVICE IF PROVISO OPTION
 IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED
 INFORMATION BEFORE PERMIT ISSUANCE.
  
 1- OK.
  
 ORIGINAL COMMENT:
 2-SINGLE HUNG BEDROOM EGRESS WINDOWS SIZE (3'-1' X
 4'-10-1/2") DOESN'T SEEM TO COMPLY WITH THE MINIMUM
 CLEAR HEIGHT OPENING REQUIREMENTS OF SEC. R310.2.1
 FBC-RESIDENTIAL. TYPICALLY, SINGLE HUNG WINDOWS WITH A
 63 INCHES HEIGHT ARE THE ONES THAT COMPLY WITH THIS
 REQUIREMENT. REVISE AS REQUIRED OR PROVIDE
 MANUFACTURER'S SPECIFICATIONS SHOWING COMPLIANCE ALL
 THE EGRESS REQUIREMENTS.
  
 RESPONSE:
 PARTIALLY ADDRESSED. (DISCUSSED WITH ROBERT BROWN,
 BUILDING OFFICIAL). SINCE THIS IS NEW CONSTRUCTION AND
 THE SPECIFIED WINDOW SIZE IS SMALLER THAN TYPICAL
 EGRESS SIZE AND THE ARCHITECT'S SPECIFIED WINDOW IS
 BASED ON SPECIFIC MANUFACTURER AND SPECIFIC SIZE WITH
 AN ADDITIONAL CONDITION TO MEET THE EGRESS
 REQUIREMENTS, THEN BUILDING OFFICIAL REQUIRES ARCHITECT
 OF RECORD TO SPECIFY ON PLANS HOW THE SPECIFIED WINDOW
 MEETS THE EGRESS REQUIREMENT. THIS IS REQUIRED IN ORDER
 FOR INSPECTOR TO VERIFY THIS CONDITION IN THE FIELD.
 ALSO, PLEASE UPLOAD THE MANUFACTURE'S CUT SHEETS ON A
 SEPARATE FILE NOT WITH THE RESPONSE LETTER. RESPONSE
 LETTER IS ONLY TO HELP EXPEDITE THE REVIEW PROCESS AND
 WILL NOT BE PART OF THE PERMIT PACKAGE. THE WINDOW CUT
 SHEETS ARE PART OF THE PERMIT PACKAGE. ALSO, SAME THING
 APPLIES TO THE ICYNENE ICC EVALUATION REPORT.
  
 ORIGINAL COMMENT:
 3- ARCHITECT TO CLEARLY SPECIFY ALL ROOF LIVE AND DEAD
 LOADS. CLEARLY SPECIFY TRUSS TOP CHORD LIVE AND DEAD
 LOADS AND BOTTOM CHORD LIVE AND DEAD LOADS. NOTE:
 INCLUDE THE ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5
 FBC-RESIDENTIAL. SEE FOOTNOTES "B" AND "G".
  
 RESPONSE:
 ROOF BOTTOM CHORD LIVE LOAD DOESN'T COMPLY WITH TABLE
 R301.5 FBC-RESIDENTIAL. MIN. BOTTOM CHORD LIVE LOAD IS
 10PSF. REVISE INFORMATION AS REQUIRED.
  
 ORIGINAL COMMENT:
 4- PROVIDE DRAINAGE PLAN SHOWING EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES. PROVIDE SURVEY SHOWING GRADE
 ELEVATIONS AND PROPOSED BUILDING.
 SEC. R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY
 AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DETAIL 1 ON SHEET A.0.1 DOESN'T REFLECT SITE
 DRAINAGE PLAN. ALSO, PROVIDE DETAIL SHOWING HOW RAISING
 THE GRADE 6 INCHES AT THE PROPERTY LINE. IF RETAINING
 WLL REQUIRED, THEN NEED TO PROVIDE COMPLETE RETAINING
 WALL DETAILS/SPECS UNDER A SEPARATE PERMIT.
  
 RESPONSE:
 DRAINAGE PLAN DOESN'T SHOW EXISTING AND PROPOSED
 ELEVATIONS. SURVEY SHOWING THE ELEVATIONS WAS NOT
 PROVIDED. INFORMATION ON DETAIL 1 ON SHEET A-0.1
 DOESN'T SHOW HOW RAISING THE GRADE 6 INCHES AT THE
 PROPERTY LINE. IF RETAINING WILL BE REQUIRED, THEN NEED
 TO PROVIDE COMPLETE RETAINING WALL DETAILS/SPECS UNDER
 A SEPARATE PERMIT.
 ALSO, PROVIDE SWALE DETAIL/SECTION FOR BOTH SIDES (EAST
 AND WEST) OF PROPOSED STRUCTURE.
  
 5- WALL SEPARATING THE TWO UNITS.
  
 ORIGINAL COMMENT:
 A)PROVIDE COMPLETE WALL SECTION DETAIL AND
 SPECIFICATIONS FOR ONE HOUR FIRE RESISTANCE RATING
 SHOWING COMPLIANCE WITH SEC. R302.3 FBC-RESIDENTIAL.
 SHOW COMPLIANCE WITH ASTM E119, UL 263 OR SEC. 703.3
 FBC-BUILDING.
  
 RESPONSE:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR TYPE OF
 "MUD" TO BE USED TO SEAL ALL OPENINGS AND PENETRATIONS
 AS SPECIFIED ON DETAIL 2 ON SHEET A.4.
 (SEC. 107.2.1 CITY AMENDMENTS. SEC. 703.3
 FBC-BUILDING).
  
 ALSO, DETAIL 2 ON SHEET A.4 STATES THAT MASONRY WALL
 BETWEEN UNIT 1 AND UNIT 2 IS A 2 HR WALL. NEED TO
 SPECIFY THE SPECIFIC TYPE OF CONCRETE BLOCK TO BE
 CONSIDERED 2 HOUR. SEE UL ASSEMBLY U905 FOR SPECIFIC
 TYPE AND REVISE AS REQUIRED. PROVIDE COMPLETE DETAIL
 ASSEMBLY.
  
 ORIGINAL COMMENT:
 B)PROVIDE DETAILS/SPECS FOR WALL THROUGH PENETRATIONS.
 SEC. R302.4.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 DETAILS PROVIDED ON SHEET A.4 ARE FOR GYPSUM WALLS.
 THIS IS MASONRY CONSTRUCTION.
 NOTE: PROVIDE DETAIL/SPECIFICATIONS FOR RECEPTACLES AND
 ANY OTHER PENETRATIONS ON THE FIRE RATED DEMISING WALL.
  
 ORIGINAL COMMENT:
 6- THERE ARE TWO DIFFERENT SPECIFICATIONS FOR ROOF
 SHEATHING ON SHEET S.2. ROOF FRAMING NOTE #1 AND
 INFORMATION SHOWN ON TABLE R803.2.3.1 FOR SHEATHING
 ATTACHMENT BELOW DON'T MATCH. REVISE AS REQUIRED TO
 MATCH TO AVOID CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS.
 SEC. R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 ROOF FRAMING NOTES SPECIFY 10D NAILS. CLEARLY SPECIFY
 TYPE OF NAILS. SEC. R803.2.3.1 FBC-RESIDENTIAL REQUIRES
 RING SHANK NAILS. SPECIFY THIS ON PLANS.
  
 ORIGINAL COMMENT:
 7- DESIGN PRESSURES FOR WINDOW #2 ON NORTH AND SOUTH
 ELEVATIONS ARE TOO LOW. THESE WINDOWS ARE LOCATED IN
 THE END ZONE. REVISE AS REQUIRED. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 DESIGN PRESSURES WERE LOWERED INSTEAD OF BEING
 INCREASED. REVISE AS REQUIRED OR PROVIDE CALCULATIONS
 FOR EACH OPENING.
  
 ORIGINAL COMMENT:
 8- GABLE END DETAIL ON SHEET ON SHEET S.2: NEED TO
 SPECIFY TWO WATER RESISTIVE BARRIERS WHEN STUCCO IS
 APPLIED TO WOOD AS REQUIRED BY SEC. R703.7.3
 FBC-RESIDENTIAL.
  
 RESPONSE:
 RESPONSE LETTER SAYS "(2) WATER RESISTIVE BARRIERS ARE
 SPECIFIED. SEE REVISED SECTION NOTE #3 ON SHEET A.4".
 THIS INFORMATION WAS NOT PROVIDED.
  
 ORIGINAL COMMENT:
 9- WIND RESISTANCE OF EXTERIOR SOFFITS: PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE SOFFIT
 CONSTRUCTION SHOWING COMPLIANCE WITH SEC. R704
 FBC-RESIDENTIAL.
  
 RESPONSE:
 RESPONSE LETTER SAYS "SOFFITS ARE STUCCO. SEE NOTE #2
 ON SHEET A.4".
 THIS INFORMATION WAS NOT PROVIDED.
 NOTE: DESIGNER OF RECORD NEEDS TO SPECIFY TYPE OF METAL
 PLASTER BASE FOR CEILINGS SHOWING COMPLIANCE WITH TABLE
 3 OF ASTM C1063.
  
 10- OK.
 11- OK.
 12- OK.
  
 ORIGINAL COMMENT:
 13-PROVIDE DOOR AND WINDOW DOOR STRUCTURAL BUCK DETAIL
 SHOWING COMPLIANCE WITH SEC. R609.7.2.1
 FBC-RESIDENTIAL. SPECIFY STRUCTURAL BUCK SIZE AND
 FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 DETAILS ON SHEET A.4.1 DON'T SPECIFY FASTENING OF THE
 BUCKS. DESIGNER OF RECORD NEEDS TO SPECIFY FASTENER
 TYPE AND SIZE/SPACING. CITING PER CODE SECTION IS NOT
 ALLOWED. SEC. 107.2.1 CITY AMENDMENTS.
  
 14- OK.
  
 ORIGINAL COMMENT:
 15- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS
 SPECIFYING R-30 ICYNENE SPRAY INSULATION. PROVIDE ICC
 EVALUATION REPORT FOR THE ICYNENE R-30 INSULATION TO
 VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 RESPONSE:
 RESPONSE LETTER SAYS "THIS HAS BEEN ADDED AS A DEFERRED
 SUBMITTAL ON REVISED SHEET A.0". REVISED SHEET DOESN'T
 SHOW THIS. ALSO, THE ICC EVALUATION REPORT WAS UPLOADED
 IN PROJECTDOX IN THE SAME FILE WITH THE RESPONSE
 LETTER. PLEASE UPLOAD THE ICC EVALUATION REPORT
 REVIEWED/APPROVED BY THE ARCHITECT ON A SEPARATE FILE
 NOT WITH THE RESPONSE LETTER.
  
 16-DEFERRED SUBMITTAL. PRODUCT APPROVALS (FAC
 61G20-3.001):
 A)ENTRY WOOD DOOR AS SPECIFIED ON PLANS.
 B)WOOD FRENCH DOOR AS SPECIFIED ON PLANS.
 C)SINGLE HUNG WINDOWS.
 D)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
 E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 E)SHINGLES.
 F)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
  
 17- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 18- REVISE ENERGY CALCULATIONS:
  
 RESPONSE:
 ENERGY CALCULATIONS WERE NOT REVISED. SAME ITEMS APPLY.
 SEE BELOW:
  
 A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER NAME, BUILDER NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 B)ITEM #2 ON PAGE 1 IS INCORRECT. THIS IS A MULTIFAMILY
 BUILDING. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 C)ITEM #3 ON PAGE 1 IS INCORRECT. THIS IS A MULTIFAMILY
 BUILDING. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 D)CEILING R-VALUE INFORMATION ON PAGE 1 DOESN'T MATCH
 INFORMATION ON PLANS.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 E)WATER HEATER IS ELECTRIC NOT GAS. SEE PLANS AND
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 F) ROOF TYPE AND MATERIAL SPECIFIED ON SECOND PAGE IS
 INCORRECT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-03 Cont ID  
Sent By jgomez Date 2022-10-03 Time 18:59 Rev Time 0.00
Received By jgomez Date 2022-10-03 Time 09:35 Sent To  
Notes
2022-09-27 18:59:59NEW DUPLEX (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22011186
 910 4TH ST
  
 1- ALL PLANS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD WHEN SUBMITTING FOR PUBLIC RECORDS.
 SEC. 481 F.S.
  
 2-SINGLE HUNG BEDROOM EGRESS WINDOWS SIZE (3'-1' X
 4'-10-1/2") DOESN'T SEEM TO COMPLY WITH THE MINIMUM
 CLEAR HEIGHT OPENING REQUIREMENTS OF SEC. R310.2.1
 FBC-RESIDENTIAL. TYPICALLY, SINGLE HUNG WINDOWS WITH A
 63 INCHES HEIGHT ARE THE ONES THAT COMPLY WITH THIS
 REQUIREMENT. REVISE AS REQUIRED OR PROVIDE
 MANUFACTURER'S SPECIFICATIONS SHOWING COMPLIANCE ALL
 THE EGRESS REQUIREMENTS.
  
 3- ARCHITECT TO CLEARLY SPECIFY ALL ROOF LIVE AND DEAD
 LOADS. CLEARLY SPECIFY TRUSS TOP CHORD LIVE AND DEAD
 LOADS AND BOTTOM CHORD LIVE AND DEAD LOADS. NOTE:
 INCLUDE THE ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5
 FBC-RESIDENTIAL. SEE FOOTNOTES "B" AND "G".
  
 4- PROVIDE DRAINAGE PLAN SHOWING EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES. PROVIDE SURVEY SHOWING GRADE
 ELEVATIONS AND PROPOSED BUILDING.
 SEC. R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY
 AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DETAIL 1 ON SHEET A.0.1 DOESN'T REFLECT SITE
 DRAINAGE PLAN. ALSO, PROVIDE DETAIL SHOWING HOW RAISING
 THE GRADE 6 INCHES AT T HE PROPERTY LINE. IF RETAINING
 WALL REQUIRED, THEN NEED TO PROVIDE COMPLETE RETAINING
 WALL DETAILS/SPECS UNDER A SEPARATE PERMIT.
  
 5- WALL SEPARATING THE TWO UNITS.
 A)PROVIDE COMPLETE WALL SECTION DETAIL AND
 SPECIFICATIONS FOR ONE HOUR FIRE RESISTANCE RATING
 SHOWING COMPLIANCE WITH SEC. R302.3 FBC-RESIDENTIAL.
 SHOW COMPLIANCE WITH ASTM E119, UL 263 OR SEC. 703.3
 FBC-BUILDING.
 NOTE: CLARIFY IF DETAIL 2 ON SHEET A.4 IS TO SHOW
 COMPLIANCE WITH EXCEPTION #2. IF THIS IS THE INTENTION,
 THEN NEED TO REVISE DETAIL TO SPECIFY THE REQUIRED TYPE
 OF FIRE RATED CEILING.
  
 B)PROVIDE DETAILS/SPECS FOR WALL THROUGH PENETRATIONS.
 SEC. R302.4.1 FBC-RESIDENTIAL.
  
 6- THERE ARE TWO DIFFERENT SPECIFICATIONS FOR ROOF
 SHEATHING ON SHEET S.2. ROOF FRAMING NOTE #1 AND
 INFORMATION SHOWN ON TABLE R803.2.3.1 FOR SHEATHING
 ATTACHMENT BELOW DON'T MATCH. REVISE AS REQUIRED TO
 MATCH TO AVOID CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS.
 SEC. R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
  
 7- DESIGN PRESSURES FOR WINDOW #2 ON NORTH AND SOUTH
 ELEVATIONS ARE TOO LOW. THESE WINDOWS ARE LOCATED IN
 THE END ZONE. REVISE AS REQUIRED. SEC. R301.2.1
 FBC-RESIDENTIAL.
 NOTE: CLARIFY WHY THE DESIGN PRESSURES FOR WINDOW #3
 ARE DIFFERENT ON THE EAST AND WEST ELEVATIONS IF THEY
 ARE THE SAME SIZE AND ARE LOCATED IN THE SAME ZONE?
  
 8- GABLE END DETAIL ON SHEET ON SHEET S.2: NEED TO
 SPECIFY TWO WATER RESISTIVE BARRIERS WHEN STUCCO IS
 APPLIED TO WOOD AS REQUIRED BY SEC. R703.7.3
 FBC-RESIDENTIAL.
  
 9- WIND RESISTANCE OF EXTERIOR SOFFITS: PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE SOFFIT
 CONSTRUCTION SHOWING COMPLIANCE WITH SEC. R704
 FBC-RESIDENTIAL.
  
 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 WALL FLASHING AT ALL EXTERIOR OPENINGS.. SEC. R703.4
 FBC-RESIDENTIAL.
  
 11-FOUNDATION PLAN SHEET S.1:
 A)FOOTING DIMENSIONS AND REINFORCING SPECIFICATIONS FOR
 MF-24 SPECIFIED ON THE FOOTING SCHEDULE ARE INCORRECT.
 REVISE AS REQUIRED. SEC. R401.2 FBC-RESIDENTIAL.
  
 B)PROVIDE SPECIFICATIONS FOR FOOTING AT ENTRY PORCH
 COLUMNS. SEC. R401.2 FBC-RESIDENTIAL.
 NOTE: COORDINATE DETAIL 9/S.3 WITH FOOTINGS SHOWN ON
 THE FOUNDATION PLAN.
  
 12-ROOF FRAMING PLAN SHEET S.2: PROVIDE
 DETAIL/SPECIFICATIONS FOR CONNECTION OF ENTRY PORCH
 COLUMNS TO WOOD BEAM. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 13-PROVIDE DOOR AND WINDOW DOOR STRUCTURAL BUCK DETAIL
 SHOWING COMPLIANCE WITH SEC. R609.7.2.1
 FBC-RESIDENTIAL. SPECIFY STRUCTURAL BUCK SIZE AND
 FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 14- PROVIDE DETAILS AND SPECIFICATIONS FOR DECORATIVE
 SHUTTERS INSTALLATION. SPECIFY FASTENING. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 15- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS
 SPECIFYING R-30 ICYNENE SPRAY INSULATION. PROVIDE ICC
 EVALUATION REPORT FOR THE ICYNENE R-30 INSULATION TO
 VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 16-PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ENTRY WOOD DOOR AS SPECIFIED ON PLANS.
 B)WOOD FRENCH DOOR AS SPECIFIED ON PLANS.
 C)SINGLE HUNG WINDOWS.
 D)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
 E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 E)SHINGLES.
 F)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
  
 17- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 18- REVISE ENERGY CALCULATIONS:
 A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER NAME, BUILDER NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 B)ITEM #2 ON PAGE 1 IS INCORRECT. THIS IS A MULTIFAMILY
 BUILDING. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 C)ITEM #3 ON PAGE 1 IS INCORRECT. THIS IS A MULTIFAMILY
 BUILDING. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 D)CEILING R-VALUE INFORMATION ON PAGE 1 DOESN'T MATCH
 INFORMATION ON PLANS.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 E)WATER HEATER IS ELECTRIC NOT GAS. SEE PLANS AND
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 F) ROOF TYPE AND MATERIAL SPECIFIED ON SECOND PAGE IS
 INCORRECT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 19- VALUATION DECLARED IN THE PERMIT APPLICATION IS
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS OR
 PROVIDE COMPLETE COST BREAKDOWN INCLUDING DESIGN
 PROFESSIONAL FEES. VALUATION WAS UPDATED TO $288,952.
 OWES $367.14.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-02-15 Cont ID  
Sent By mpeterso Date 2023-02-15 Time 09:32 Rev Time 0.00
Received By mpeterso Date 2023-02-15 Time 09:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-11-04 Cont ID  
Sent By mpeterso Date 2022-11-04 Time 10:30 Rev Time 0.00
Received By mpeterso Date 2022-11-04 Time 10:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-09-08 Cont ID  
Sent By mpeterso Date 2022-09-08 Time 15:58 Rev Time 0.00
Received By mpeterso Date 2022-09-08 Time 15:58 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2023-03-15 Cont ID  
Sent By amhamilt Date 2023-03-15 Time 11:19 Rev Time 0.00
Received By amhamilt Date 2023-03-15 Time 11:19 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2023-01-24 Cont ID  
Sent By amhamilt Date 2023-01-24 Time 10:18 Rev Time 0.00
Received By amhamilt Date 2023-01-24 Time 10:18 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-11-30 Cont ID  
Sent By amhamilt Date 2022-11-30 Time 10:05 Rev Time 0.00
Received By amhamilt Date 2022-11-30 Time 10:05 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2022-09-14 Cont ID  
Sent By amhamilt Date 2022-09-14 Time 14:58 Rev Time 0.00
Received By amhamilt Date 2022-09-14 Time 14:58 Sent To  
Notes
2022-09-14 15:00:22THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PER HPB DECISION, PLEASE INDICATE ON WINDOW AND DOOR
 SCHEDULE/ELEVATIONS COMPLIANCE WITH THE FOLLOWING:
  
 1. ALL WINDOWS SHALL HAVE EXTERNAL, DIMENSIONAL MUNTINS
 WITH EITHER A PYRAMID OR
 OGEE PROFILE. ALL STREET OR SIDEWALK FACING GLASS SHALL
 BE CLEAR. ALL NON-STREET FACING
 GLASS SHALL BE CLEAR OR CLEAR WITH LOW E COATING.
 2. SHUTTERS WILL BE ADDED TO THE TWO LARGER SINGLE HUNG
 WINDOWS ON THE EAST ELEVATION.
 ALL SHUTTERS SHALL BE PROPORTIONATELY SIZED AND SHALL
 MEASURE THE FULL HEIGHT AND ONE HALF
 THE WIDTH OF THE WINDOW FRAME
  
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-03-15 Cont ID  
Sent By lmarchan Date 2023-03-15 Time 16:58 Rev Time 0.00
Received By lmarchan Date 2023-02-09 Time 15:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-03-01 Cont ID  
Sent By jgomez Date 2023-03-01 Time 11:05 Rev Time 0.00
Received By jgomez Date 2023-02-09 Time 07:07 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-25 Cont ID  
Sent By lmarchan Date 2023-01-25 Time 08:26 Rev Time 0.00
Received By lmarchan Date 2023-01-05 Time 11:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-02 Cont ID  
Sent By jgomez Date 2022-12-02 Time 19:11 Rev Time 0.00
Received By jgomez Date 2022-10-19 Time 16:10 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-27 Cont ID  
Sent By jgomez Date 2022-09-27 Time 19:02 Rev Time 0.00
Received By jgomez Date 2022-08-18 Time 06:20 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2023-06-23 Cont ID  
Sent By lmarchan Date 2023-06-23 Time 12:46 Rev Time 0.00
Received By lmarchan Date 2023-03-01 Time 16:33 Sent To  
Notes
2023-06-22 10:54:45RECEIPT - MU-2023-012439 - $8594.94 PAID
2023-03-01 16:33:383/1/23 EMAILED IMPACT OFFICE TO REVIEW PER JGOMEZ. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2022-12-02 Cont ID  
Sent By jgomez Date 2022-12-02 Time 17:36 Rev Time 0.00
Received By jgomez Date 2022-12-01 Time 13:28 Sent To  
Notes
2022-12-02 17:38:51PERMIT LIBRARIAN WILL EMAIL COUNTY TO REVIEW IMPACT
 FEES QUESTIONNAIRE AND EXISTING CREDIT FORM AFTER THE
 PERMIT IS APPROVED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-09-27 Cont ID  
Sent By jgomez Date 2022-09-27 Time 19:00 Rev Time 0.00
Received By jgomez Date 2022-09-27 Time 18:59 Sent To  
Notes
2022-09-27 19:01:40IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-11-03 Cont ID  
Sent By medwards Date 2022-11-03 Time 10:31 Rev Time 0.00
Received By medwards Date 2022-11-03 Time 10:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-08-26 Cont ID  
Sent By medwards Date 2022-08-26 Time 08:03 Rev Time 0.00
Received By medwards Date 2022-08-26 Time 08:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-10-21 Cont ID  
Sent By rwbrown Date 2022-10-21 Time 09:15 Rev Time 0.00
Received By rwbrown Date 2022-10-21 Time 09:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-08-23 Cont ID  
Sent By rwbrown Date 2022-08-23 Time 07:15 Rev Time 0.00
Received By rwbrown Date 2022-08-23 Time 07:15 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2022-12-02 Cont ID  
Sent By jgomez Date 2022-12-02 Time 19:09 Rev Time 0.00
Received By jgomez Date 2022-12-02 Time 19:09 Sent To  
Notes
2022-12-02 19:11:07NEED TO PROVIDE ALL ROOFING PRODUCT APPROVALS FOR
 REVIEW.
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-10-03 Cont ID  
Sent By jgomez Date 2022-10-03 Time 19:02 Rev Time 0.00
Received By jgomez Date 2022-10-03 Time 13:10 Sent To  
Notes
2022-10-03 13:12:07ROOFING REVIEW:
  
 1-PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)SHINGLES.
 B)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status P Date 2023-03-07 Cont ID  
Sent By jgomez Date 2023-03-07 Time 11:38 Rev Time 0.00
Received By jgomez Date 2023-03-07 Time 10:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status F Date 2023-03-06 Cont ID  
Sent By jgomez Date 2023-03-06 Time 17:26 Rev Time 0.00
Received By jgomez Date 2023-03-06 Time 17:26 Sent To  
Notes
2023-03-06 17:29:08SIGNATURE REVIEW:
  
 1- REVISED ENERGY CALCULATIONS HAVE A COPY OF THE
 ENGINEERS SEAL. IT DOESN'T HAVE THE SIGNATURE OF THE
 ENGINEER OF RECORD. NEED TO HAVE THE ORIGINAL
 SEAL/SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY
 SEC. 61G15-23.001 FAC AND CHAPTER 471 F.S. WHEN
 SUBMITTING PLANS/DOCUMENTS FOR PUBLIC RECORDS. THIS IS
 AN ELECTRONIC SUBMITTAL. SUBMIT PLANS/DOCUMENTS WITH
 ENGINEER'S VERIFIABLE DIGITAL SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2023-03-02 Cont ID  
Sent By jgomez Date 2023-03-02 Time 15:36 Rev Time 0.00
Received By jgomez Date 2023-03-02 Time 15:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-02-15 Cont ID  
Sent By mpeterso Date 2023-02-15 Time 09:44 Rev Time 0.00
Received By mpeterso Date 2023-02-15 Time 09:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-01-23 Cont ID  
Sent By jgomez Date 2023-01-23 Time 18:02 Rev Time 0.00
Received By jgomez Date 2023-01-23 Time 18:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-03 Cont ID  
Sent By medwards Date 2022-11-03 Time 10:31 Rev Time 0.00
Received By medwards Date 2022-11-03 Time 10:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-08-26 Cont ID  
Sent By medwards Date 2022-08-26 Time 08:03 Rev Time 0.00
Received By medwards Date 2022-08-26 Time 08:03 Sent To  
Notes
2022-08-26 08:04:16DESIGNER MUST DIGITALLY SIGN THE DRAWINGS. FS 471/481
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2023-03-15 Cont ID  
Sent By amhamilt Date 2023-03-15 Time 11:19 Rev Time 0.00
Received By amhamilt Date 2023-03-15 Time 11:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2023-01-24 Cont ID  
Sent By amhamilt Date 2023-01-24 Time 10:32 Rev Time 0.00
Received By amhamilt Date 2023-01-24 Time 10:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-11-30 Cont ID  
Sent By amhamilt Date 2022-11-30 Time 10:05 Rev Time 0.00
Received By amhamilt Date 2022-11-30 Time 10:05 Sent To  
Notes
2022-11-30 10:08:43PERMIT HAS PASSED
  
 ANY DRIVEWAYS, MECHANICAL, PAVING, FENCES, SITE WALLS,
 GENERATORS, POOLS AND LANDSCAPING TO BE DONE UNDER
 SEPARATE PERMITS.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-09-14 Cont ID  
Sent By ckimmerl Date 2022-09-14 Time 14:45 Rev Time 0.00
Received By amhamilt Date 2022-09-14 Time 14:44 Sent To  
Notes
2022-09-14 14:45:34THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 NEW CONSTRUCTION REQUIRES SUBMITTAL OF SEPARATE
 LANDSCAPE PERMIT PRIOR TO ZONING APPROVAL MOVING
 FORWARD, PLEASE APPLY FOR LANDSCAPE PERMIT.
  
 PLEASE ALSO INDICATE THAT ALL MECHANICAL EQUIPMENT WILL
 BE SCREENED AND ENCROACH NO MORE THAN 4FT INTO ANY
 SETBACK ON SITE PLAN.
  
 PLEASE ALSO INDICATE THAT ALL PAVERS/TIRE STRIPS WILL
 BE LOCATED AT LEAST 3 FT FROM SIDE LOT LINES (2FT AFTER
 FIRST 25 FT)
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  