Plan Review Stops For Permit 22011061 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
P |
Date |
2022-02-22 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2022-02-22 |
Time |
14:54 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2022-02-22 |
Time |
14:54 |
Sent To |
|
|
Notes |
2022-02-22 14:54:42 | ADDRESS CHANGED FROM 2015 WILKINS AVE A TO 2015 WILKINS | | AVE |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2022-02-15 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2022-02-15 |
Time |
16:59 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2022-02-15 |
Time |
16:59 |
Sent To |
|
|
Notes |
2022-02-15 17:00:40 | PLANS ARE SHOWING THE INCORRECT UNIT NUMBERS THE NORTH | | UNIT IS 2015 WILKINS AVE B AND THE SOUTH UNIT IS 2015 | | WILKINS AVE A, PLEASE UPDATE THE PLANS. UNIT NUMBERS | | NEED TO BE CHANGES TO AN UNIQUE ADDRESS AS UNITS HAVE | | THEIR OWN PARCEL NUMBER. PLEASE HAVE OWNER CONTACT | | [email protected] FOR THE UNITS TO BE GIVEN NEW ADDRESSES. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2022-04-18 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-04-18 |
Time |
17:36 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-04-18 |
Time |
17:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2022-03-30 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-03-30 |
Time |
18:21 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-03-30 |
Time |
10:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2022-04-12 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-04-12 |
Time |
07:47 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-04-12 |
Time |
07:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2022-02-28 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-02-28 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-02-28 |
Time |
13:53 |
Sent To |
|
|
Notes |
2022-02-28 14:23:14 | ELECTRIC REVIEW FAILED | | 1) PLEASE PROVIDE AN ELECTRIC LOAD CALCULATION FOR THE | | ENTIRE SERVICE (BOTH UNITS) NEC 215.5 | | 2) PLEASE ADD A NOTE STATING AFCI PROTECTION TO INCLUDE | | NEC 406.4 REQUIREMENTS | | 3) INCLUDE A NOTE CORRECTLY STATING COMPLIANCE WITH | | 210.8 GFCI PROTECTION | | 4) PLEASE DETAIL COMPLETE SCOPE OF ELECTRIC WORK. | | DETAIL ELECTRIC WORK TO BE REMOVED, REPLACED OR | | MODIFIED FBC 107.2 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-04-18 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-04-18 |
Time |
17:36 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-04-04 |
Time |
10:25 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2022-03-29 |
Time |
|
Rev Time |
0.00 |
Received By |
cdecoeur |
Date |
2022-02-11 |
Time |
06:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2022-04-11 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-04-11 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-04-11 |
Time |
09:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2022-02-15 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-02-15 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-02-15 |
Time |
15:41 |
Sent To |
|
|
Notes |
2022-02-15 15:45:40 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-22011061 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | THIS PERMIT APPLICATION AND PLAN REVIEW IS FOR UNIT B | | ONLY | | | | 1) THERE IS A MECH CHANGE OUT PERMIT FOR THIS PROJECT. | | THIS SHOULD BE CLOSED OUT AS IT DOES NOT APPLY NOW THAT | | THE COMPLETE SYSTEM IS BEING CHANGED OUT. THIS WILL | | REQUIRE A MECHANICAL SUB PERMIT FOR THIS MASTER PERMIT. | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS. | | | | 3) PLEASE SHOW THE DRYER EXHAUST DUCT MATERIAL, SIZE | | AND TERMINATION LOCATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2022-04-05 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2022-04-05 |
Time |
13:59 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2022-04-05 |
Time |
13:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2022-02-14 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2022-02-14 |
Time |
09:55 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2022-02-14 |
Time |
09:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2022-04-12 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-04-12 |
Time |
07:53 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-04-12 |
Time |
07:53 |
Sent To |
|
|
Notes |
2022-04-11 09:28:22 | MECHANICAL DIGITAL SIGNATURE APPROVED ME | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2022-03-29 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-03-29 |
Time |
12:56 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-03-29 |
Time |
12:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2022-04-20 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2022-04-20 |
Time |
12:37 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2022-04-20 |
Time |
12:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2022-04-11 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2022-04-11 |
Time |
10:11 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2022-04-11 |
Time |
10:11 |
Sent To |
|
|
Notes |
2022-04-11 10:14:20 | 4/11/2022 | | FAIL | | PLEASE APPLY FOR A LANDSCAPE PERMIT TO ALLOW STAFF TO | | MOVE FORWARD WITH THIS CONSTRUCTION REMODEL. | | | | | | ALEXIS SANGELEER | | ASSOCIATE PLANNER | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2022-02-18 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2022-02-18 |
Time |
16:59 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2022-02-18 |
Time |
16:59 |
Sent To |
|
|
Notes |
|
|